1. PRODUCT NAME
Viking Standard Response Ordinary
Hazard Dry Horizontal Sidewall Sprin-
klers VK250, VK252, and VK254
•Adjustable Recessed
•Adjustable Standard
•Plain Barrel
Available since 2005.
2. MANUFACTURER
The Viking Corporation
210 N. Industrial Park Road
Hastings, Michigan 49058, USA
Telephone: (269) 945-9501
(877) 384-5464
Fax: (269) 945-9599
3. PRODUCT DESCRIPTION
The Viking Standard Response Ordi-
nary Hazard Dry Horizontal Sidewall
Sprinklers are thermosensitive glass-
bulb spray sprinklers, suitable for use in
areas subject to freezing. They are de-
signed for dry systems and preaction
systems where it is necessary to prevent
water or condensation from entering the
supply nipple before the sprinkler oper-
ates. They may also be installed in
spaces subject to freezing and supplied
from a wet system in an adjacent heated
area. Large orifice dry sprinklers allow
greater flows at lower pressures than
standard orifice dry sprinklers.
The sprinkler is of the Model M design
with a 5 mm glass bulb and horizontal
sidewall deflector. The Viking Standard
Response Ordinary Hazard Dry Hori-
zontal Sidewall Sprinkler is available in
several finishes and temperature ratings
to meet design requirements.
The assembly features a sealed brass
inlet and a durable, threaded steel barrel
with an electrodeposited epoxy base
coating. The seal at the threaded end of
the assembly is held in place by force
transmitted from the compression
screw, through the glass bulb and inter-
nal parts, onto a special sealing spring.
During fire conditions, the heat-sensitive
liquid in the glass bulb expands, causing
the glass to shatter, releasing the inter-
nal parts to open the waterway. Water
flowing through the sprinkler orifice
strikes the sprinkler deflector, forming a
uniform spray pattern to extinguish or
control the fire.
The Viking Standard Response Ordi-
nary Hazard Dry Horizontal Sidewall
Sprinkler may be installed with the barrel
exposed (refer to Figure 4 on page 102
k), or with one of two escutcheon styles:
•For recessed installations, a recessed
style escutcheon with up to 5/8" (15,8
mm) adjustment (see Figure 1 on page
102 I), is available.
•For standard installations, the sprin-
kler is available with an adjustable,
surface-mounted escutcheon, fin-
ished to allow up to 2" (50,8 mm) of ad-
justment (see Figures 2 and 3 on page
102 j).
Both escutcheon styles slide over the
sprinkler deflector, allowing installation
of the escutcheon after the wall finish is
applied.
Viking dry horizontal sidewall sprinklers
are available in ¼" (6,35 mm) incre-
ments for the recessed style, and in ½"
(12,7 mm) increments for the adjustable
standard escutcheon style, and the plain
barrel style, installed with no escutch-
eon.
These sprinklers may be ordered in min-
imum lengths from 1-1/2" (38,1 mm) for
the adjustable standard style, 3" (76,2
mm) for the plain barrel style, and 3-1/4"
(82,5 mm) for the adjustable recessed
style. They have listings and approvals
with a maximum length of 45-1/2" (1 156
mm) for the adjustable standard style*,
47" (1 194 mm) for the plain barrel style*,
and 47-1/2" (1 207 mm) for the adjust-
able recessed style*.
* Lengths exceeding the standard length are avail-
able, with no approvals, on a “made-to-order” ba-
sis:
•Recessed Dry HSW up to 65-1/2” (1 664 mm).
• Adjustable Standard Dry HSW up to 63-1/2” (1
613 mm).
• Plain Barrel Dry HSW up to 65” (1 651 mm).
Contact the manufacturer for more information.
4. TECHNICAL DATA
LISTINGS
Refer to the Approval Chart on page 102 I.
Glass-bulb fluid temperature rated to
-65 °F (-55 °C).
Rated to 175 psi (1 207 kPa) water work-
ing pressure.
Thread Size: 1" NPT or 25 mm BSP
Minimum Operating Pressure: 7 psi
(48,3 kPa)
Nominal K-Factor: 8.0 U.S. (11,5 met-
ric**) for lengths up to 20". For
lengths exceeding 20", refer to Fig-
ure 5 on page 102 k.
**Metric K-Factor shown is for use when pressure is
measured in kPa. When pressure is measured in
BAR, multiply the metric K-Factor shown by 10.0.
Factory tested pneumatically at 100 psi
(685 kPa).
SPRINKLER MATERIALS
Frame: Brass Castings UNS-C84400
Deflector: Brass UNS-C51000
Bulb: Glass, nominal 5 mm diameter
Belleville Spring Sealing Assembly:
Nickel Alloy, coated on both sides
with Teflon Tape
Spring Base: Brass UNS-C31400 or
UNS-C31600
Screw: Brass UNS-C36000
Pip Cap: Brass UNS-C36000
Pip Cap Adapter: Brass UNS-C36000
Orifice: Copper UNS-C21000
Gasket: Buna-N
Tube: ERW Hydraulic Steel Tube
Sprinkler 102 h
September 16, 2005
TECHNICAL DATA
STANDARD RESPONSE
ORDINARY HAZARD
DRY HORIZONTAL SIDEWALL
SPRINKLERS (VK250, VK252, VK254)
Form No. F_010105
Note: Units of measure in parentheses may be approximations.
Adjustable
Standard
Plain
Barrel
Adjustable
Recessed
Sprinkler Temperature
Classification
Nominal Sprinkler Temperature
Rating (Fusing Point)
Maximum Ambient
Ceiling Temp.1
Bulb
Color2
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue
1Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location,
and other requirements of the Authority Having Jurisdiction. Refer to specific installation
standards.
2Frames of decorative sprinklers are not color coded. The temperature rating is stamped on
the deflector.
Table 1
Replaces page 102 h-l, dated Sept. 8, 2005 (corrected to
remove FM Approval and revised the K-Factor graph).