Tyco RM-1 User manual

Model RM-1
Riser Manifold
Commercial and Residential
Page 1 of 8 AUGUST 2021 TFP963
Worldwide
Contacts
www.tyco-fire.com
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
General
Description
The TYCO commercial and residential
Model RM-1 Riser Manifold provide
the necessary waterflow alarm, pres-
sure gauge, alarm test orifice, drain,
and sight glass equipment in a single
assembly for use in NFPA 13 com-
mercial sprinkler systems and in NFPA
13D/13R residential sprinkler systems
as follows:
NFPA 13*
• 1-1/2 in. (DN40)
Male Thread x Female Thread
• 2 in.– 6 in. (DN50 – DN150)
Groove x Groove
NFPA 13D
• 1 in. (DN25)
Female Thread x Female Thread
NFPA 13R
• 1-1/2 in. (DN40)
Male Thread x Female Thread
• 2 in. (DN50)
Groove x Groove
* Although the Riser Manifold described in this techni-
cal data sheet is intended for NFPA 13 sprinkler sys-
tems, it may be used for NFPA 13D or 13R residential
sprinkler systems, where a test orice of 2.8K or 4.2K
is acceptable.
The variety of sizes and grooved end
connections allow cost effective and
easy transition to check valves, control
valves, and system piping. The Model
RM-1 Riser Manifolds may be installed
either horizontally (flow switch on top)
or vertically (flow going up) orientation,
for both single sprinkler rises and floor
control in high-rises.
Optional Pressure Relief Kits feature a
175 psi pressure relief valve and trim
components for convenient integration
into commercial and residential riser
manifold assemblies.
The pressure relief valve, installed in
manifold assemblies above the nor-
mally closed test and drain or drain
valve, automatically bleeds system
pressure exceeding 175 psi through a
flexible hose connected to the mani-
fold drain outlet (Ref. Figure 5), reduc-
ing system pressure to 175 psi.
NOTICE
The Model RM-1 Riser Manifolds
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of the NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA),
in addition to the standards of any other
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Technical
Data
Approvals
UL and ULC Listed
FM Approved
Listed by California State Fire Marshall
Maximum Working Pressure
300 psi (20,7 bar)
Friction Loss
See Table A
Test Orifice
1 in.– 3 in. (DN25 – DN80) Manifolds: 2.8K
4 in.– 6 in. (DN100 – DN150) Manifolds: 4.2K
Finish
Red Painted

TFP963
Page 2 of 8
Nominal
Riser
Size
Inches
(DN)
End
Connections
Nominal Dimensions
Inches
(mm)
Nominal
Drain
Size
Inches
(DN)
Inlet Outlet A B C D E F G H
1-1/2
(40)
Thread
MNPT
Thread
FNPT
10
(254)
15-1/2
(394)
2-1/4
(57)
5-5/8
(143)
8-3/8
(213)
15
(381)
4-3/8
(111)
1-1/4
(32)
2
(50) Groove Groove 13
(330)
18
(457)
2-1/16
(53)
5-5/8
(143)
8-3/8
(213)
15-1/4
(388)
4-3/8
(111)
1-1/4
(32)
2-1/2
(65) Groove Groove 13
(330)
18-1/16
(460)
2-1/16
(53)
5-5/8
(143)
8-3/8
(213)
15-1/4
(388)
4-3/8
(111)
1-1/4
(32)
3
(80) Groove Groove 13
(330)
18-1/16
(460)
2-1/16
(53)
5-7/8
(150)
8-5/8
(219)
15-3/4
(400)
4-3/8
(111)
1-1/4
(32)
4
(100) Groove Groove 13
(330)
20 -1/4
(514)
4-1/4
(108)
6-3/4
(172)
10-3/4
(273)
18-3/8
(467)
5-3/16
(132)
2
(50)
6
(150) Groove Groove 13
(330)
20 -1/4
(514)
4-1/4
(108)
7-3/4
(197)
11-3/4
(300)
21
(533)
6-3/4
(172)
2
(50)
NO DESCRIPTION P/N
1 300 psi/2000 kPa
Water Pressure Gauge . . 90050001
2 Test and Drain Valve,
Model TD-1:
1-1/2 – 3 Inch
(DN40 – DN80)
Size Manifolds,
1-1/4”, 2.8K Orice.....A61G0420
4 – 6 Inch
