Vertiv R48-2000C User manual

NetSure™
R48-2000C Outdoor Rectifier
Installation and User Manual (UM1R482000C), Revision A
Model Number: R48-2000C

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
2
The information contained in this document is subject to change
without notice and may not be suitable for all applications. While
every precaution has been taken to ensure the accuracy and
completeness of this document, Vertiv Group Corporation
assumes no responsibility and disclaims all liability for damages
resulting from use of this information or for any errors or
omissions. Refer to other local practices or building codes as
applicable for the correct methods, tools, and materials to be
used in performing procedures not specifically described in this
document.
This document may contain confidential and/or proprietary
information of Vertiv Group Corporation, and its receipt or
possession does not convey any right to reproduce, disclose its
contents, or to manufacture or sell anything that it may describe.
Reproduction, disclosure, or use without specific authorization
from Vertiv Group Corporation is strictly prohibited.
Vertiv and the Vertiv logo are trademarks or registered
trademarks of Vertiv Group Corporation. NetPerform™,
NetReach™, NetSure™ and NetXtend™ are trademarks of Vertiv
Energy Systems, Inc. All other trademarks are the property of
their respective owners.
© 2019 Vertiv Energy Systems, Inc. All rights reserved.

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
3
TABLE OF CONTENTS
Admonishments Used in this Document ................................................ 5
Important Safety Instructions ................................................................. 6
General Safety.................................................................................... 6
Voltages.............................................................................................. 6
AC Input Voltages.....................................................................................6
DC Output Voltages..................................................................................6
Hazardous Voltage ............................................................................. 7
Handling Equipment Containing Static Sensitive
Components ....................................................................................... 7
Static Warning......................................................................................... 8
Introduction ............................................................................................ 9
Ordering Structure ............................................................................. 9
What is in the Box ....................................................................................9
Rectifier Overview.............................................................................. 9
Rectifier Specifications....................................................................... 9
DC Output Ratings..................................................................................10
AC Input Ratings.....................................................................................12
Environmental Ratings...........................................................................15
Compliance Information .......................................................................16
Standard Features..................................................................................16
Mechanical Specifications......................................................................17
Installation ............................................................................................ 19
Installing the Rectifier ...................................................................... 19
General...................................................................................................19
Pole Installation Procedure...................................................................19
Wall Installation Procedure...................................................................21
Making Electrical Connections.............................................................. 24
Important Safety Instructions .......................................................... 24
Wiring Considerations...................................................................... 24
Frame Ground Connection............................................................... 24
External Alarm and Control Connections......................................... 24
Nominal 120 VAC / 208 VAC / 220 VAC / 230 VAC / 240 VAC
Input and AC Input Equipment Grounding Connections ................. 25
-48 VDC Output Connections ........................................................... 25
Customer Wiring to the Mating Connectors.................................... 25
Paralleling Rectifiers for Redundancy .............................................. 26
Final Step.......................................................................................... 26
Customer Cable Pre-install Procedure...................................................26
Customer Wiring Connection procedure...............................................27
Initially Starting and Checking Rectifier Operation............................... 34
Initially Starting the Rectifier ........................................................... 34
Checking System Status.................................................................... 34
Operation .............................................................................................. 35
Local Indicators ................................................................................ 35
Rectifier High Voltage Shutdown and Lockout Restart.................... 35

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
4
Troubleshooting and Repair ................................................................. 36
Troubleshooting ............................................................................... 36
Repair ............................................................................................... 36

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
5
ADMONISHMENTS USED IN THIS DOCUMENT
DANGER! Warns of a hazard the reader will be exposed to that will likely
result in death or serious injury if not avoided. (ANSI, OSHA)
WARNING! Warns of a potential hazard the reader may be exposed to that could
result in death or serious injury if not avoided. This admonition is not used for
situations that pose a risk only to equipment, software, data, or service. (ANSI)
CAUTION! Warns of a potential hazard the reader may be exposed to that could
result in minor or moderate injury if not avoided. (ANSI, OSHA) This admonition
is not used for situations that pose a risk only to equipment, data, or service,
even if such use appears to be permitted in some of the applicable standards.
(OSHA)
ALERT! Alerts the reader to an action that must be avoided in order to protect
equipment, software, data, or service. (ISO)
ALERT! Alerts the reader to an action that must be performed in order to prevent
equipment damage, software corruption, data loss, or service interruption. (ISO)
FIRE SAFETY! Informs the reader of fire safety information, reminders,
precautions, or policies, or of the locations of fire-fighting and fire-safety
equipment. (ISO)
SAFETY! Informs the reader of general safety information, reminders, precautions,
or policies not related to a particular source of hazard or to fire safety. (ISO, ANSI,
OSHA)

