manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Visonic
  6. •
  7. Security System
  8. •
  9. Visonic MAESTRO-1600 User manual

Visonic MAESTRO-1600 User manual

This manual suits for next models

1

Other Visonic Security System manuals

Visonic PowerG SR-740 PG2 User manual

Visonic

Visonic PowerG SR-740 PG2 User manual

Visonic POWERMAX - User manual

Visonic

Visonic POWERMAX - User manual

Visonic POWERMAXCOMPLETE PANEL - Assembly instructions

Visonic

Visonic POWERMAXCOMPLETE PANEL - Assembly instructions

Visonic POWERMASTER-10 User manual

Visonic

Visonic POWERMASTER-10 User manual

Visonic PowerMaster-10 G2 User manual

Visonic

Visonic PowerMaster-10 G2 User manual

Visonic POWERMASTER-10 Assembly instructions

Visonic

Visonic POWERMASTER-10 Assembly instructions

Visonic MCS-730 User manual

Visonic

Visonic MCS-730 User manual

Visonic PowerMax Complete User manual

Visonic

Visonic PowerMax Complete User manual

Visonic POWERMAXEXPRESS - INSTALLATION 2 Assembly instructions

Visonic

Visonic POWERMAXEXPRESS - INSTALLATION 2 Assembly instructions

Visonic MCS-710 User manual

Visonic

Visonic MCS-710 User manual

Visonic SR-730 PG2 - User manual

Visonic

Visonic SR-730 PG2 - User manual

Visonic TOWER 10 AM - User manual

Visonic

Visonic TOWER 10 AM - User manual

Visonic MCS-720 User manual

Visonic

Visonic MCS-720 User manual

Visonic POWERMAX - Assembly instructions

Visonic

Visonic POWERMAX - Assembly instructions

Visonic POWERMAX - Instructions for use

Visonic

Visonic POWERMAX - Instructions for use

Visonic PowerMaster-10 G2 User manual

Visonic

Visonic PowerMaster-10 G2 User manual

Visonic PowerMaster-10 G2 User manual

Visonic

Visonic PowerMaster-10 G2 User manual

Visonic MCT-211 User manual

Visonic

Visonic MCT-211 User manual

Visonic POWERMAXEXPRESS - Assembly instructions

Visonic

Visonic POWERMAXEXPRESS - Assembly instructions

Visonic PowerMax10 User manual

Visonic

Visonic PowerMax10 User manual

Visonic GB-501 PG2 User manual

Visonic

Visonic GB-501 PG2 User manual

Visonic POWERMASTER-10 User manual

Visonic

Visonic POWERMASTER-10 User manual

Visonic POWERMAX - User manual

Visonic

Visonic POWERMAX - User manual

Visonic POWERMASTER-10 Assembly instructions

Visonic

Visonic POWERMASTER-10 Assembly instructions

Popular Security System manuals by other brands

Polon-Alfa 4000 Installation and maintenance manual

Polon-Alfa

Polon-Alfa 4000 Installation and maintenance manual

Nexcom NViS 14162 Series user manual

Nexcom

Nexcom NViS 14162 Series user manual

Eminent EM8670 Quick install

Eminent

Eminent EM8670 Quick install

urmet domus alpha 1060 INSTALLATION AND USE BOOKLET

urmet domus

urmet domus alpha 1060 INSTALLATION AND USE BOOKLET

SmartPool YardGuard YG03 manual

SmartPool

SmartPool YardGuard YG03 manual

DSC PC5964 Mounting instructions

DSC

DSC PC5964 Mounting instructions

Secure USAB-1 operating instructions

Secure

Secure USAB-1 operating instructions

B&B 480 SERIES Operation & maintenance manual

B&B

B&B 480 SERIES Operation & maintenance manual

ADEMCO VISTA-20P Series Installation and setup guide

ADEMCO

ADEMCO VISTA-20P Series Installation and setup guide

Inner Range Concept 2000 user manual

Inner Range

Inner Range Concept 2000 user manual

Johnson Controls PENN Connected PC10 Install and Commissioning Guide

Johnson Controls

Johnson Controls PENN Connected PC10 Install and Commissioning Guide

Aeotec Siren Gen5 quick start guide

Aeotec

Aeotec Siren Gen5 quick start guide

Swann SW-P-MC2 Specifications

Swann

Swann SW-P-MC2 Specifications

Ecolink Siren+Chime user manual

Ecolink

Ecolink Siren+Chime user manual

EDM Solution 6+6 Wireless-AE installation manual

EDM

EDM Solution 6+6 Wireless-AE installation manual

Siren LED GSM operating manual

Siren

Siren LED GSM operating manual

Detection Systems 7090i Installation and programming manual

Detection Systems

Detection Systems 7090i Installation and programming manual

FRIEDLAND MA10 Installation and operating instructions

FRIEDLAND

FRIEDLAND MA10 Installation and operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