(DN100 – DN150)
Size Manifolds,
2”, 4.2K Orice ........A61G0601
3 Flow Switch, VSR-M:
1-1/2” (DN40) .........91144815
2” (DN50) ............91144802
2-1/2” (DN65) .........91144825
3” (DN80) ............91144803
4” (DN100) ...........91144804
6” (DN150) ...........91144806
4 Field Replaceable
Retard/Switch.........91144800
G
E
F
H
2
D
INLET
OUTLET
A
C
3, 4
FLOW
1
B
OPTIONAL
PRESSURE
RELIEF TRIM
CONNECTION
FIGURE 1
MODEL RM-1 COMMERCIAL RISER MANIFOLDS
1-1/2 – 6 INCH (DN40 – DN150)

TFP963
Page 3 of 8
NO DESCRIPTION P/N
1 300 psi/2000 kPa
Water Pressure Gauge . . 90050001
2 Ball Valve, 1” (DN25)....97111603
3 Flow Switch, VSR-M,
1” (DN25) ............91144801
4 Field Replaceable
Retard/Switch.........91144800
NO DESCRIPTION P/N
1 300 psi/2000 kPa
Water Pressure Gauge . . 90050001
2 Ball Valve, 1” (DN25)....97111603
3 Flow Switch, VSR-M,
1-1/2” (DN40) .........91144815
4 Field Replaceable
Retard/Switch.........91144800
FLOW
1" NPT
(FEMALE)
2-1/2"
(64 mm)
3-7/8"
(100 mm)
10-1/8"
(257 mm)
4-5/8"
(118 mm)
3-3/4"
(96 mm)
1"
NPT
DRAIN
10"
(254 mm)
2
1" NPT
(FEMALE)
3, 4
11"
(280 mm)
1
OPTIONAL
PRESSURE
RELIEF TRIM
CONNECTION
3-7/8"
(100 mm)
10"
(254 mm)
1-1/2" NPT
(MALE)
7/16"
(11 mm)
1-1/2" NPT
(FEMALE)
4-3/4"
(121 mm)
3-7/8"
(100 mm)
1
FLOW
2
3, 4
11-3/8"
(290 mm)
13-1/4"
(337 mm)
OPTIONAL
PRESSURE
RELIEF TRIM
CONNECTION
1"
NPT
DRAIN
FIGURE 2
MODEL RM-1 RESIDENTIAL RISER MANIFOLD
1 INCH (DN25)
FIGURE 3
MODEL RM-1 RESIDENTIAL RISER MANIFOLD
1-1/2 INCH (DN40)

TFP963
Page 4 of 8
Manifold
Installation
TYCO Model RM-1 Riser Manifold
must be installed in accordance with
this section.
The Model RM-1 Riser Manifold may be
installed either horizontally (flow switch
on top) or vertically (flow going up). The
inlet of the Riser Manifold may be con-
nected directly to a shut-off control
valve.
Notes:
Where applicable pipe thread sealant
is to be applied sparingly. Use of a
non-hardening pipe thread sealant is
recommended.
Never remove any piping component
nor correct or modify any piping defi-
ciencies without first depressurizing
and draining the system.
Provisions for an alarm test flow on
Residential Models must be made.
The alarm test flow is to be through
an orifice having a flow capacity equal
to or smaller than the smallest orifice
sprinkler in the system. One of two
options can be considered. The first
option is to temporarily install a test
orifice in the outlet of the drain line
prior to performing the alarm test. The
second option is to install an Inspec-
tor’s Test Connection downstream of
the Waterflow Alarm Switch.
Step 1. Install the manifold body with
the flow arrow pointing in the down-
stream position using threaded con-
nections and/or listed mechanical
grooved connections, as applicable.
Step 2. Connect the drain line and on
commercial manifolds set the Model
TD-1 Test and Drain Valve to the OFF
position or on residential manifolds
close the drain valve.
Step 3. Refer to Figure 6 for wiring
guidance. All wiring must be performed
in accordance with the authority having
jurisdiction and/or the National Electri-
cal Code.
Step 4. Refer to Figure 5 for Optional
Pressure Relief Trim installation.
Step 5. Place the system in service
by filling the system with water. When
filling the system, partially open the
control valve to slowly fill the system.
Filling the system slowly will help avoid
damaging the waterflow alarm switch.
