  9. Tyco Fire Product CENTRAL Omega HEC-12 User manual

Tyco Fire Product CENTRAL Omega HEC-12 User manual

OmegaHEC-12
Product
Description
The Omega Model HEC-12
sprinkler is an extremely versatile
horizontal sidewall sprinkler. It is a
low profile, aesthetically pleasing,
wall mounted sprinkler that operates
five to six times faster than a
standard sprinkler. It offers a high
degree of protection for human life
and features a spray pattern that has
been shown to be effective in the
control or extinguishment of fire.
The Model HEC-12 carries a
Listing* by Underwriters Laboratories
for use as a Quick Response
Sprinkler that is listed for installation
in light hazard and ordinary hazard
occupancies in accordance with
current NFPA 13 Standards.
The Model HEC-12 is available in
three standard finishes, chrome
plated, brass plated and white
painted. Its mating escutcheon plate
is available in three standard finishes,
chrome plated, brass plated and
white painted, with additional special
finishes available upon request.
Operation: A fusible alloy pellet is
compressed with a bearing disc into a
copper housing by a ball plunger.
Heat is absorbed by the heat
collecting fins and conducted to the
alloy pellet. At the rated temperature
the alloy melts, causing the ball
plunger to drop, freeing balls from the
retaining groove. This movement
allows system water pressure to force
the orifice sealing mechanism and
deflector assembly open. Water is
then discharged in a designed flow
pattern.
HEC-12 8-92
QuickResponse
HorizontalSidewallSprinkler
* For specific listing requirements see the appropriate
information contained in this brochure.
1⁄2"Orifice
Horizontal
Sidewall
Automatic
Sprinkler
Technical
Data
Manufactured by: Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Model: HEC-12
Style: Horizontal Sidewall
Orifice Size: 1/2"
(12.7 mm)
K Factor: 5.6
(80.08)
Thread Size: 1/2" N.P.T.
Temperature Rating: 145°F/63°C
160°F/71°C
200°F/93°C
Approvals: U.L., U.L.C., M.E.A.
(Cal. No. 375-75-SA)
Maximum Working Pressure: 175 psi
Factory Hydro Test: 100% at 500 psi
Standard Finishes:
Sprinkler: chrome plated, brass
plated and white
painted
Escutcheon: chrome plated, brass
plated and white
painted
Length: 2 3/8"
(60.33 mm)
Width: 1 3/8"
(34.9 mm)
Weight: 4.5 oz.
(127.6 grams)
No. 1-5.0
OBSOLETE
2
Installation Diagram
Omega HEC-12 Horizontal Sidewall Sprinkler
Omega HEC Sprinkler Wrench
(Part #15932000)
1" Supply Pipe
Finished
Ceiling Line
1" x 1/2" Reducing
Coupling (N.P.T.)
Finished
Wall Line
1"±1/8"
4" to 12"
Note: Use this flange for field
installation. Use Central's Omega
Sidewall Sprinkler Wrench. DO
NOT “WRENCH” DEFLECTOR.
Escutcheon
5/8"
±1/8"
1/2"
Face of Coupling 2 1/4" Dia. Max.
2" Dia. Min.
OBSOLETE
3
Special care must be taken when
installing with a copper system.
Sprinklers must be installed only after
the inside of the sprinkler nipple and
associated fittings have been wire
brushed to remove any flux. Residual
flux can cause corrosion and in
extreme cases can impair proper
sprinkler operation.
Design
Data
In Quick Response applications, Model HEC-12 145°F, 160°F and 200°F rated
sprinklers are intended for standard area coverages and standard flow and
pressure requirements as specified in current NFPA 13 Standards. They are
listed for use in ordinary and light hazard occupancies installed with the
deflector from 4" to 12" below the ceiling.
Design Requirements — Quick Response Applications
* Teflon is a trademark of the DuPont Corp.
Care &
Maintenance
Sprinklers must be handled
carefully. They must not be
transported or stored where ambient
temperatures may exceed 100°F/
38°C. For best results, store them in
a cool, dry location in the original
shipping package.
Do not install sprinklers that have
been dropped or visibly damaged.
Sprinklers must never be painted,
coated, plated, or altered in any other
way from manufactured condition or
they may not function properly. Any
sprinklers altered in such manner
must be replaced.
The owner is responsible for the
proper working condition of all fire
protection devices and accessories.
The NFPA Standard 25 entitled,
“Inspection, Testing and Maintenance
of Water-Based Fire Protection
Systems
”, contains guidelines and
minimum maintenance requirements.
Furthermore, the local
Authority
Having Jurisdiction
may have
additional regulations and
requirements for maintenance,
testing, and inspection that must be
obeyed.
It is advisable to have sprinkler
systems inspected regularly by a
qualified inspection service. Length
of time between such inspections can
vary due to accessibility, ambient
atmosphere, water supply, and site
activity.
Do not attempt to re-assemble or
otherwise reuse a sprinkler that has
operated. Replace any sprinkler
exhibiting corrosion or damage;
always use new sprinklers of the
same type and temperature rating as