DE5110 1
0$(67520$(6752'/
Computerized, Multi-Function 8 to 16 Zone Alarm
Control/Communicator Installation Instructions
Table of Contents
1. INTRODUCTION 25. KEYPAD DISPLAY UNITS 12
1.1 S
y
stem Overview 2 5.1 Ke
y
pad t
y
pes 12
1.2 List of Components 2 5.2 LED ke
y
pads KP-1001/8 and KP-1001/16 12
1.3 S
y
stem Confi
g
urations 3 5.3 KP-1003 - Ke
y
pad with Lar
g
e LCD 14
2. SPECIFICATIONS 3 5.4 KP-1002 - Ke
y
pad with Re
g
ular LCD 14
2.1 General Data 3 5.5 Mountin
g
the Ke
y
pad/Displa
y
Units 14
2.2 Communicator Characteristics 4 5.6 Connectin
g
the Ke
y
pad to the Bus 15
2.3 Siren Driver Data 5 6. EXP-1600 ZONE EXPANDER OPTION 15
2.4 Ph
y
sical Properties 5 6.1 Description and Use 15
3. THE ALARM CONTROL CABINET 5 6.2 Mountin
g
16
3.1 Alarm Control Module Description 5 6.3 Wirin
g
17
3.2 Power Pack Kit PK-1 5 7. SIR-1000 SIREN DRIVER OPTION 18
3.3 Optional Enhancement Kits 6 7.1 Description and Use 18
3.4 Mountin
g
the Alarm Control Cabinet 7 7.2 Mountin
g
18
3.5 Wirin
g
the Alarm Control Module 7 7.3 Wirin
g
18
3.6 Software and Hardware Reset 9 8. KEYPAD BUS LENGTH CONSIDERATIONS 18
4. DL-1000 TWO-WAY COMMUNICATOR 10 8.1 Problem Anal
y
sis 18
4.1 Description and Use 10 8.2 Technical Data 19
4.2 Operation Routine 10 8.3 Calculatin
g
Method 19
4.3 Mountin
g
12 APPENDIX A - REMOTE AND LOCAL COMPUTER 20
4.4 Wirin
g
12 APPENDIX B - SYSTEM DATA RECORD 21
2DE5110
,1752'8&7,21
 6\VWHP 2YHUYLHZ
The MAESTRO-1600 is a programmable modular alarm control
system, designed to be easily customized as required by the end
user. The simplest version consists of an 8-zone control module
that operates in conjunction with one or several stylish
keypad/display units. Two types of LED keypads and two types of
LCD keypads are available.
By addition of a two-way communicator - the DL-1000 - the
MAESTRO-1600 becomes MAESTRO-1600DL. The communi-
cator reports events to central stations or private telephones, and
also permits data download / upload from a remote terminal.
Power pack kits adapted to the requirements in the country of use
are supplied as requested. A power pack kit consists of a power
transformer and an AC input terminal block with a built-in fuse.
Optional modules such as a zone expander and a siren driver are
also available for system enhancement.
 /LVW RI &RPSRQHQWV
• The control module: This module accommodates all control
circuitry and operation software for a programmable 8-zone
alarm system.
• DL-1000: A two-way digital communicator. It reports events to
two central stations or to four private telephones (or to a pager).
In addition, it accepts programming data and control commands
from remote download/upload terminals. This module plugs into
a socket at the left-hand edge of the system control module.
• Keypad / display units (ordered separately): These units
enable the installer and the user to enter their commands and
provide visual and audible feedback for every action. Four types
are available, as described in Sec. 4.
• PK-1 power pack kit (ordered separately): Step-down
transformer with 16 VAC output and fused AC input terminal
block. The kit is adapted to the AC mains voltage in the country
of use and to the regulatory requirements in that country.
• 12V backup battery (ordered separately): Provides operating
power in case of an AC failure.
Figure 1.1 Fully Equipped MAESTRO-1600DL Housing