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
6
IMPORTANT SAFETY INSTRUCTIONS
General Safety
DANGER! YOU MUST FOLLOW APPROVED SAFETY PROCEDURES.
Performing the following procedures may expose you to hazards. These procedures should
be performed by qualified technicians familiar with the hazards associated with this type of
equipment. These hazards may include shock, energy, and/or burns. To avoid these hazards:
a) The tasks should be performed in the order indicated.
b) Remove watches, rings, and other metal objects.
c) Prior to contacting any uninsulated surface or termination, use a voltmeter to verify that no
voltage or the expected voltage is present. Check for voltage with both AC and DC
voltmeters prior to making contact.
d) Wear eye protection.
e) Use certified and well-maintained insulated tools. Use double insulated tools appropriately
rated for the work to be performed.
Voltages
AC Input Voltages
DANGER! This system operates from AC input voltage capable of producing fatal electrical
shock. AC input power must be completely disconnected from the branch circuits wiring
used to provide power to the system before any AC electrical connections are made. Follow
local lockout/tagout procedures to ensure upstream branch circuit breakers remain de-
energized during installation. DO NOT apply AC input power to the system until all electrical
connections have been completed and checked.
DC Output Voltages
DANGER! This system produces DC power and may have a DC source connected to it.
Although the DC voltage is not hazardously high, the rectifier can deliver large amounts of
current. Exercise extreme caution not to inadvertently contact or have any tool
inadvertently contact an output terminal or exposed wire connected to an output terminal.
NEVER allow a metal object, such as a tool, to contact more than one termination at a time,
or to simultaneously contact a termination and a grounded object. Even a momentary short
circuit can cause sparking, explosion, and injury.
DANGER! Follow local lockout/tagout procedures to ensure DC branch circuit protection
devices remain de-energized during installation at loads, as required.

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
7
Hazardous Voltage
DANGER! HAZARD OF ELECTRICAL SHOCK.
More than one disconnect may be required to de-energize the system before servicing.
Handling Equipment Containing Static Sensitive Components
ALERT! Installation or removal of equipment containing static sensitive components requires
careful handling. Before handling any equipment containing static sensitive components,
read and follow the instructions contained on the Static Warning Page.

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
8
STATIC WARNING
This equipment contains static sensitive components. The warnings listed below must be
observed to prevent damage to these components. Disregarding any of these warnings may
result in personal injury or damage to the equipment.
1. Strictly adhere to the procedures provided in this document.
2. Before touching any equipment containing static sensitive components, discharge all static
electricity from yourself by wearing a wrist strap grounded through a one megohm resistor.
Some wrist straps have a built-in one megohm resistor; no external resistor is necessary.
Read and follow wrist strap manufacturer’s instructions outlining use of a specific wrist strap.
3. Do not touch traces or components on equipment containing static sensitive components.
Handle equipment containing static sensitive components only by the edges that do not have
connector pads.
4. After removing equipment containing static sensitive components, place the equipment only
on conductive or anti-static material such as conductive foam, conductive plastic, or
aluminum foil. Do not use ordinary Styrofoam™or ordinary plastic.
5. Store and ship equipment containing static sensitive components only in static shielding
containers.
6. If necessary to repair equipment containing static sensitive components, wear an
appropriately grounded wrist strap, work on a conductive surface, use a grounded soldering
iron, and use grounded test equipment.

