Description of operation VALLOX 70 COMPACT / VALLOX 70K COMPACT
Control of operation
Power supply to the VALLOX 70 COMPACT unit is controlled
with the 0/1 switch in the distribution panel. There is also a
maintenance switch HK inside the unit.
VALLOX 70K COMPACT is equipped with a plug. There is
also a maintenance switch HK inside the unit.
Fan speed adjustment
The Sand Efans of the unit are controlled depending on
operating conditions with a separate 4-step (1, 2, 3 and 4)
switch HS located in the ventilation zone, or with a cooker
hood.
Heat recovery bypass
Summer-time bypass of the heat recovery cell HR is done
manually by turning the HR damper Hin the bypass position
for the summer.
Supply air temperature
Regulating thermostat T1 controls the operation of the electric
radiator JL, keeping the supply air going out from the unit at
the setpoint.
Preheating of outdoor air
Regulating thermostat T2 controls the operation of the electric
radiator EL as follows: the radiator heats outdoor air before
the cell and prevents the heat recovery cell from freezing. In
very cold temperatures the preheating radiator EL is not enough
to heat maximum air flow to a sufficient degree (in a temperature
of minus 30 degrees, maximum air flow is 30 dm3/s, which
corresponds to speed 2 or 3). The threshold of thermostat T2
can be adjusted inside the unit.
Heat recovery defrosting
(alternative to preheating radiator)
The anti-freezing thermostat T2 of the HR cell keeps stopping
the supply air fan S, thereby preventing the risk of the freezing
of the HR cell. The fan starts automatically as soon as the risk
of freezing has passed. The threshold temperature of freezing
risk can be set at thermostat T2.
Fireplace switch function
The unit can be equipped with an optional fireplace switch
FS. It can be a timer equipped with opening points. Timing
period can be 15…30 minutes.
Alarms
Pressure difference switch PDS is an optional device for controlling
pressure difference on the supply air side. If the pressure
difference rises above the setup, because of dirty filters or
clogged ducts, an indicator is lit on the front panel of the unit.
Parts list VALLOX 70 COMPACT/VALLOX 70K COMPACT
© VALLOX • We reserve the right to make changes without prior notification.
What the units include can vary depending on the sales area.
7
VALLOX 70 COMPACT
Code Name Technical details Standard
/ Option
G4 Filter, extract air and supply air G4 Standard
F7 Fine filter, supply air F7 Standard
H HR bypass damper Manual Standard
HS Speed adjustment 4-step switch Standard Standard
VALLOX 70 Compact or cooker hood Option
HS Speed adjustment Cooker hood Standard
VALLOX 70K Compact
EL Preheating radiator Elecctric, max 0.9 kW Standard
JL Post-heating radiator Elecctric, max 0.9 kW Standard
HR Heat recovery cell, pair efficiency ~75 % Standard
S Supply air fan 105 W 56 dm3/s 50 Pa Standard
E Extract air fan 105 W 65 dm3/s 50 Pa Standard
HK Maintenance / safety switch Door switch Standard
T1 Regulating thermostat 0…40 ºC Standard
T2 HR defrost thermostat Factory setting +4 ºC Standard
FS Fireplace switch Opening points Option
15…30 minutes
PDS Pressure difference switch Adjustment range 0...500 Pa Option
Pressure guard for Factory setting 190 Pa
the supply air side