• SIR-1000 (option): A siren driver module that generates a
swept-tone audio signal, used for driving internal or external
loudspeakers. This add-on module is described in Sec. 6.
• TK1 tamper switch kit (option): Protects the alarm control
cabinet against tampering; actuated when the front lid is
opened.
DE5110 3
• Momentary action Keyswitch (option): If one of the zones is
defined as a "keyswitch zone", you may install a keyswitch for
arming/disarming the system (in the AWAY mode only).
 6\VWHP &RQILJXUDWLRQV )LJ 
An alarm system based on the MAESTRO-1600DL must include,
as a minimum, the units which are shaded in Fig. 1.2. Each
optional unit (shown in dotted lines) contributes additional
capabilities to the alarm system.
Various detectors must be wired to the control module's zone
inputs, same as in any other alarm control panel. The detectors
are not shown in the diagram, but their existence is suggested by
the zone loop circuits.
A.All servicing should be undertaken by qualified services
personnel.
B.Electrical wiring must comply with the local standards and
regulations that are valid at the time of installation.
C.Do not perform service or repair operations unless the mains
power supply to the control panel is cut off by the circuit
breaker.
Figure 1.2 MAESTRO-1600DL, System Block Diagram
63(&,),&$7,216
 *HQHUDO 'DWD
Number of Zones: 8 or 16 (with expander), programmable
attributes.
Programmable Zone Types: Instant, delayed type 1, delayed
type 2, follower type 1, follower type 2, 24 hours (bell), 24 hours
(bell/ buzzer), fire, keyswitch.
Additional Zone Attributes: Priority, Perimeter, Chime, Silent
Alarm Loop Type: End-of-Line (E.O.L.), 10 kΩ
Control Facilities: Installer code, master code, 6 users codes and
one "maid code" - 4 digits each. Keyswitch option also available.
Download/Upload: Full control and data download/upload from a
remote computer; partial control from a remote DTMF telephone.
Arming Modes: AWAY, HOME, AWAY-INSTANT and
HOME-INSTANT
Disarming Modes: Regular or "ambush"
Emergency Pushbuttons: Quick-action keys A, B and C
Alarm Types: Silent or bell/buzzer, as programmed
Audible Alarm Modes:
Continuous (initiated by all zones except for fire zones)
Pulsating (initiated by fire zones only).
Bell/Siren Timeout: Programmable, 1 to 99 minutes. If the zone
remains open, the alarm renews 30 seconds after timeout. The
number of alarm renewals is also programmable (1 to 99 times).
Exit Delay: Programmable, 0 to 99 seconds
4DE5110
Entry Delay: Programmable, 0 to 99 seconds.
Special Functions: Zone bypass, force arming, false alarm
cancellation
Data Retrieval: Alarm memory and trouble indications
Test Modes: Walk, Bell/Siren/Battery, Keypad, Communicator
Alarm Relay Contact Ratings: 5A @ 24 Volts (SPDT).
Supply Voltage: 230 VAC (115 VAC optional).
Power Transformer AC Output: 16 VAC, 40 VA.
Auxiliary DC Output (via the 12VDC terminals): 12 VDC, 700
mA max.
Siren/Bell DC Output (via the V-BELL jumper): 3 A max.
Maximum Number of Keypads: 4
Keypad Current Drain (Max.)
KP-1001/8 & KP-1001/16: 35 mA
KP-1002: 45 mA
KP-1003: 60 mA
PGM Output Current Sinking Capability: 100 mA max.
Fuse Ratings:
230 VAC input - 315 mA (time lag type T315 mA/250V
5X20mm)
12 VDC for detectors, keypads and accessories - 1A;
12 VDC supply for bell - 3A;
Siren driver - 1.5A.
Standby Battery: Lead-acid type, 12 V, up to 6 Ah.
Charging Current: Electronically limited to 300 mA
