General
Description
The Central Model K11 ECLH, 11.2
K-Factor, Quick Response, Extended
Coverage Light Hazard (ECLH) Pen-
dent and Recessed Pendent Sprin-
klers are decorative glass bulb sprin-
klers designed for use in light hazard
occupancies such as churches, hos-
pitals, offices, and restaurants.
They are intended for use in automat-
ic sprinkler systems designed in ac-
cordance with standard installation
rules (e.g., NFPA 13) for the protec-
tion of light hazards up to a maxi-
mum coverage area of 400 ft2(37,2
m2), as compared to the maximum
coverage area of 225 ft2(20,9 m2)
for standard coverage sprinklers.
The recessed version of the Models
K11 ECLH Sprinklers using a two-
piece Series 4221 Recessed Es-
cutcheon provides up to 1/2 inch
(12,7 mm) of total adjustment from
the flush pendent position. The ad-
justment provided by the Recessed
Escutcheon reduces the accuracy to
which the fixed pipe drops to the
sprinklers must be cut.
Operation. The glass bulb contains
a fluid which expands when exposed
to heat. When the rated temperature
is reached, the fluid expands suffi-
ciently to shatter the glass bulb,
which then allows the sprinkler to ac-
tivate and flow water.
WARNINGS
The Model K11 ECLH Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association, in addition to
the standards of any other authori-
ties having jurisdiction. Failure to do
so may impair the integrity of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. The installing contractor or
sprinkler manufacturer should be
contacted relative to any questions.
Technical
Data
Sprinkler Identification Number
SIN C5232
Approvals
UL and C-UL Listed. FM Approved.
(Refer to Table A. The approvals ap-
ply only to the service conditions indi-
cated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 inch NPT or ISO 7-R3/4
Nominal Discharge Coefficients
K = 11.2 GPM/psi1/2
(161,3 LPM/bar1/2)
Temperature Ratings
135°F/57°C to 200°F/93°C
Finishes
Sprinkler: White Polyester, Chrome
Plated, Natural Brass
Recessed Escutcheon: White
Coated or Chrome Plated
(Other finishes are available on re-
quest.)
Physical Characteristics
The K11 ECLH utilizes a dezincifica-
tion resistant (DZR) bronze frame, a
brass button, and a 3 mm bulb. The
frame orifice is sealed with a gas-
keted spring plate (Belleville Seal)
consisting of a beryllium nickel disc
spring that is sealed on both its in-
side and outside edges with a Tef-
lon