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
9
INTRODUCTION
The R48-2000 C provides a rectifier mounted inside an environmentally protective enclosure. The
R48-2000 C can be wall or pole mounted.
Ordering Structure
What is in the Box
Refer to Table 1.
Table 1:
ITEM
(1) 21505943 Pole/Wall mount Kit(1x)
①63240BQ0 Mounting Bracket (Small)(1x)
②63240BPY Mounting Bracket (Big)(2x)
③63126330 Pole Mount Band(2x)
④26011356 M5 Flat Head Screws(3x)
⑤26011153 M8 Bolts w/ Flat Washer and Lock Washer(2x)
⑥26011018 M5 Bolts w/ Flat Washer and Lock Washer(6x)
(2) 21505942 Front Side shield Kit(1x)
①26011383 M6 Bolts w/ Flat Washer and Lock Washer(4x)
②63240BPM Front Side Shield(1x)
③63128427 Securing Colume(4x)
(3) UM1R482000C Installation and User Manual(1x)
Rectifier Overview
The rectifier provides load power during normal operating conditions. The rectifier is a constant
power design. The rectifier is rated at its maximum output power. This means that, within the
normal operating ambient temperature range and input voltage range, the maximum available
output power is a constant 2000 W. Within these ranges, the rectifier operates in one of three
modes, depending upon load demands. Transition between modes is completely automatic. If
ambient temperature rises above or input voltage falls below acceptable values, the rectifier
continues to operate but at derated output power levels.
•Constant Voltage Mode: For any initial output voltage setting from -42 VDC to -58 VDC
(factory set at -54 VDC), output voltage remains constant regardless of load. This is the
normal operating condition, in which loads are being supplied. The rectifier operates in the
Constant Voltage Mode unless load increases to the point where the product of load current
and output voltage is approximately 2000 W.
•Constant Power Mode: As load increases above approximately 2000 W (non-adjustable),
output current continues to increase, but output voltage decreases as required to maintain
constant output power. The rectifier operates in the Constant Power Mode unless load
continues to increase to the point where the current limit setting is reached.
•Constant Current Mode: If load increases to the current limit setting, output voltage
decreases linearly to maintain output current at the current limit setting.
Rectifier Specifications
The specifications are for a single unit only, unless otherwise noted.

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
10
DC Output Ratings
1. Voltage: -42 VDC to -58 VDC, positive ground. Output voltage is factory set at -54 VDC.
2. Output Power and Current:
a) 2000 W (41.7 A) @ 200 VAC to 250 VAC input and -48 VDC output.
3. Output Characteristics: Refer to Figure 1 for a graph of output voltage vs. output current.
Figure 1: Output Voltage vs. Output Current
4. Power Derating Based on Input Voltage: The rectifier power varies with changes in input
voltage. It uses an advanced power limitation method. The lower input threshold is 85 VAC. The
rectifier can provide its maximum rated power (2000 W) as long as the input voltage is within the
range of 176 VAC to 300 VAC. Below 176 VAC, and down to 85 VAC, the rectifier will continue to
operate normally but will be in a power derating mode. The relationship between the output
power and input voltage is illustrated in Figure 2.
Figure 2: Power Derating Based on Input Voltage
0
10
20
30
40
50
60
0 5 10 15 20 25 30 35 40 45
Output Voltage (V)
Output Current (A)
Output voltage v.s. Output current at max. Power
0.0%
20.0%
40.0%
60.0%
80.0%
100.0%
120.0%
050 100 150 200 250 300 350
% of output power
Input voltage (Vac)
Output power vs. Input voltage and Vo>48V at Temp≤45℃

