VESDA VLP User manual

VESDA VLP
Product Guide
September 2014
Document: 10278_09
Part Number: 19145


VESDA by Xtralis VESDAVLPProduct Guide
www.xtralis.com i
Intellectual Property and Copyright
This document includes registered and unregistered trademarks. All trademarks displayed are the trademarks of
their respective owners. Your use of this document does not constitute or create a licence or any other right to use
the name and/or trademark and/or label.
This document is subject to copyright owned by Xtralis AG (“Xtralis”). You agree not to copy, communicate to the
public, adapt, distribute, transfer, sell, modify or publish any contents of this document without the express prior
written consent of Xtralis.
Disclaimer
The contents of this document is provided on an “as is” basis. No representation or warranty (either express or
implied) is made as to the completeness, accuracy or reliability of the contents of this document. The manufacturer
reserves the right to change designs or specifications without obligation and without further notice. Except as
otherwise provided, all warranties, express or implied, including without limitation any implied warranties of
merchantability and fitness for a particular purpose are expressly excluded.
General Warning
This product must only be installed, configured and used strictly in accordance with the General Terms and
Conditions, User Manual and product documents available from Xtralis. All proper health and safety precautions
must be taken during the installation, commissioning and maintenance of the product. The system should not be
connected to a power source until all the components have been installed. Proper safety precautions must be taken
during tests and maintenance of the products when these are still connected to the power source. Failure to do so
or tampering with the electronics inside the products can result in an electric shock causing injury or death and may
cause equipment damage. Xtralis is not responsible and cannot be held accountable for any liability that may arise
due to improper use of the equipment and/or failure to take proper precautions. Only persons trained through an
Xtralis accredited training course can install, test and maintain the system.
Liability
You agree to install, configure and use the products strictly in accordance with the User Manual and product
documents available from Xtralis.
Xtralis is not liable to you or any other person for incidental, indirect, or consequential loss, expense or damages of
any kind including without limitation, loss of business, loss of profits or loss of data arising out of your use of the
products. Without limiting this general disclaimer the following specific warnings and disclaimers also apply:
Fitness for Purpose
You agree that you have been provided with a reasonable opportunity to appraise the products and have made
your own independent assessment of the fitness or suitability of the products for your purpose. You acknowledge
that you have not relied on any oral or written information, representation or advice given by or on behalf of Xtralis
or its representatives.
Total Liability
To the fullest extent permitted by law that any limitation or exclusion cannot apply, the total liability of Xtralis in
relation to the products is limited to:
i. in the case of services, the cost of having the services supplied again; or
ii. in the case of goods, the lowest cost of replacing the goods, acquiring equivalent goods or having the goods
repaired.
Indemnification
You agree to fully indemnify and hold Xtralis harmless for any claim, cost, demand or damage (including legal costs
on a full indemnity basis) incurred or which may be incurred arising from your use of the products.
Miscellaneous
If any provision outlined above is found to be invalid or unenforceable by a court of law, such invalidity or
unenforceability will not affect the remainder which will continue in full force and effect. All rights not expressly
granted are reserved.

VESDAVLPProduct Guide VESDA by Xtralis
ii www.xtralis.com
Scope
The VESDA VLP Product Guide is written to provide you with comprehensive knowledge of the detector.
This guide introduces you to the VESDA VLP features, technical specifications and gives an understanding of
its components and their function. You will also find instructions on installing, cabling and powering up the
detector.
This guide is for anyone involved with the design, maintenance and purchasing of the VESDA system. It is
assumed that anyone using this manual has knowledge and the appropriate certification from the local fire and
electrical authorities.
Document Conventions
The following typographic conventions are used in this document:
Convention Description
Bold Used to denote: emphasis.
Used for names of menus, menu options, toolbar buttons.
Italics Used to denote: references to other parts of this document or other
documents. Used for the result of an action.
The following icons are used in this document:
Convention Description
Caution: This icon is used to indicate that there is a danger to
equipment. The danger could be loss of data, physical damage, or
permanent corruption of configuration details.
Warning: This icon is used to indicate that there is a danger of electric
shock. This may lead to death or permanent injury.
Warning: This icon is used to indicate that there is a danger of inhaling
dangerous substances. This may lead to death or permanent injury.
Contact Us
UK and Europe +44 1442 242 330
D-A-CH +49 431 23284 1
The Americas +1 781 740 2223
Middle East +962 6 588 5622
Asia +86 21 5240 0077
Australia and New Zealand +61 3 9936 7000
www.xtralis.com