gasket. The compression screw
is bronze, and the deflector is brass.
No. 2-6.1
K11 ECLH
Quick
Response
Pendent &
Rec. Pendent
Sprinklers
Model K11 ECLH
Quick Response
Extended Coverage
Light Hazard Sprinklers
Tyco Fire Products — www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Customer Services/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel. (800) 381-9312 / Fax: (800) 791-5500
CENTRAL K11 ECLH 2-01
OBSOLETE
Figure 1
Models K11 ECLH
Pendent Sprinklers
PLATE SEATING
ESCUTCHEON
SURFACE
(41.3 mm)
1-5/8"
1/2" (12.7 mm)
NOMINAL MAKE-IN
(61.9 mm)
2-7/16"
NPT
3/4"
WRENCH
FLAT
(BOTH SIDES)
Figure 2
Models K11 ECLH
Pendent Sprinklers
With Series 4221 Recessed Escutcheon
SPRINKLER FINISH
Temperature
Rating
Bulb
Color Code
Natural
Brass
Chrome
Plated
Polyester
Coated
(All Colors)
135°F/57°C
155°F/68°C
175°F/79°C
Red
Yellow
Orange
Pendent (C5232) Recessed (C5232) w/Series 4221 Escutcheon
1, 2, 3 1, 2, 3
Notes:
1. Listed by Underwriters Laboratories, Inc.
2. Listed by Underwriters Laboratories for use in Canada (i.e., C-UL Listed)
3. Approved by Factory Mutual Research Corporation.
Table A
Laboratory Listings and Approvals
(The laboratory listings and approvals only apply to the service conditions
indicated in the Design Criteria section.)
Natural
Brass
Chrome
Plated
Polyester
Coated
(All Colors)
1, 2
1, 2
1, 2, 3
1, 2
200°F/93°C Green 1, 2 1, 2
Lead
Coated
(73.0 mm)
2-7
/
8" DIA.
2-1/4" DIA.
(57.2 mm)
MOUNTING
SPRINKLER
SURFACE
CLOSURE
FACE OF
FITTING
(14.3±6.4 mm)
9/16±1/4"
MOUNTING
7/8" (22.2 mm)
1-3/8" (34.9 mm)
1/8"
(3.2 mm)
PLATE
FLUSH
1/2" (12.7 mm)
†
DuPont Registered Trademark
Figure 3
W-Type 3
Upright and Pendent
Sprinkler Wrench Figure 4
W-Type 5
Recessed Pendent
Sprinkler Wrench
"FITTIN
G
SIDE"
FITTING
TOWARDS SPRINKLER
RECESS
WRENCH
(END "B")
RECESS
2
WREN
C
H
1
OBSOLETE
Table B
UL and C-UL Listing Criteria for Installation of
K11 ECLH Pendent and Recessed Pendent Sprinklers
RESPONSE
COVERAGE AREA
WxL
FT. x FT. (m x m)
MINIMUM
FLOW
GPM (LPM)
MINIMUM
PRES.
PSI (BAR)
PENDENT
SPRINKLER
TEMP. RATING
°F
16 x 16 (4.9 x 4.9) 135, 155, 175, 20030 (114) 7.0 (0,48)
40 (151) 12.8 (0,88)
QUICK
135, 155, 175, 20018 x 18 (5.5 x 5.5)
20 x 20 (6.1 x 6.1)
8.2 (0,57)32 (121)
135, 155, 175, 200
NOTES:
(a) The K11 ECLH Sprinklers may be used in QR-EC Light Hazard Occupancy automatic sprinkler applications per NFPA 13.
(b) The K11 ECLH Sprinklers are only permitted to be used with unobstructed, smooth ceiling construction as defined by NFPA 13.
(c) Follow the requirements of NFPA 13 for spacing of the K11 ECLH Sprinklers with respect to ceiling mounted obstructions.
(d) The minimum allowable spacing between the K11 ECLH Sprinklers to prevent cold soldering is 8 feet (2,4 m).
(e) The maximum permitted ceiling slope for K11 ECLH Sprinklers is a 2 inch (50,8 mm) rise over a 12 inch (304,8 mm) horizontal run.
(f) The deflector-to-ceiling distance for the K11 ECLH Sprinklers is 1-5/8 to 12 inches (41,3 to 304,8 mm), unless the Series 4221 Recessed
Escutcheon is utilized.
RECESSED
SPRINKLER
TEMP. RATING
°F
135, 155, 175, 200
135, 155, 175
135, 175
TABLE C
FM Approval Criteria For Installation of
K11 ECLH Pendent and Recessed Pendent Sprinklers
RESPONSE
COVERAGE AREA
WxL
FT. x FT. (m x m)
MINIMUM
FLOW
GPM (LPM)
MINIMUM
PRES.
PSI (BAR)
PENDENT
SPRINKLER
TEMP. RATING
°F
16 x 16 (4.9 x 4.9) 135, 15530 (114) 7.0 (0,48)
40 (151) 12.8 (0,88)
QUICK
135, 15518 x 18 (5.5 x 5.5)
20 x 20 (6.1 x 6.1)
8.2 (0,57)32 (121)
135, 155
NOTES:
(a) The K11 ECLH Sprinklers may be used in QR-EC Light Hazard Occupancy automatic sprinkler system applications per FM installation
standards.
(b) The K11 ECLH Sprinklers are only permitted to be used with smooth level ceilings per FM installation standards.
(c) The minimum allowable spacing between the K11 ECLH Sprinklers to prevent cold soldering is 8 feet (2,4 m).
(d) The maximum permitted ceiling slope for K11 ECLH Sprinklers is a 1 inch (25,4 mm) rise over a 12 inch (304,8 mm) horizontal run.
(e) The deflector-to-ceiling distance for the K11 ECLH Sprinklers is 1-5/8 to 4 inches (41,3 to 101,6 mm), unless the Series 4221 Recessed
Escutcheon is utilized.
(f) The maximum ceiling height for the K11 ECLH Sprinklers is 10 feet (3,1 m).
RECESSED
SPRINKLER
TEMP. RATING
°F
135
135
135
Design Criteria
The Model K11 ECLH Sprinklers (SIN C5232) are only to be installed in accordance with Table B or C, as applicable.
Only the Series 4221 Recessed Escutcheon is to be used for recessed installations.
OBSOLETE
Installation
The Model K11 ECLH Sprinklers
must be installed in accordance with
the following instructions:
NOTES
Do not install any bulb type sprinkler
if the bulb is cracked or there is a
loss of liquid from the bulb. With the
sprinkler held horizontally, a small