After the system is fully pressurized,
completely open the control valve.
Step 6. Secure all supply valves open.
NO DESCRIPTION P/N
1 300 psi/2000 kPa
Water Pressure Gauge . . 90050001
2 Ball Valve, 1” (DN25)....97111603
3 Flow Switch, VSR-M,
2” (DN50) ............91144802
4 Field Replaceable
Retard/Switch.........91144800
3-7/8"
(100 mm)
1/2"
(13 mm)
5"
(127 mm)
4-1/8"
(105 mm)
2"
(GROOVED)
2"
(GROOVED)
13"
(330 mm)
2
3, 4
1
FLOW
11-7/8"
(300 mm)
16"
(406 mm)
OPTIONAL
PRESSURE
RELIEF TRIM
CONNECTION
1"
NPT
DRAIN
FIGURE 4
MODEL RM-1 RESIDENTIAL RISER MANIFOLD
2 INCH (DN50)

TFP963
Page 5 of 8
Optional
Pressure
Relief Trim
Installation
Model RM-1 commercial and resi-
dential riser manifold assemblies are
designed to accommodate an optional
pressure relief valve and trim compo-
nents (Ref. Figure 5).
Optional pressure relief trim must be
installed in accordance with the follow-
ing procedures.
Notes:
For assembly in Riser Manifolds
installed and in service, verify the fire
protection system is de-pressurized
and drained. Close the system supply
control valve, set commercial manifold
test and drain valve to DRAIN or open
residential drain valve to relieve resid-
ual pressure and drain system. Make
certain that drainage water will not
cause any damage or injury.
Refer to Care and Maintenance section
for other requirements when closing a
fire protection system control valve and
placing system in service.
Apply thread sealant or TEFLON tape
on all threaded connections, with the
exception of internally sealed flexible
hose connections.
Commercial Manifolds
Refer to Figure 1 for commercial riser
manifold features and Figure 5 for pres-
sure relief trim components described
in this procedure.
Step 1. Remove 1/2 in. pipe plug from
manifold tee. Inspect exposed female
tee threads, remove thread sealant
remnants or debris as necessary.
Step 2. Install Pressure Relief Valve (1)
in manifold tee, orienting valve outlet
port perpendicular to and facing away
from manifold body.
Step 3. Install 1/2 in. x Close Nipple
(2) in pressure relief valve outlet port.
Step 4. Disconnect drain piping from
grooved outlet of manifold TD-1 test
and drain valve as applicable and install
Figure 323 Grooved Reducing Tee (4)
on valve outlet by securing with Fig-
ure 577 Grooved Coupling (5), align-
ing tee threaded branch outlet parallel
with pressure relief valve outlet port.
Reconnect drain piping to Figure 323
tee drain outlet as necessary.
Note: Refer to Technical Data Sheet
G901 for Figure 577 Grooved Coupling
installation and assembly instructions.
Step 5. Install Flexible Hose (3) by
threading female ends onto 1/2 in. x
close nipple installed on relief valve
outlet port and onto Figure 323 reduc-
ing tee branch outlet.
Note: Assure Flexible Hose is not sus-
ceptible to being caught or snagged by
other moving equipment.
Residential Manifolds
Refer to Figures 2, 3 or 4 for residen-
tial riser manifold features and Figure
5 for pressure relief trim components
described in this procedure.
Step 1. Remove 1/2 in. pipe plug from
manifold tee. Inspect exposed female
tee threads, remove thread sealant
remnants or debris as necessary.
Step 2. Install Pressure Relief Valve (1)
in manifold tee, orienting valve outlet
port perpendicular to and facing away
from manifold body.
Step 3. Disconnect drain piping from
threaded outlet of manifold drain valve
as applicable and install 1 in. x Close
Nipple (5) in valve outlet.
Step 4. Install Figure 815 Reducing
Tee (4) onto 1 inch x close nipple, align-
ing tee branch outlet parallel with pres-
sure relief valve outlet port. Reconnect
drain piping to Figure 815 tee drain out-
let as necessary.
Step 5. Install 1/2 in. x Close Nipples
(2) in pressure relief valve outlet port
and in Figure 815 reducing tee branch
outlet.
Step 6. Install Flexible Hose (3) by
threading female ends onto 1/2 in. x
close nipples installed on relief valve
outlet port and Figure 815 reducing tee
branch outlet.