VESDA by Xtralis VESDAVLPProduct Guide
www.xtralis.com iii
Codes and Standards Information for Air Sampling Smoke Detection
We strongly recommend that this document is read in conjunction with the appropriate local codes and standards
for smoke detection and electrical connections. This document contains generic product information and some
sections may not comply with all local codes and standards. In these cases, the local codes and standards must
take precedence. The information below was correct at time of printing but may now be out of date, check with your
local codes, standards and listings for the current restrictions.
FCC Compliance Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15
of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, the user is encouraged to try to correct the interference by one
or more of the following measures; re-orientate or relocate the receiving antenna, increase the separation between
the equipment and receiver, connect the equipment to a power outlet which is on a different power circuit to the
receiver or consult the dealer or an experienced radio/television technician for help.
FDA
This Xtralis product incorporates a laser device and is classified as a Class 1 laser product that complies with FDA
regulations 21 CFR 1040.10. The laser is housed in a sealed detector chamber and contains no serviceable parts.
The laser emits invisible light and can be hazardous if viewed with the naked eye. Under no circumstances should
the detector chamber be opened.
FM Hazardous Applications
3611 Hazardous Approval Warning: Exposure to some chemicals may degrade the sealing of relays used on the
detector. Relays used on the detector are marked “TX2-5V”, “G6S-2-5V” or “EC2-5NU”.
VESDA detectors must not be connected or disconnected to a PC while the equipment is powered in an FM
Division 2 hazardous (classified) location (defined by FM 3611).
FM Approved Applications
The product must be powered from VPS-100US-120 or VPS-100US-220 only.
ONORM F3014
ONORM F3014, transport times for all tubes (including capillaries) must not exceed 60 seconds from any hole. This
means that the predesigned pipe networks that include capillaries cannot be used.
AS1603.8
The performance of this product is dependent upon the configuration of the pipe network. Any extensions or
modifications to the pipe network may cause the product to stop working correctly. You must check that ASPIRE2
approves alterations before making any changes. ASPIRE2 is available from your VESDA distributor.
AS1851.1 2005
Maintenance Standards. Wherever this document and the AS1851.1 differ, AS1851.1 should be followed in
preference to this document.

VESDAVLPProduct Guide VESDA by Xtralis
iv www.xtralis.com
Regional Regulatory Requirements and Notices
UL
For open area protection the fire alarm threshold (signal) that initiates an evacuation procedure via the Fire Alarm
Panel must not be set less sensitive than 0.625%/ft. The detector can send this signal via the Fire Alarm Panel
Output signal or the Pre-alarm output signal.
Through validation testing, Underwriters Laboratories Inc. has verified that VESDA ECO gas detectors, when
installed within the sample pipe network, present no significant effects on the smoke detection performance of
VESDA. The use of the ASPIRE2 calculation software is required to verify system design performance with all
devices included in the design.
European Installations
The product must use a power supply conforming to EN54: Part 4.
EN54-20
The product must use a power supply conforming to EN 54-4.
The product is compliant with EN 54-20 sensitivity requirements provided the following conditions are met:
lFor a Class A detector, hole sensitivity must be better than 1.5% obscuration/m and transport time less than
60 seconds
lFor a Class B detector, hole sensitivity must be better than 4.5% obscuration/m and transport time less than
90 seconds
lFor a Class C detector, hole sensitivity must be better than 10% obscuration/m and transport time less than
120 seconds
These limits should be verified using ASPIRE2 during the design of the sampling pipe network.
The product is compliant with EN 54-20 flow monitoring requirements provided the following conditions are met:
lThe minor low and minor high flow thresholds should be set at 85% and 115% respectively
lThe flow through the detector predicted by ASPIRE2 should be in the range 20 to 115 lpm
Additional information:
lClass A detectors passed EN 54-20 approvals testing with 30 holes and 0.05% obscuration/m detector
sensitivity
lClass B detectors passed EN 54-20 approvals testing with 60 holes and 0.06% obscuration/m detector
sensitivity
lClass C detectors passed EN 54-20 approvals testing with 100 holes and 0.08% obscuration/m detector
sensitivity
Product Listings
lUL
lULC
lFM
lCCC
lActivFire
lLPCB
lVdS
lCE
lVNIIPO
lNF
lEN 54-20
Regional approvals listings and regulatory compliance vary between VESDA product models. Refer to
www.xtralis.com for the latest product approvals matrix.
Document: 10278_09
Part Number: 19145