replacements.
Installation
Model HEC-12 sprinklers must be
installed in accordance with current
NFPA 13 Standards. Deviations from
these requirements and standards or
any alteration to the sprinkler itself
will void any warranty made by
Central Sprinkler Company. In
addition, installation must also meet
local government provisions, codes,
and standards as applicable.
The system piping must be properly
sized to ensure the minimum required
flow rate from the sprinkler.
Prior to installation, check for
proper model, style, orifice size, and
temperature rating. Install sprinklers
after the piping is in place to avoid
mechanical damage; replace any
damaged unit. Wet pipe systems
must be protected from freezing.
Upon completion of the installation,
the system must be tested per
recognized standards.
In the event of a thread leak,
remove the unit, apply new pipe joint
compound or tape, and reinstall.
Installation Sequence
Step 1. The unit must be installed in
the horizontal position.
Step 2. The face of the sprinkler
fitting should be installed 1" (±1/8")
behind the finished wall line.
Adjustments are made via the
adjustable sliding escutcheon plate to
compensate for variations in the
fittings.
The sprinkler will function properly,
only when the system piping is
anchored to the building structure.
Otherwise, reaction forces from
system initiation could alter the
sprinkler alignment and disrupt the
distribution pattern.
Step 3. Use only a non-hardening
pipe joint compound or Teflon* tape.
Apply to the male threads only.
Step 4. Hand tighten the sprinkler
into the fitting. Use an Omega HEC
sprinkler wrench to tighten the
assembly into the fitting. A leak tight
joint requires the application of only
7-14 ft.-lbs. of torque. A tangential
force of 14-28 lbs. delivered through
a 6" long rachet handle will deliver
adequate torque. Torque levels over
21 ft.-lbs may distort the orifice seal,
resulting in leakage.
Step 5. To install the escutcheon
plate, align it with and press it over
the sprinkler body until the outer edge
of the escutcheon meets the
mounting surface.
Do not over or under tighten the
sprinkler to compensate for
inaccurate escutcheon plate
adjustment.
Caution: Special care must be
taken when installing with a CPVC
system. Sprinklers must be installed
after the CPVC manufacturer's
recommended setting time for the
primer and cement to ensure that
neither accumulate within the
sprinkler.
OBSOLETE
©1992 Central Sprinkler Company
Printed in U.S.A.
Ordering
Information
When placing an order, indicate the
full product name. Specify the
quantity, model, style, orifice size,
temperature rating, type of finish,
escutcheon plate finish, and sprinkler
wrench.
For special painted escutcheon
finishes, the customer must provide
paint in a quick-drying or lacquer-
base finish to insure proper color
duplication. Without such a guide,
Central Sprinkler Company cannot be
responsible for acceptable color
matching.
Availability and Service: Central
sprinklers, valves, accessories, and
other products are available
throughout the U.S. and Canada, and
internationally, through a network of
Central Sprinkler distribution centers.
You may write directly to Central
Sprinkler Company or call 215-362-
0700 for the distributor nearest you.
Conversion Table:
1 inch = 25.400 mm
1 foot = 0.3048 M
1 pound = 0.4536 kg
1 foot pound = 1.36 Nm
1 psi = 6.895 Kpa
= 0.0689 bar
= 0.0703 kg/cm2
1 U.S. gallon = 3.785 dm3
= 3.785 liters
Conversions are approximate.
Because the discharge pattern is
critical to protection of life and
property, nothing should be hung or
attached to the sprinkler unit that
would disrupt the pattern. Such
obstructions must be removed. In the
event that construction has altered
the original configuration, additional
sprinklers may need to be installed to
maintain the protection level.
Do not attempt to replace sprinklers
without first removing the fire
protection system from service. Be
certain to secure permission from all
authorities having jurisdiction, and
notify all personnel who may be
affected during system shutdown. A
fire watch during maintenance
periods is a recommended
precaution.
To remove the system from service
mode, first refer to the system
operating guide and valve
instructions. Drain water and relieve
pressure in the pipes. Remove the
existing unit and install the
replacement, using only the
recommended sprinkler wrench. Be
certain to match model, style, orifice,
and temperature rating.
Guarantee: Central Sprinkler
Company will repair and/or replace
any product found to be defective in
material or workmanship within a
period of one year from date of
shipment. Please refer to the current
Price List for further details of the
warranty.
Central Sprinkler Company
451 N. Cannon Avenue, Lansdale, PA 19446
Phone (215) 362-0700
FAX (215) 362-5385
HEC-12.2
OBSOLETE