Note: Assure Flexible Hose is not sus-
ceptible to being caught or snagged by
other moving equipment.
Residential Riser Manifolds
NO DESCRIPTION P/N
1 Pressure Relief Valve,
175 psi, 1/2” NPT ..........1001184-01
2 1/2” x Close Nipple, Qty 2 . . . 1001023-01
3 Flexible Hose, 1/2” x 16” . . . . 1001266-03
4 Figure 815 Threaded
Reducing Tee,
1” x 1” x 1/2” NPT .........1001259-07
5 1” x Close Nipple . . . . . . . . . . 1001025-01
Commercial Riser Manifolds
NO DESCRIPTION P/N
1 Pressure Relief Valve,
175 psi, 1/2” NPT ..........1001184-01
2 1/2” x Close Nipple ........1001023-01
3 Flexible Hose:
1-1/2 – 3 Inch (DN40 – DN80)
Size Manifolds,
1/2” x 24” ................1001266-02
4 – 6 Inch (DN100 – DN150)
Size Manifolds,
1/2” x 30” ................1001266-01
4 Figure 323 Reducing Tee,
Grooved x NPT Threaded:
1-1/2 – 3 Inch (DN40 – DN80)
Size Manifolds,
1-1/4” x 1-1/4” x 1/2”.......3231305GS
4 – 6 Inch (DN100 – DN150)
Size Manifolds,
2” x 2” x 1/2” .............3232005GS
5 Figure 577 Rigid Grooved
Coupling:
1-1/2 – 3 Inch (DN40 – DN80)
Size Manifolds,
1-1/4” ...................57713AGCP
4 – 6 Inch (DN100 – DN150)
Size Manifolds,
2” ......................57720AGCP
3
4
5
MODEL RM-1
COMMERCIAL
RISER MANIFOLD
1
2
MODEL RM-1
RESIDENTIAL
RISER MANIFOLD
1
3
2
5
4
2
FIGURE 5
MODEL RM-1 COMMERCIAL AND RESIDENTIAL RISER MANIFOLDS
OPTIONAL PRESSURE RELIEF TRIM INSTALLATION

TFP963
Page 6 of 8
NOTE:
NOTE:
CONTACT RATINGS:
SWITCH TERMINAL CONNECTIONS
IMPROPER CONNECTION METHOD PROPER CONNECTION METHOD
CAUTION:
For supervised circuits, see "Switch Terminal Connections" above. The Waterow Alarm
Switch has two switches, one can be used to operate a central station, proprietary or remote
signaling unit, while the other contact is used to operate a local audible or visual annunciator.
When connecting to a
UL Listed control panel,
use panel resistor rating
for circuit supervision
Two sets of SPDT (Form C)
10.0 Amps at 125/250VAC
2.0 Amps at 30VDC Resistive
10 mAmps min. at 24VDC
An uninsulated section of a
single conductor is not
permitted to be looped around
the terminal and serve as two
separate connections. The
wire must be severed to serve
as two separate connections,
thereby providing supervision
of the connection in the event
that the wire becomes
dislodged from the terminal.
NO NC COM COM NONC
WIRE NUT FIRE PANEL OR
ADDRESSABLE
MODULE
WIRE NUT LOCAL
AUDIBLE/VISUAL
ANNUNCIATOR
BLACKWHITE
NEUTRAL
WHITE
BLACK
(LINE/HOT)
CIRCUIT
BREAKER
LOAD OUT TO
AUDIBLE/VISUAL
ANNUNCIATOR
INCOMING
OUTGOING
SINGLE
CONDUCTOR
UNINSULATED
LOOPED SECTION
CLAMPING
PLATE
TERMINAL
SEPARATE
CONDUCTORS
CLAMPING
PLATE
TERMINAL
SEVERED
STRIPPED
ENDS
FIGURE 6
MODEL RM-1 COMMERCIAL AND RESIDENTIAL RISER MANIFOLD
WIRING GUIDANCE

TFP963
Page 7 of 8
Care and
Maintenance
TYCO Riser Manifolds RM-1 must be
serviced and maintained in accordance
with this section.