VESDA by Xtralis VESDAVLPProduct Guide
www.xtralis.com 1
Table of Contents
1 Introduction 3
1.1 Features 3
2 Operation 5
2.1 VESDA VLP Configurations 6
2.2 Components 9
3 Product Information 11
3.1 Product Specification 11
3.2 Dimensions 13
3.3 Relays 16
4 Mounting the VESDA VLP 19
4.1 Securing the mounting bracket 19
4.2 Mounting the VESDA VLP in Normal Orientation 19
4.3 Mounting the VESDA VLP in the Inverted Orientation 20
4.4 Mounting the VESDA VLP without a mounting bracket 20
4.5 Recess mounting kit 21
5 Connecting the VESDA VLP to the Pipe Network 23
5.1 Inlet Pipes 23
5.2 Managing the Exhaust Air 24
6 Wiring Connections 25
6.1 Termination Card 25
7 Power Source 29
8 Backup Battery 31
9 Powering Up 33
9.1 Installation Checklist 34
10 Preliminary Systems Check 35
11 Maintenance 37
11.1 Replacing the chassis/Air Inlet Pipe Manifold 37
11.2 Internal Wiring 40
11.3 Spare Parts 42
Index 43

VESDAVLPProduct Guide VESDA by Xtralis
2www.xtralis.com
This page is intentionally left blank.

VESDA by Xtralis VESDAVLPProduct Guide
www.xtralis.com 3
1 Introduction
The VESDA VLP is an aspirating smoke detector providing very early warning of fire conditions by drawing air
samples through an air sampling pipe network. The detector chamber can detect presence of smoke at very
low concentrations. The embedded and PC software complimenting the VESDA VLP provides a wide range
of user defined parameters and reporting capabilities. The detector easily interfaces with fire warning and fire
suppression release systems, and can be easily integrated into a building management system.
1.1 Features
The VESDA VLP features make it a versatile smoke detection product:
lEach detector can cover an area up to 2,000 m² (20,000 sq. ft.)
lWide sensitivity range
lFour programmable alarm thresholds
lAutoLearn feature
lFour pipe Inlets
lIndividual pipe flow monitoring
lReplaceable air filter cartridge
lOption for inverted mounting
lRecessed mounting option
lModular to meet site specific requirements
lModular Display Module and LCD Programmer
lSeven programmable relays
lHigh efficiency aspirator
lProgrammable general purpose Input
lPC capable programming and monitoring
lMultilingual displays
lEvent log for up to 18,000 events

VESDAVLPProduct Guide VESDA by Xtralis
4www.xtralis.com
This page is intentionally left blank.

VESDA by Xtralis VESDAVLPProduct Guide
www.xtralis.com 5
2 Operation
An air sampling pipe network collects air samples from a protected area. The integrated aspirator draws air
into the sampling pipes through a pipe inlet manifold. Up to four pipes can be connected to a VESDA VLP
detector.1
Inside the VESDA VLP, a sample of air is passed into the laser detection chamber. Ultra-fine air filtration
provides very clean air to protect the optical surfaces inside the detector from contamination.
The detection chamber uses a stable Class 1 laser light source and carefully positioned sensors to achieve
the optimum response to a vast range of smoke types. Any smoke detected in the laser detection chamber is
signaled to the main processor card. If the presence of detected smoke is higher than the set thresholds it is
reported as an alert, action, fire 1 or fire 2 alarm depending upon the alarm thresholds.
Air is exhausted from the VESDA VLP and may be vented back into the protected zone.
Legend
AAir inlets from pipe networks
BAir is drawn into the aspirator
CSome air is filtered and:
Dflows into the chamber for testing
Eis filtered a second time, then used to flush the chamber with ultra clean air
FAll air is then vented
Figure 2-1: Operation and internal air flow of a VESDA VLP
1For further information on air sampling pipe networks please see the Pipe Network Design and Installation
Manuals.