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
11
5. Power Derating Based on Temperature: The rectifier delivers full power when operating at an
ambient temperature of +50 °C (+122 °F) or below. The rectifier continuously monitors the ambient
temperature surrounding the power conversion circuit. If this temperature for any reason (such as
a high ambient temperature) increases above approximately +50 °C (+122 °F), the rectifier will not
shut down. Rather, the rectifier limits its maximum output power to maintain the temperature of
the power conversion circuit within design parameters. Operation between +50 °C (+122 °F) and
+75 °C (+167 °F) will result in output power being decreased. Full power capability is restored when
the temperature decreases to below approximately +50 °C (+122 °F). Refer to Figure 3 to view the
relationship between the output power and the ambient temperature.
WARNING! The module is rated for continuous operation at full output power up to +50 °C
(+122 °F). Operation between +50 °C (+122 °F) and +75 °C (+167 °F) will result in output
power decrease. Operation above +75 °C (+167 °F) is considered abnormal and should be
used on a temporary1basis only.
6. Temporary Operation at Abnormal Temperature: Temporary operation is defined as a period of
not more than eight consecutive hours per day, and a total of not more than 15 days in a year.
(This refers to a total of 120 hours in any given year, but no more than 15 occurrences in that one-
year period.)
Other power rating values are as follows (refer to Figure 3):
a) At an ambient temperature of +65 °C (+149 °F), the power delivered by the rectifier is 800 W.
b) At an ambient temperature of +75 °C (+167 °F), the power delivered by the rectifier is 0 W.
NOTE! If used outdoors under full solar radiation, all the operation temperature ratings are
decreased by 15 °C.
Figure 3: Power Derating Based on Temperature
7. Regulation:
a) Static: Steady state regulation is ±0.6 % as controlled within the rectifier for any and all
combinations of load from no load to full load, input voltage, and input frequency at a constant
ambient temperature.
b) Dynamic: Response time ≤200 us and overshot ≤5 % for load changes at 50 % - 25 % - 50 %
and 50 % - 75 % - 50 % at rated output current.

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
12
For any step load change within the range of 10 % to 90 % of full load within 50 ms, per Telcordia
GR-947-CORE, the maximum voltage transient will not exceed 5 % of the initial steady state voltage
within 50±10 us. Recovery to within 1 % of the initial steady state voltage does not exceed 1
milliseconds.
8. Filtering:
a) Voice Band Noise: Peak-peak voltage is ≤200 mV at 0 MHZ to 20 MHZ and normal output
voltage.
b) Wide Band Noise: Wideband noise voltage is ≤50 mV at 3.4 kHz to 150 kHz and ≤20 mV at 0.15
MHz to 30 MHz.
AC Input Ratings
1. Voltage: Nominal 120 VAC / 208 VAC / 220 VAC / 230 VAC / 240 VAC, single phase, 3-wire, 50 Hz
/ 60 Hz, with an operating range of 85 VAC to 300 VAC. Acceptable input frequency range is 45 Hz
to 65 Hz.
Permitted Variation: 85 VAC to 300 VAC.
2. Harmonic Content (THD): Meets EN61000-3-2. ≤5 % from 50 % to 100 % of rated output current
at 220 VAC.
3. Inrush Current: Peak does not exceed 1.5 times of the peak value of the maximum steady-state
input current at full load, 220 VAC input voltage, and for any duration of AC input interrupts. Under
the above conditions, standard AC distribution circuit breakers will not trip.
4. Typical Input Data: 50 Hz input.
a) Refer to Table 2.
b) Maximum Input Current: Refer to Table 3.
c) Efficiency Curve: Refer to Figure 4.
5. Typical Input Data: 60 Hz input.
a) Refer to Table 4.
b) Maximum Input Current: Refer to Table 5.
c) Efficiency Curve: Refer to Figure 5 and Figure 6.
Table 2: Typical Input Data with 50 Hz Input
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
Heat
Dissipation
BTU/Hr
208
0
0.747
156.234
13.38
0.08
--
45.654
25
2.559
534.2
514.9
0.96
90.901
159.854
50
4.85
1012.9
992.3
0.9786
93.979
203.849
75
7.13
1485.3
1475.8
0.9934
94.642
269.828
100
9.503
1973.8
1962.1
0.99416
94.736
352.417
110
10.457
2170.5
2159.9
0.9951
94.543
402.201

