
TCI-C Universal Controller
OUTPUT CONFIGURATION
Doc: 70-00-0123, V1.3, Date: 20170131 © Vector Controls GmbH, Switzerland Page 12
Subject to alteration
Output Priority
1. Alarm level low
2. Alarm level high
3. Operation mode OFF
4. Control function
Output configuration
Analog output configuration (1A, 2A)
Select control loop or special function (0= OFF):
1= LP1, 2= LP2
3= Dehumidify (4 pipe, max LP1 cooling, LP2 direct)
4= Manual positioning or by time schedule (0–100%)
5= Feedback: transmit value of an input
When A00=1 or 2select sequence or set point feedback:
0= Heating/reverse
1= Cooling/direct
2= Heating and cooling (2 pipe)
3= Transmit set point of selected control loop
When A00 = 4 select manual/time schedule positioning
0 = Position output by time schedule only
1 = Position output manually or by time schedule
When A00=5, select input (0= function disabled):
1= 1U, 2= 2U, 3= 3U, 4= 4U
Type of output signal: OFF= 0–10V, 0–20mA, ON= 2–10V, 4–20mA
Minimum limitation of output signal default and in loop heating mode
Maximum limitation of output signal default and in loop heating mode
Minimum limitation of output signal in loop cooling mode
Maximum limitation of output signal in loop cooling mode
Choose alarm to set output to 100% (output 0% on conflicting alarms)
Alarm: 1 2 3 4 5 6 7 8
Triangle shown
=alarm selected
Choose alarm to set output to 0%. (output 0% on conflicting alarms)
Alarm: 1 2 3 4 5 6 7 8
Triangle shown
=alarm selected
Transmit value (1A00=5): minimum input value
Transmit value (1A00=5): maximum input value
Set jumpers on the back of the controller: 0–10 VDC (default), or 0–20 mA. Further define analog outputs with A02.
Custom ranges can be created by setting minimum and maximum signal limits.
A control loop, special function, digital control or analog control sequence is not active until it is assigned an output.
Low and high limit alarms are defined with input parameters. With output parameters assign an
alarm to an output and select output state. The required output for each alarm can be
individually selected. Multiple alarms can be signed to one output. If one alarm is selected to
simultaneously activate and deactivate an output, the one to de-activate has precedence.
With manual positioning (1A00=4) position the output by time schedule or directly in 0.5%
steps. Setting 1A01 to 0 will disable manual positioning. The output will then only be controlled by time schedule.
With dehumidifying (1A00=3) the maximum value is taken of cooling and dehumidifying. When the humidity is too
high, cooling will continue to operate, even without a demand for cooling, to dehumidify the air and heating will
activate to maintain comfort.
Input values of universal inputs and set points of control loops may be transmitted on the analog outputs.
For VAV Function individual minimum and
maximum limits may be assigned for cooling and
heating. In VAV applications maximum cooling
output matches the maximum air volume the
VAV box is set to deliver. As demand for airflow
in cooling mode decreases, airflow dwindles until
it reaches minimum cooling output (1A05). This
minimum will be based on the airflow needed at
design cooling and is typically 10% to 15% of
maximum cooling airflow. When this minimum is
reached the system is in dead-band –neither
heating nor cooling. Minimum airflow in heating
mode is set with 1A03. As the system moves into
heating mode, heating airflow increases until it
reaches the maximum heating output (1A04), typically 30 to 50% of maximum cooling airflow.