VESDAVLPProduct Guide VESDA by Xtralis
6www.xtralis.com
2.1 VESDA VLP Configurations
The modular options available with a VESDA VLP are:
lFire and OK LEDs (FOK)
lLCD Programmer
lVESDA VLP Display Module
Figure 2-2: VLP-012 installed with LCD Programmer and Display Module
2.1.1 Display Module
The VESDA VLP Display Module is mounted either on the detector front cover or at a remote location in a
remote mounting box or a 19” subrack. It provides a visual representation of the smoke levels and the four
alarm stages for the assigned detector. An array of fault LEDs illuminate in different configurations to report
Urgent, Minor, Zone and System faults. Up to 20 Display Modules can be assigned to one detector, however
the Display Module can be configured to report the status of only one detector at a time.
Legend
AAlarm Threshold Indicators
BBar graph of detected smoke
CNumerical display
DAlarm LEDs
EFault LEDs
FPush Button Keys
Figure 2-3: Display Module for VESDA VLP
OK LED
The OK LED stays illuminated during normal operation indicating the unit is functioning normally. When this
LED is off a warning beep sounds, indicating a Fault condition is active.

VESDA by Xtralis VESDAVLPProduct Guide
www.xtralis.com 7
Isolate LED
This LED is illuminated when the detector is Isolated and relays are de-activated disabling alarm outputs of
the detector. The display can be programmed to beep every 60 seconds.
Alarm Levels
lALERT: When illuminated this LED indicates that the smoke level is above the alert threshold. This
means the detector has identified very early stages of a fire condition and/or that the smoke level in the
area is above normal.
lACTION: When illuminated this LED indicates that the detected smoke level has passed the threshold
value fixed for Action, but is not intended to initiate a general fire alarm response procedure.
lFIRE 1: When illuminated this LED indicates that the detected smoke level is above the threshold
value set to initiate a general fire alarm response procedure. This indicates a fire may be imminent or is
in progress. When interfaced with a Fire Alarm Control Panel (FACP) it can generate an automatic fire
alarm.
lFIRE 2: When illuminated this LED indicates a fire is in progress. The detector can be interfaced with
an FACP to activate automatic suppression systems and evacuation procedures.
Bar Graph
The Bar graph is a 20 step indicator where each indicator represents an increase in the detected level of
smoke, relative to the preset fire alarm level.
Threshold Indicators
The illuminated LEDs represent visual settings for ALERT, ACTION, and FIRE 1 alarm levels. The FIRE 1
indicator is always at the top.
Fault LEDs
The Fault LEDs illuminate to indicate:
lURGENT: A serious fault requiring immediate attention
lSYSTEM: A fault affecting the network to which the Display Module is connected
lZONE: A fault in the VESDA Zone monitored by the Display Module
lPOWER: A fault in the power supply if the GPI function is used
lNETWORK: A communications fault on VESDAnet
lAIRFLOW: Higher or lower than acceptable levels of air flow through the inlet pipe(s)
lFILTER: The air filter requires changing
Push Button Keys
These buttons enable various systems functions. These do not allow configuring the system. The buttons can
be disabled by the systems administrator.
lMode/Test (Dual Function): Selects modes on the numerical display - sensitivity, smoke level, or
zone number. When depressed for more than two seconds it performs a light test function.
lSilence: This button silences any alarm or fault warnings. The LEDs stop flashing to acknowledge a
fault or alarm condition.
lReset: Resets any latched alarms and faults on the detector. Any active alarms or faults are reported
again after the time delays have elapsed.
lIsolate: Isolates the detector from any external devices or systems (an isolate alarm will normally be
raised at the Fire Alarm Control Panel).
Note: It is normal practise to signal the Isolate condition to the Fire Control Panel using the Isolate relay.

VESDAVLPProduct Guide VESDA by Xtralis
8www.xtralis.com
Numerical Displays
lSensitivity: Shows the level of smoke that must be measured to illuminate the entire bar graph and
always corresponds with the Fire 1 alarm level.
lSmoke Level: Indicates the current level of smoke in the relevant VESDA Zone and is represented as
% obs/m or % obs/ft.
lZone Number: This is the VESDA Zone number assigned to the Display Module.
The Mode button is used to select the parameter to display in the numeric display. These values represent the
current readings for the corresponding parameters mentioned alongside the lit LED.
2.1.2 LCD Programmer
The VESDA LCD Programmer is used for configuring, commissioning and maintenance of the devices on
VESDAnet. It can replace either the center or the right plate of the front cover of the detector, or can be
mounted at a remote location. A hand-held model is also available. The hand-held model is connected to the
VESDAnet socket on the termination card of the detector. 1
Legend
ADisplay
BKeys
Figure 2-4: LCD Programmer module
1For a detailed description and use of the LCD Programmer please refer to the LCD Programmer Product
Guide.