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
13
240
0
0.861
207.6
12.9
0.06
--
44.017
25
2.311
557.9
513.76
0.923
91.524
148.579
50
4.206
1012
989.1
0.9773
94.318
191.752
75
6.18
1485.7
1471.1
0.9902
94.944
253.791
100
8.195
1967.1
1955.3
0.994
94.907
339.803
110
9.01
2162
2152
0.9953
94.872
376.540
NOTE! System output is initially adjusted to 54 volts DC as measured at the system sense
point at 50% of full load and nominal input. “Percent of Full Load” refers to percent of 17.24
amperes.
Table 3: Maximum Input Current with 50 Hz Input
NOMINAL INPUT VOLTAGE
INPUT VOLTAGE
INPUT CURRENT (AMPERES)
208/240
176
11.98
NOTE! At 100% of full load with output adjusted to 58 volts DC as measured at the output
terminals.
Table 4: Typical Input Data with 60 Hz Input
NOMINAL
INPUT
VOLTAGE
PERCENT
OF FULL
LOAD
INPUT
CURRENT
(AMPERES
)
INPUT VA
INPUT
WATTS
POWER
FACTOR
EFFICIENC
Y %
HEAT
DISSIPATIO
N BTU/HR
120
0
0.533
64.05
18.64
0.283
0
63.6023
25
4.403
528.6
524.8
0.994
90.028
178.5656
50
8.438
1006.9
1005.8
0.9989
92.735
249.3239
75
12.66
1503
1501.9
0.999
92.945
361.5329
100
--
--
--
--
--
--
110
--
--
--
--
--
--
208
0
0.8959
187.4
13.36
0.07
0.000
45.5862
25
2.615
545.9
517
0.947
90.968
159.3375
50
4.84
1010.36
991.9
0.982
94.052
201.3062
75
7.15
1487.7
1475.7
0.992
94.648
269.4866
100
9.506
1974.8
1961.7
0.9939
94.720
353.4051
110
10.4596
2171.1
2159.6
0.9946
94.679
392.1081
240
0
1.031
248.9
13.04
0.05
0.000
44.4943
25
2.376
575.8
517.3
0.907
91.333
152.9745
50
4.241
1020.7
989.2
0.969
94.309
192.0934
75
6.198
1489.7
1471.3
0.987
94.931
254.4731
100
8.203
1969.9
1955.1
0.993
95.040
330.8850
110
9.018
2163.5
2152.1
0.9947
95.009
366.5170

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
14
NOTE! System output is initially adjusted to 54 volts DC as measured at the system sense
point at 50% of full load and nominal input. “Percent of Full Load” refers to percent of 17.24
amperes.
Table 5: Maximum Input Current with 60 Hz Input
NOMINAL INPUT VOLTAGE
INPUT VOLTAGE
INPUT CURRENT (AMPERES)
208/240
176
11.98
NOTE! At 100% of full load with output adjusted to 58 volts DC as measured at the output
terminals.
Figure 4: Efficiency Curve (@ 230 VAC, 50 Hz)
Figure 5: Efficiency Curve (@ 240 VAC, 60 Hz)
84
86
88
90
92
94
96
98
0 10 20 30 40 50 60 70 80 90 100
Load (% of rated load)
Efficiency Curve
Efficiency (%)
75.0
80.0
85.0
90.0
95.0
020 40 60 80 100
Efficiency(%)
Load(% of rated load)
Efficiency Curve

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
15
Figure 6: Efficiency Curve (@ 120 VAC, 60 Hz)
Environmental Ratings
1. Operating Ambient Temperature Range:
a) -40 °C (-40 °F) to +50 °C (+122 °F) with full power performance.
b) +50 °C (+122 °F) to +75 °C (+167 °F) with derating output.
c) Temperature Coefficient: 0.02 % per degrees Celsius.
2. Storage Ambient Temperature Range: -20 °C (-4 °F) to +55 °C (+131 °F).
3. Relative Humidity: This rectifier is capable of operating in an ambient relative humidity range of
0 to 90 %.
4. Altitude: 3048 m (9842 feet).
5. Surge Protection: EN61000-4-5 up to level 4, Telcordia GR-1089-Core, IEEE C62.41-2002,
YD/T 731-2002.
Performance Criteria B.
AC Power Terminals
TEST LEVEL
SOURCE
IMPEDANCE
PERFORMANCE
CRITERIA
LINE TO LINE
LINE TO GROUND
± 4 kV
± 4 kV
2 ohms
B
NA
± 6 kV
12 ohms
B
DC Power Terminals:
TEST LEVEL
SOURCE
IMPEDANCE
PERFORMANCE
CRITERIA
LINE TO LINE
LINE TO GROUND
± 500 V
± 500 V
2 ohms
B
± 800 V
± 800 V
2 ohms
B
The test method is described in EN 61000-4-5. In this test the DC-cables shall be 5 m long.
6. Single Rectifier Audible Noise: At 25 °C ≤45 dB(A). Measurement made at 0.6 m distance in
front of rectifier and at same horizontal line of the middle of rectifier.
75.0
80.0
85.0
90.0
95.0
020 40 60 80 100
Efficiency(%)
Load(% of rated load)
Efficiency Curve