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product Gem F892QR User manual

Tyco Fire Product

Tyco Fire Product Gem F892QR User manual

Tyco Fire Product Gem F892X User manual

Tyco Fire Product

Tyco Fire Product Gem F892X User manual

Tyco Fire Product CENTRAL Omega HEC-12 PRO Prohibitor User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Omega HEC-12 PRO Prohibitor User manual

Tyco Fire Product CENTRAL K11 ECOH User manual

Tyco Fire Product

Tyco Fire Product CENTRAL K11 ECOH User manual

Tyco Fire Product TFR MAX User manual

Tyco Fire Product

Tyco Fire Product TFR MAX User manual

Tyco Fire Product Star Pulsar S160QR User manual

Tyco Fire Product

Tyco Fire Product Star Pulsar S160QR User manual

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product Star SG-R User manual

Tyco Fire Product

Tyco Fire Product Star SG-R User manual

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product CC1 User manual

Tyco Fire Product

Tyco Fire Product CC1 User manual

Tyco Fire Product CENTRAL WS User manual

Tyco Fire Product

Tyco Fire Product CENTRAL WS User manual

Tyco Fire Product Star Quasar Q User manual

Tyco Fire Product

Tyco Fire Product Star Quasar Q User manual

Tyco Fire Product central bvr User manual

Tyco Fire Product

Tyco Fire Product central bvr User manual

Tyco Fire Product Gem G102 User manual

Tyco Fire Product

Tyco Fire Product Gem G102 User manual

Tyco Fire Product CENTRAL BV-EC User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV-EC User manual

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product CENTRAL ELO-16 GB FR User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-16 GB FR User manual

Tyco Fire Product Gem F960 User manual

Tyco Fire Product

Tyco Fire Product Gem F960 User manual

Tyco Fire Product CENTRAL H17/32 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL H17/32 User manual

Tyco Fire Product Star Pulsar ESFR-1 User manual

Tyco Fire Product

Tyco Fire Product Star Pulsar ESFR-1 User manual

Tyco Fire Product Gem F898 User manual

Tyco Fire Product

Tyco Fire Product Gem F898 User manual

Tyco Fire Product CENTRAL RFII Series User manual

Tyco Fire Product

Tyco Fire Product CENTRAL RFII Series User manual

Tyco Fire Product Star E User manual

Tyco Fire Product

Tyco Fire Product Star E User manual

Popular Irrigation System manuals by other brands

Tyco TY-B Series manual

Tyco

Tyco TY-B Series manual

Toro ZSERIES 570Z brochure

Toro

Toro ZSERIES 570Z brochure

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Reliable F1-300 quick start guide

Reliable

Reliable F1-300 quick start guide

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Tyco CC3 manual

Tyco

Tyco CC3 manual

Reliable F4FR quick start guide

Reliable

Reliable F4FR quick start guide

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Reliable F1FR42 Series manual

Reliable

Reliable F1FR42 Series manual

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Johnson Controls tyco ESFR-17 manual

Johnson Controls

Johnson Controls tyco ESFR-17 manual

Reliable RFC30 LL manual

Reliable

Reliable RFC30 LL manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.