VESDA by Xtralis VESDAVLPProduct Guide
www.xtralis.com 9
2.2 Components
Legend
AFront cover EPipe inlet manifold
BTermination card FAir filter
CBlank card protecting processor card GAspirator
DChassis with laser detector chamber HMounting box/enclosure
Figure 2-5: An exploded view of the detector

VESDAVLPProduct Guide VESDA by Xtralis
10 www.xtralis.com
This page is intentionally left blank.

VESDA by Xtralis VESDAVLPProduct Guide
www.xtralis.com 11
3 Product Information
3.1 Product Specification
Supply Voltage 18 to 30 VDC
Power Consumption @24 VDC
lVESDA VLP with Blank Plates 3,000rpm lNormal: 5.8W
lAlarm On: 6.96W
lVESDA VLP with Blank Plates @ 4,200rpm lNormal: 8.16W
lAlarm On: 9.36W
lProgrammer Module lNormal: 0.6W (Backlight Off)
lAlarm On: 2.2W (Backlight On)
lDisplay Module lNormal: 1.6W
lAlarm On: 2.2W
Dimensions (WHD) 350 mm x 225 mm x 125 mm
(13.8 in x 8.9 in x 4.9 in)
Weight 4.0 kg (9 lbs) including Display and Programmer
Modules
Operating Conditions
To operate the VESDA VLP detector outside these
parameters please contact your nearest VESDA Technical
Office.
Temperature:
lDetector Ambient: 0°C–39°C (32°–103°F)
lSampled Air: -20° - 60°C (-4° - 140°F)
lTested to: -10°C - 55°C (14° - 131°F)
Humidity:
l10-95% RH, non-condensing
Storage Conditions
(Non-operational)
lBattery life: Up to 2 years
lHumidity: Dry (<95%)
lTemperature: 0° to 85°C
lMust not exposed to sunlight or other radiation
sources
Sampling Pipe Network lMaximum area of coverage: 2000 m² (21500 sq. ft.)
lMaximum length per pipe: 100 m (325 ft)
lAggregate pipe length: 200 m (650 ft)
lMinimum flow per pipe: 15 l/m
lPipe Modelling Design Tool: ASPIRE2™
These pipe lengths represent best practice for systems with single
pipe runs on each port (no branching). For longer and/or more
complex pipe arrangements, predictions of EN54-20 compliance are
determined using ASPIRE2.
Pipe Size lInternal Diameter: 15-21 mm (0.874 inch)
lExternal Diameter: 25 mm (1.05 inch)
25 mm to 1.050 inch adaptor supplied for USA market.
Relays l7 relays. Contacts rated 2A @ 30 VDC.
lProgrammable to latch or non-latch states
lProgrammable 0 - 60 seconds time delay for each
relay
Table 3-1: Detector Specifications

VESDAVLPProduct Guide VESDA by Xtralis
12 www.xtralis.com
Relays Default Configuration 7 relays:
Alert, Action, Fire 1, Fire 2, Minor Fault, Urgent Fault and
Isolate.
(7 x NO/NC contacts)
IP Rating IP30
Cable Access 8 x 25 mm (1in) knockouts in various positions
Cable Termination Screw terminal blocks (0.2-2.5 sq mm, 30-12 AWG)
Sensitivity Range 0.005 to 20.00% obs/m (0.0015 to 6.25% obs/ft.)
Threshold Setting Range lAlert: 0.005 - 1.990% obs/m
(0.0015 - 0.6218% obs/ft.)
lAction: 0.010 - 1.995% obs/m
(0.0031 - 0.6234% obs/ft.)
lFire 1: 0.015 - 2% obs/m
(0.0046 - 0.625% obs/ft.)
lFire 2: 0.020 - 20% obs/m
(0.0062 - 6.25% obs/ft.)**
** Limited to 12% obs/m 4% obs/ft. in UL mode
All shipments are factory configured for UL Mode. If the UL Mode is
switched OFF the UL listing will be voided.
Table 3-1: Detector Specifications (continued...)
Notes:
lFor operating the VESDA VLP Detector outside the parameters mentioned above please contact
VESDA Technical Support
lUL Mode: Factory Default = ON (Fire 2 set to 12% obs/m 4% obs/ft. to comply with UL268)
lFactory Default = OFF (Fire 2 Threshold can be set up to 20% obs/m 6.25%/ft)
3.1.1 Key Software Features
Event Log Up to 18,000 events stored on FIFO basis
AutoLearn lMinimum: 15 minutes
lMaximum: 15 days, 23 hrs, 59 minutes
lRecommended minimum period: 1 day
During AutoLearn, thresholds are NOT changed from
pre-set values
Referencing Compensation for external ambient conditions
Four Alarm Levels Alert, Action, Fire 1 and Fire 2
Two Fault Warning Levels Minor Fault and Urgent fault
Maintenance Aids lFilter and flow monitoring
lEvent reporting via VESDAnet or event log