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
16
7. High Voltage Category (per UL60950): III
8. Power Distribution System: TN/TT/IT
9. EMI/RFI Suppression:
a) The rectifier conforms to the requirements of FCC rules Part 15, Class B for radiated and
conducted emissions limits.
b) The rectifier conforms to the requirements of European Norm, EN55022, Class B for radiated and
conducted emissions limits.
10. Pollution Degree: Degree 3.
Compliance Information
1. EMC: ETSI EN 300 386, FCC CFR 47 Part 15 class B, Telcordia GR-1089-CORE.
2. EMI Load Range: 5 % to 100 %.
3. Safety: IEC 60950, EN 60950.
Standard Features
1. Type of Power Conversion Circuit: High frequency.
2. Input Protection:
a) Input Over/Under Voltage Protection: The rectifier will shut down at low or high voltage input;
based on the following voltage levels:
Low Voltage Disable Point: 80 VAC, ±5 V; hysteresis is at least 15 VAC for restart.
High Voltage Disable Point: 305 VAC, ±5 V; hysteresis is at least 10 VAC for restart.
b) Between85 VAC and 176VAC the output power will be derated linearly based on the input
voltage as follows:
At input voltage of 85 VAC with output >48 VDC, maximum output power is 1000 W.
At input voltage of 176 VAC with output >48 VDC, maximum output power is 2000 W.
3. Output Protection:
a) Overload / Reverse Current: The rectifier has a fuse wire in the negative output DC bus. This
fuse is not customer replaceable.
b) Current Limiting: The rectifier has a current limit function. The current limit point is factory set
at 41.7 A. The current limit accuracy is ±1.5 A when the output voltage ranges from 42 VDC to 58
VDC.
c) Advanced Current Limit Function: The rectifier has an advanced Current Limit Function. When a
short circuit occurs at the rectifier output terminals, the rectifier will keep its output current at a
constant value (factory set at 34.5 A). This function effectively protects the rectifier and the
equipment connected to the rectifier. When the short circuit fault is cleared, the rectifier will
automatically restore back to normal operation.
d) High Voltage Shutdown:
•Fixed Control: If rectifier output voltage exceeds a factory set value of 59.5 VDC and the
rectifier is delivering more than 10 % of its rated current, the rectifier shuts down. (The
restart hysteresis is 0.5 V ±0.2 V.)

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
17
The rectifier then restarts and a HVSD restart timer starts (factory set at 5 minutes). If
output voltage again exceeds the high voltage shutdown value before the HVSD restart timer
expires, the rectifier shuts down and locks out. Manual restart is then required (by turning
power to the rectifier off , waiting until the LEDs on the rectifier extinguish, then turning
power to the rectifier on). If the rectifier does not experience a high voltage condition
before the HVSD restart timer expires, the restart circuit is reset.
If two or more rectifiers are paralleled, only the rectifier causing the high voltage condition
shuts down.
•Backup: If rectifier output voltage exceeds 59.5 VDC ±0.5 V (non-adjustable), the rectifier
shuts down. The rectifier then restarts and a HVSD restart timer starts (factory set at 5
minutes). If output voltage again exceeds the high voltage shutdown value before the HVSD
restart timer expires, the rectifier shuts down and locks out. Manual restart is then required
(by turning power to the rectifier off, waiting until the LEDs on the rectifier extinguish, then
turning power to the rectifier on).
4. Over-Temperature Protection: The rectifier provides over temperature protection by derating
output power and recovers automatically.
5. Active Load Sharing: The rectifier uses advanced digital active load sharing technology that
maintains balancing to within 5 % of rated current.
6. Paralleling: Up to three (3) rectifiers can be connected in parallel in one system. Do not exceed
the load rating of a single rectifier.
7. Rectifier Output Current Imbalance: When the average current of the system is greater than
10% of full rated current, and a load sharing severe imbalance occurs (such as an output fuse
opens) and the output current drops to zero, then the red fault indicator illuminates.
8. Monitoring Function: The rectifier has a built-in advanced DSP that monitors and controls the
operation of the rectifier.
WARNING! This product is not intended for oil exposure.
CAUTION! Double pole/neutral fusing.
Mechanical Specifications
1. Dimensions: Refer to Figure 7.
a) Millimeters: 400 (Height) X380 (Width) X 90 (Depth)
b) Inches: 15.7 (Height) X 14.96 (Width) X 3.5 (Depth)
2. Weight: 11 kg (24 lbs)
3. Indicators (located behind door):
a) Power (Green LED)
b) Protection (Yellow LED)
c) Alarm (Red LED)