air bubble should be present. The di-
ameter of the air bubble is approxi-
mately 1/16 inch (1,6 mm) for the
135°F/57°C to 200°F/93°C tempera-
ture ratings.
A leak tight 3/4 inch NPT sprinkler
joint should be obtained with a
torque of 10 to 20 ft.lbs. (13,4 to
26,8 Nm). A maximum of 30 ft.lbs.
(40,7 Nm) of torque is to be used to
install sprinklers. Higher levels of
torque may distort the sprinkler inlet
with consequent leakage or impair-
ment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in an Escutch-
eon Plate by under- or over-tighten-
ing the Sprinkler. Readjust the
position of the sprinkler fitting to suit.
Step 1. Model K11 ECLH Sprinklers
must be installed in the pendent posi-
tion and with the deflector parallel to
the mounting surface.
Step 2. After installing the Series
4221 mounting plate (or other es-
cutcheon, as applicable) over the
sprinkler pipe threads and with pipe
thread sealant applied to the pipe
threads, hand tighten the sprinkler
into the sprinkler fitting.
Step 3. Wrench tighten pendent
sprinklers using only the W-Type 3
(End B) Sprinkler Wrench. Wrench
tighten the recessed pendent sprin-
klers using only the W-Type 5 Sprin-
kler Wrench. The wrench recess of
the applicable sprinkler wrench
(Ref. Figure 3 and 4) is to be applied
to the sprinkler wrench flats (Ref. Fig-
ure 1).
Care &
Maintenance
The Model K11 ECLH Sprinklers
must be maintained and serviced in
accordance with the following instruc-
tions:
NOTES
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to operation in a fire
situation.
Before closing a fire protection sys-
tem main control valve for mainte-
nance work on the fire protection sys-
tem which it controls, permission to
shut down the affected fire protec-
tion systems must be obtained from
the proper authorities and all person-
nel who may be affected by this ac-
tion must be notified.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
shipped or stored where their tem-
perature will exceed 100°F/38°C and
they must never be painted, plated,
coated, or otherwise altered after
leaving the factory. Modified sprin-
klers must be replaced. Sprinklers
that have been exposed to corrosive
products of combustion, but have not
operated, should be completely
cleaned by wiping the sprinkler with
a cloth or by brushing it with a soft
bristle brush.
Care must be exercised to avoid
damage - before, during, and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/slip-
page, or the like, must be replaced.
Also, replace any sprinkler that has
a cracked bulb or that has lost liquid
from its bulb (Ref. Installation Sec-
tion).
The owner is responsible for the in-
spection, testing, and maintenance
of their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any
other authorities having jurisdiction.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under nor-
mal use and service. This warranty
will expire ten (10) years from date
of shipment by Tyco Fire Products.
No warranty is given for products or
components manufactured by com-
panies not affiliated by ownership
with Tyco Fire Products or for prod-
ucts and components which have
been subject to misuse, improper in-
stallation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with
applicable Standards of the National
Fire Protection Association, and/or
the standards of any other Authori-
ties Having Jurisdiction. Materials
found by Tyco Fire Products to be de-
fective shall be either repaired or re-
placed, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products
or parts of products. Tyco Fire Prod-
ucts shall not be responsible for
sprinkler system design errors or in-
accurate or incomplete information
supplied by Buyer or Buyer’s repre-
sentatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL
THEORY, FOR INCIDENTAL, INDI-
RECT, SPECIAL OR CONSEQUEN-
TIAL DAMAGES, INCLUDING BUT
NOT LIMITED TO LABOR
CHARGES, REGARDLESS OF
WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE POS-
SIBILITY OF SUCH DAMAGES,
ANDINNOEVENTSHALLTYCO
FIRE PRODUCTS’ LIABILITY EX-
CEED AN AMOUNT EQUAL TO THE
SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS
OR IMPLIED, INCLUDING WAR-
RANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICU-
LAR PURPOSE.
Ordering
Information
Ordering Information: When plac-
ing an order, indicate the full product
name. Please specify the quantity,
model, style, and size, as applicable.
Refer to Price List for complete list-
ing of Part Numbers.
Please Specify:
Model K11 ECLH Pendent Sprinkler.
W-Type 3 Sprinkler Wrench.
W-Type 5 Sprinkler Wrench.
Series 4221 Recessed Escutcheon.
Conversion Factors:
1ft.= 0.3048m
1 sq. ft. = 0.093 m2
1 gpm = 3.785 Lpm
1 psi = 0.06895 bar
1 gpm/ft2= 40.74 mm/min
Printed in U.S.A. 2-01
OBSOLETE