Before closing a fire protection system
control valve for inspection or main-
tenance work on the fire protection
system that it controls, permission to
shut down the effected fire protection
system must first be obtained from
the proper authorities and all person-
nel who may be affected by this action
must be notified.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for moni-
toring proprietary and/or central station
alarms.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION (e.g., NFPA 25), in addi-
tion to the standards of any authority
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Note: No attempt is to be made to
repair any Riser Manifold component
in the field. Only the pressure gauge,
waterflow alarm switch, or relief valve
can be replaced. If any other problems
are encountered the entire riser mani-
fold must be replaced.
The alarm/flow test procedure will
result in operation of the associated
alarms. Consequently, notification
must be given to the owner and the fire
department, central station, or other
signal station to which the alarms are
connected, and notification must be
given to the building occupants.
The following inspection procedure
must be performed as indicated, in
addition to any specific requirements
of the NFPA, and any impairment must
be immediately corrected:
Alarm/Flow Test Procedure
Step 1. Place the Model TD-1 Test and
Drain Valve in the TEST position (Ref.
Figure 7). On residential assemblies
without a test orifice, temporarily install
a test orifice in the drain outlet and fully
open the Drain Valve. Make certain
that drainage water will not cause any
damage or injury.
Step 2. Verify operation of associated
alarms.
Step 3. Verify that the residual (i.e.,
flowing) pressure indicated by the pres-
sure gauge is no less that originally
recorded for the system when it was
first installed.
Step 4. Close the Drain Valve on the
Residential models and the Test and
Drain valve on commercial models.
Step 5. Verify that the static (i.e., not
flowing) pressure indicated by the pres-
sure gauge is no less that originally
recorded for the system when it was
first installed.
DRAIN MARKING
ON HANDLE
POSITIONED
ON DETENT
OFF MARKING
ON HANDLE
POSITIONED
ON DETENT
SET
CONDITION
FRONT
VIEW
SIGHT
FLOW
TEST
CONDITION
DRAIN
CONNECTION
TEST MARKING
ON HANDLE
POSITIONED
ON DETENT
DRAIN
CONDITION
MODEL TD-1
TEST AND
DRAIN
VALVE
FIGURE 7
MODEL RM-1 COMMERCIAL RISER MANIFOLD
TD-1 TEST AND DRAIN VALVE OPERATION

TFP963
Page 8 of 8
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a trademark of The Chemours Company FC, LLC
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2021 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indi-
cate the full product name, including
description and part number (P/N).
Riser Manifolds
Specify: Size (specify) Connection Type
(specify inlet x outlet) Model RM-1 Riser
Manifold, P/N (specify):
Commercial
1-1/2 in. (DN40) MT x FT . . . . . . . . . . . . . . 40551
2 in. (DN50) G x G . . . . . . . . . . . . . . . . . . . 40601
2-1/2 in. (DN65) G x G . . . . . . . . . . . . . . . . 40 611
3 in. (DN80) G x G . . . . . . . . . . . . . . . . . . . 40621
4 in. (DN100) G x G . . . . . . . . . . . . . . . . . . 40651
6 in. (DN150) G x G. . . . . . . . . . . . . . . . . . . 40661
Residential
1 in. (DN25) FT x FT . . . . . . . . . . . . . . . . . . 40671
1-1/2 in. (DN40) MT x FT . . . . . . . . . . . . . . 40571
2 in. (DN50) G x G . . . . . . . . . . . . . . . . . . . 40591
Optional 175 psi Pressure Relief Kit
Specify: Pressure Relief Kit, Model
RM-1 Riser Manifold, (specify Commer-
cial or Residential application), (specify
size range), P/N (specify):
Commercial
1-1/2 in. – 3 in. (DN40 – DN80) 40721
4 in. – 6 in. (DN100 – DN150) 40731
Residential
1 in.– 2 in. (DN25 – DN50) . . . . . . . . . . . . . . 40711
Replacement Parts
Specify: Model RM-1 Riser Manifold
(specify part description), P/N (specify
from Figures 1, 2, 3, 4 or 5)
Nominal
Valve Size
ANSI in. (DN)
Equivalent
Length of
Schedule 40 Pipe
ft (m)
2 (DN50) 4.5 (1,3)
2-1/2 (DN65) 3.6 (1,1)
3 (DN80) 3 (5,1)
4 (DN100) 4 (6,6)
6 (DN150) 9.6 (2,9)
TABLE A
FRICTION LOSS EXPRESSED
AS FLOW THROUGH
EQUIVALENT LENGTH OF
SCHEDULE 40 PIPE