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
18
Figure 7: Overall Dimensions
Note:
1. Dimensions are in
millimeter(mm), unless
otherwise specified.
2. Finish: Aluminum with
Powder Painted.
3. Weight:
Net: 11 kg
Shipping:
90
114
380
400
419
471
Rear view
Top view
Front viewLeft side view Right side view
Bottom view

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
19
INSTALLATION
Installing the Rectifier
General
The rectifier can be pole mounted or secured to a suitable wall.
For mounting; use a corrosion inhibiting compound (CIC) inside the tapped mounting holes to keep
water away or use organically plated stainless steel bolts. See Figure 9 and Figure 14.
If the front door is opened during installation, ensure the front door is securely closed and the
screws are torqued to 29 Kgf cm (2.9 Nm) (25 in-lbs).
Pole Installation Procedure
1. Unpack the rectifier and mounting accessories.
2. Install the mounting bracket (big) in the appropriate top position on the pole with the supplied
pole mount band. Securely tighten the pole mount band to the pole. The pole mount band
accommodates poles from 6” to 12” in diameter. Refer to Figure 8.
3. Install mounting brackets to the rear panel of the rectifier with the supplied hardware. Refer to
Figure 9.
4. Secure the top of the rectifier to the pole by securing the mounting bracket (small) to the
mounting bracket (big) with the supplied M8 bolts. Refer to Figure 10.
5. Secure the bottom of the rectifier to the pole by securing the mounting bracket (big) to the pole
with the supplied pole mount band. Refer to Figure 11.
6. Secure the front side shield to the rectifier with the supplied M6 bolts. Refer to Figure 12.
Figure 8: Installing the Mounting Bracket to the Pole with the Pole Mount Band
Pole
Pole mount band
P/N 63126330
Mounting bracket (big)
P/N 63240BPY

Vertiv |NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C) |Rev. A
20
Figure 9: Installing the Mounting Brackets to the Rectifier
Mounting bracket (small)
P/N 63240BQ0
M5 flat head screws (3)
P/N 26011356
For mounting; use a corrosion
inhibiting compound (CIC) inside
the tapped mounting holes to keep
water away, or use organically
plated stainless steel bolts.
Mounting bracket (big)
P/N 63240BPY
M5 bolts (3)
P/N 26011018
Figure 10: Securing the Rectifier to the Pole at the Top
M8 bolts (2 places)
P/N 26011153
Table of contents
Other Vertiv Media Converter manuals

Vertiv
Vertiv C48/24-1500 User manual

Vertiv
Vertiv NetSure C24/48-1500 User manual

Vertiv
Vertiv 584622100 User manual

Vertiv
Vertiv eSure 565649 User manual

Vertiv
Vertiv NetSure IPE Series User manual

Vertiv
Vertiv eSure 565391 User manual

Vertiv
Vertiv NetSure IPE Series User manual

Vertiv
Vertiv Netsure User manual

Vertiv
Vertiv eSure C48/58-1000B User manual

Vertiv
Vertiv eSure C48/58-1000 User manual