VESDA by Xtralis VESDAVLPProduct Guide
www.xtralis.com 13
3.2 Dimensions
Figure 3-1: Dimensions (rear view)
Figure 3-2: Dimensions

VESDAVLPProduct Guide VESDA by Xtralis
14 www.xtralis.com
3.2.1 Default Settings
Parameter Default Values Range Access Level
Minimum Maximum
Event Log - Events
lSmoke Level Enabled n/a n/a Adm
lAlarms Enabled n/a n/a Adm
lFaults Enabled n/a n/a Adm
lUser Action Enabled n/a n/a Adm
Fire 2 Threshold 2% obs/m
(0.625% obs/ft)
0.02% obs/m
(0.0062% obs/ft)
20.0% obs/m
(6.25% obs/ft)
Adm
Fire 1 Threshold 0.2% obs/m
(0.0625% obs/ft)
0.015% obs/m
(0.0046% obs/ft)
2% obs/m
(0.6250% obs/ft)
Adm
Action Threshold 0.14% obs/m
(0.044% obs/ft)
0.010% obs/m
(0.0031 obs/ft)
1.995% obs/m
(0.6234% obs/ft)
Adm
Alert Threshold 0.08% obs/m
(0.025% obs/ft)
0.005% obs/m
(0.0015% obs/ft)
1.990% obs/m
(0.6218% obs/ft)
Adm
Alarm Delays…Fire 2 10 Seconds 0 Seconds 60 Seconds Adm
Alarm Delays…Fire 1 10 Seconds 0 Seconds 60 Seconds Adm
Alarm Delays…Action 10 Seconds 0 Seconds 60 Seconds Adm
Alarm Delays…Alert 10 Seconds 0 Seconds 60 Seconds Adm
Delay Times Simultaneous Simultaneous Cumulative Adm
Instant Fire Disabled Enabled Disabled Adm
Change-over Times:
lDay
lNight
l07:00:00
l19:00:00
Two Seconds 11:59:58 Adm
Weekend Saturday & Sunday Adjust to suit
environment
Adjust to suit
environment
Adm
Holidays
lFirst Day
lLast Day
l1-Jan-90
l1-Jan-90
Adjust to suit
environment
Adjust to suit
environment
Adm
Smoke Change:
lChange by:
lMin. Interval
l0.02% obs/m
(0.0062% obs/ft.)
l2 seconds
l0.005% obs/m
(0.0015% obs/ft.)
l2 seconds
l0.2% obs/m
(0.0625% obs/ft.)
l10 seconds
lAdm
lDst
AutoLearn 14 Days
0 Hours
0 Minutes
0 Days
0 Hours
15 Minutes
15 Days
23 Hours
59 Minutes
Adm
Air flow Thresholds:
lHigh Urgent
lHigh Minor
lLow Minor
lLow Urgent
lDelay
l130%
l120%
l80%
l70%
l0 seconds
l105%
l105%
l25%
l25%
l0 seconds
l200%
l200%
l95%
l95%
l60 seconds
Adm
Flow Control:
lAspirator Speed 3000 RPM 3000 RPM 4200 RPM Adm
Table 3-2: Factory default settings and permissible thresholds
Other manuals for VLP
1
Table of contents
Other VESDA Smoke Alarm manuals

VESDA
VESDA VLQ-100 User manual

VESDA
VESDA LaserPLUS VLP-000 User manual

VESDA
VESDA VESDA-E VES-A00-P User manual

VESDA
VESDA lasercompact VLC-500 User manual

VESDA
VESDA VESDA-E VEP-A00 User manual

VESDA
VESDA VLP Operating manual

VESDA
VESDA VLF-500 User manual

VESDA
VESDA VESDA-E VEA User manual

VESDA
VESDA VLS-XXX User manual

VESDA
VESDA LaserCOMPACT User manual