
Printed in U.S.A. 2-01
Ordering Information: When
placing an order, indicate the full
product name. Please specify the
quantity, model, style, orifice size,
temperature rating, type of finish or
coating, and sprinkler wrench. Refer
to price list for complete listing of Part
Numbers.
Patents: U.S.A. Patent Number
4,014,388 is applicable to the Model
BV4-QREC ECLH Concealed
Pendent Sprinklers. Other Patents
are pending with regard to other
design features.
Teflon is a trademark of the DuPont Corp.
Ordering
Information
Flow Control
Tyco Fire
Products
The Model BV4-QREC ECLH Concealed
Pendent Sprinklers must be maintained
and serviced in accordance with the
following instructions.
NOTES
Absence of the Cover Plates which is
used to cover a clearance hole, may delay
the time to operation in a fire situation.
When properly installed, there is a
nominal 3/32 inch (2,4 mm) air gap
between the lip of the Cover Plate and the
ceiling. This air gap is necessary for
proper operation of the sprinkler. If the
ceiling is to be repainted after the
installation of the sprinkler, care must be
exercised to ensure that the new paint
does NOT seal off any of the air gap.
Factory painted Cover Plates MUST NOT
be repainted. They should be replaced, if
necessary, by factory painted units.
Do not pull the Cover Plates relative to the
Retainer Assembly. Separation may
result.
Before closing a fire protection system
main control valve for maintenance work
on the fire protection system it controls,
permission to shut down the affected fire
protection systems must be obtained from
the proper authorities. All personnel who
may be affected by this action must be
notified.
Sprinklers which are found to be leaking
or exibiting visible signs of corrosion must
be replaced.
Automatic sprinklers must never be
shipped or stored where their tempera-
tures will exceed 100°F/38°C and they
must never be painted, plated, coated or
otherwise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced if
they cannot be completely cleaned by
wiping the sprinkler with a cloth or by
brushing it with a soft bristle brush.
Care must be exercised to avoid damage
- before, during, and after installation.
Sprinklers damaged by dropping, striking,
wrench twist/slippage, or the like, must be
replaced. Also, replace any sprinkler that
has a cracked bulb or that has lost liquid
from its bulb (Ref. Installation Section).
If a sprinkler must be removed for some
reason, do not reinstall it or a replacement
without reinstalling the Cover Plate
Assembly. If a Cover Plate Assembly
becomes dislodged during service,
replace it immediatly.
The owner is responsible for the inspec-
tion, testing, and maintenance of their fire
protection system and devices in
compliance with this document, as well as
with the applicable standards of the
National Fire Protection Association (e.g.,
Care &
Maintenance
NFPA 25), in addition to the standards of
any other authorities having jurisdiction.
The installing contractor or sprinkler
manufacturer should be contacted relative
to any questions.
It is recommended that automatic sprinkler
systems be inspected, tested, and
maintained by a qualified Inspection
Service.
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years against
defects in material and workmanship
when paid for and properly installed and
maintained under normal use and
service. This warranty will expire ten
(10) years from date of shipment by
Tyco Fire Products. No warranty is
given for products or components
manufactured by companies not
affiliated by ownership with Tyco Fire
Products or for products and compo-
nents which have been subject to
misuse, improper installation, corrosion,
or which have not been installed,
maintained, modified or repaired in
accordance with applicable Standards
of the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Materi-
als found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither
assumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL
THEORY, FOR INCIDENTAL, INDI-
RECT, SPECIAL OR CONSEQUEN-
TIAL DAMAGES, INCLUDING BUT
NOT LIMITED TO LABOR CHARGES,
REGARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS'
LIABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR
PURPOSE.
Limited
Warranty