TECHNICAL SPECIFICATIONS
Model
Weight
kg
Electrical
connection
Power taken from
the network P1 kW
Power
(A)
Fan enclosure
protection class
Control
Vallox Exxeo 150 20 1~ 230 VAC, 50 Hz 0.085 0.7 IP54 2-speed or 0–10 V control and Modbus connection
Vallox Exxeo 150 DS 23 1~ 230 VAC, 50 Hz 0.085 0.7 IP54 Similar to an old AC dual speed roof fan
Vallox Exxeo 150 DPC 20 1~ 230 VAC, 50 Hz 0.085 0.7 IP54 2-speed or 0–10 V control, pressure and air volume
control and Modbus connection
Vallox Exxeo 300 29 1~ 230 VAC, 50 Hz 0.170 1.4 IP54 2-speed or 0–10 V control and Modbus connection
Vallox Exxeo 300 DS 32 1~ 230 VAC, 50 Hz 0.170 1.4 IP54 Similar to an old AC dual speed roof fan
Vallox Exxeo 300 DPC 29 1~ 230 VAC, 50 Hz 0.170 1.4 IP54 2-speed or 0–10 V control, pressure and air volume
control and Modbus connection
Vallox Exxeo 700 32 1~ 230 VAC, 50 Hz 0.440 2.2 IP54 2-speed or 0–10 V control and Modbus connection
Vallox Exxeo 700 DS 35 1~ 230 VAC, 50 Hz 0.440 2.2 IP54 Similar to an old AC dual speed roof fan
Vallox Exxeo 700 DPC 32 1~ 230 VAC, 50 Hz 0.440 2.2 IP54 2-speed or 0–10 V control, pressure and air volume
control and Modbus connection
Vallox Exxeo 1400 68 1~ 230 VAC, 50 Hz 0.800 4.0 IP54 2-speed or 0–10 V control and Modbus connection
Vallox Exxeo 1400 DS 70 1~ 230 VAC, 50 Hz 0.800 4.0 IP54 Similar to an old AC dual speed roof fan
Vallox Exxeo 1400 DP 68 1~ 230 VAC, 50 Hz 0.800 4.0 IP54 2-speed or 0–10 V control, pressure and air volume
control and Modbus connection
Vallox Exxeo 2000 73 3~ 400 VAC, 50 Hz 1.100 1.8 IP55 2-speed or 0–10 V control and Modbus connection
Vallox Exxeo 2000 DS 75 3~ 400 VAC, 50 Hz 1.100 1.8 IP55 Similar to an old AC dual speed roof fan
Vallox Exxeo 2000 DPC 73 3~ 400 VAC, 50 Hz 1.100 1.8 IP55 2-speed or 0–10 V control, pressure and air volume
control and Modbus connection
Vallox Exxeo 2500 99 3~ 400 VAC, 50 Hz 1.100 1.85 IP55 2-speed or 0–10 V control and Modbus connection
Vallox Exxeo 2500 DS 101 3~ 400 VAC, 50 Hz 1.100 1.85 IP55 Similar to an old AC dual speed roof fan
Vallox Exxeo 2500 DPC 99 3~ 400 VAC, 50 Hz 1.100 1.85 IP55 2-speed or 0–10 V control, pressure and air volume
control and Modbus connection
Vallox Exxeo 4100 107 3~ 400 VAC, 50 Hz 3.500 5.6 IP55 2-point or 0–10 V control and Modbus connection
Vallox Exxeo 4100 DS 109 3~ 400 VAC, 50 Hz 3.500 5.6 IP55 Similar to an old AC dual speed roof fan
Vallox Exxeo 4100 DPC 107 3~ 400 VAC, 50 Hz 3.500 5.6 IP55 2-speed or 0–10 V control, pressure and air volume
control and Modbus connection
QUICK SELECTION TABLE
Volume flow rate, qv (m/s) the penetration part in place in the roof fan | Static pressure dierence (Pa)
Static pressure dierence (Pa) 50 75 100 125 150 175 200 225 250 300 350 400 500 600 800
Vallox Exxeo 150 0.204 0.192 0.180 0.170 0.160 0.147 0.137 0.126 0.113 0.085 0.058 0.035
Vallox Exxeo 300 0.366 0.357 0.347 0.337 0.327 0.315 0.302 0.288 0.273 0.243 0.213 0.182 0.130
Vallox Exxeo 700 0.767 0.756 0.744 0.731 0.719 0.704 0.689 0.675 0.659 0.624 0.581 0.534 0.409
Vallox Exxeo 1400 1.503 1.482 1.458 1.435 1.412 1.389 1.367 1.345 1.322 1.263 1.196 1.128 0.986 0.76
Vallox Exxeo 2000 2.281 2.233 2.184 2.134 2.08 2.03 1.983 1.92 1.856 1.725 1.565
Vallox Exxeo 2500 2.935 2.849 2.742 2.648 2.565 2.466 2.356 2.235 2.098 1.734 1.003 0.599
Vallox Exxeo 4100 4.417 4.357 4.299 4.247 4.187 4.121 4.058 3.995 3.932 3.804 3.663 3.513 3.196 2.793 1.125
The following must be observed when choosing
the roof fan:
• The static pressure indicated by the graph = pressure available for
use in the ducts. The pressure was calculated at the bottom end of
the penetration part. Air density = 1.20 kg/m.
IMPORTANT
It is recommended
to keep the fan on at
all times, as water or
snow could enter the
structures. If the fan
is switched o, it is
recommended to use a
damper to protect the
duct system.
Adjustments to Vallox Exxeo’s sound power level to the environment
(LwA) to define the sound pressure level LpA.
Sound pressure level LpA - at distance r, dB(A), roof fan installed on top of the flue
1 m 10 m 20 m 30 m 40 m 50 m
-11 dB -31 dB -37 dB -41 dB -43 dB -45 dB
SOUND PRESSURE LEVEL
INTRODUCTION