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product CENTRAL BV-EC User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV-EC User manual

Tyco Fire Product CENTRAL LD User manual

Tyco Fire Product

Tyco Fire Product CENTRAL LD User manual

Tyco Fire Product CENTRAL BVR-2 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BVR-2 User manual

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product Star Quasar Q User manual

Tyco Fire Product

Tyco Fire Product Star Quasar Q User manual

Tyco Fire Product CENTRAL RFII Series User manual

Tyco Fire Product

Tyco Fire Product CENTRAL RFII Series User manual

Tyco Fire Product Star Mizar S215 User manual

Tyco Fire Product

Tyco Fire Product Star Mizar S215 User manual

Tyco Fire Product CENTRAL ESLO User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESLO User manual

Tyco Fire Product CENTRAL TFP1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL TFP1 User manual

Tyco Fire Product Star SG-R User manual

Tyco Fire Product

Tyco Fire Product Star SG-R User manual

Tyco Fire Product Gem F685 User manual

Tyco Fire Product

Tyco Fire Product Gem F685 User manual

Tyco Fire Product Star Pulsar ESFR-1 User manual

Tyco Fire Product

Tyco Fire Product Star Pulsar ESFR-1 User manual

Tyco Fire Product CENTRAL DS-2 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL DS-2 User manual

Tyco Fire Product Gem F895 User manual

Tyco Fire Product

Tyco Fire Product Gem F895 User manual

Tyco Fire Product Star Pulsar S195 User manual

Tyco Fire Product

Tyco Fire Product Star Pulsar S195 User manual

Tyco Fire Product Gem ISSUE D QUARTZOID User manual

Tyco Fire Product

Tyco Fire Product Gem ISSUE D QUARTZOID User manual

Tyco Fire Product CENTRAL K17-231 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL K17-231 User manual

Tyco Fire Product CENTRAL ELO-16 GB FR User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-16 GB FR User manual

Tyco Fire Product EC-17 User manual

Tyco Fire Product

Tyco Fire Product EC-17 User manual

Tyco Fire Product SIN S3230 User manual

Tyco Fire Product

Tyco Fire Product SIN S3230 User manual

Tyco Fire Product Star Pulsar S160 User manual

Tyco Fire Product

Tyco Fire Product Star Pulsar S160 User manual

Tyco Fire Product Gem F960 User manual

Tyco Fire Product

Tyco Fire Product Gem F960 User manual

Tyco Fire Product CENTRAL Attic BB1-17/32 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Attic BB1-17/32 User manual

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR User manual

Popular Irrigation System manuals by other brands

Tyco TY-B Series manual

Tyco

Tyco TY-B Series manual

Toro ZSERIES 570Z brochure

Toro

Toro ZSERIES 570Z brochure

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Reliable F1-300 quick start guide

Reliable

Reliable F1-300 quick start guide

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Tyco CC3 manual

Tyco

Tyco CC3 manual

Reliable F4FR quick start guide

Reliable

Reliable F4FR quick start guide

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Reliable F1FR42 Series manual

Reliable

Reliable F1FR42 Series manual

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Johnson Controls tyco ESFR-17 manual

Johnson Controls

Johnson Controls tyco ESFR-17 manual

Reliable RFC30 LL manual

Reliable

Reliable RFC30 LL manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.