 &RPPXQLFDWRU &KDUDFWHULVWLFV
Programmable Central Station Telephone Numbers
Channel 1: One first priority number and one backup number
Channel 2: One second priority number and one backup number
Programmable Private Telephone Numbers: One temporary
"follow me" number, 3 "permanent" numbers
Phone Number Length: 16 digits max, including hexadecimal
digits for pauses
Dialing Methods: DTMF or Pulse, as programmed
Mark/Space Value Options - 40/60, 34/66, 60/40, 66/34
Central-Station Related Parameters
Communication Protocols:
DTMF protocol (at the rate of 10 digits per second),
Tone pulse protocol with data/handshake tones of 1900/1400 or
1800/2300 Hz
Additional protocols in future versions.
Data Rate Options (for tone pulse protocol): 10, 20, 33, 40 pps
Data Verification Options: Double round or Checksum
Report Types: Alarm/restore, arm/disarm and system
maintenance events
Report Destinations: Any report type may be linked to any one
of these reporting destinations – 1st channel only, 2nd channel
only, 1st and 2nd channels or none altogether.
Protocol Formats: 3/1, 3/2, 4/1, 4/2 and 4/2 + checksum.
Private-Telephone Related Parameters
Report Types: Regular alarms (two-tone siren) and 24-hour
zone alarms (swept-tone siren).
Report Destinations: All 4 telephones or none altogether.
 6LUHQ 'ULYHU 'DWD
Alarm signal: Continuous swept-tone siren (all alarms except
FIRE); pulsating swept-tone siren (FIRE).
Output Power: 10 W max.
Loudspeaker Impedance: Not less than 4 ohms
 3K\VLFDO 3URSHUWLHV
Operating Temperature Range: 0°C to 49°C (32°F to 120°F)
Storage Temperature Range: -20°C to 60°C (-4°F to 140°F)
Dimensions (H x W x D):
Metal Cabinet: 262 x 315 x 74 mm (10-5/16 x12-3/8 x2-15/16 in.).
Keypads (all models): 159 x112 x 30 mm (6-1/4x4-3/8 x1-3/8 in.).
Optional UPB-3 Cabinet: 165x108x38mm(6-1/2x4-1/4x1-1/2 in.).
Weight:
Metal Cabinet with Control Module & Communicator:
2.180 kg (4.8 lb).
LED Keypad KP-1001: 224 g (7.9 oz)
Medium LCD Keypad KP-1002: 253 g (8.9 oz)
Large LCD Keypad KP-1003: 273 g (9.6 oz)
DE5110 5
7+($/$50&21752/&$%,1(7
 $ODUP &RQWURO 0RGXOH 'HVFULSWLRQ
As the nerve center or the brain of the entire alarm system, this
programmable module includes the hardware and firmware
necessary for managing the system with or without auxiliary
modules - the communicator, zone expander and the siren driver.
It must be stressed, though, that at least one keypad/display unit is
required to set up a workable 8-zone alarm system.
Figure 3.1 The MAESTRO-1600 Control Module
The control module (Fig. 3.1) comes mounted within the alarm
control cabinet. Its printed circuit board is equipped with a socket
for the communicator module (at the left hand edge) and a socket
for the siren driver module (at the right hand edge).
Operating power is supplied from a 16 VAC / 40 VA stepdown
transformer - part of the power pack kit PK-1. The control module
accommodates a voltage regulator and a charger for the backup
battery. Regulated 12 VDC output for the detectors, all the
keypads and other external devices is obtained via an on-board 1A
fuse marked "ACCESSORIES". Two pairs of 12VDC output
terminals are provided, to allow easier connection of a large
number of accessories.
The ALARM relay has changeover (Form 1C) dry contacts rated at
5A/24 Volts, and can be used to activate alarm devices such as
sirens or bells (Fig. 3.7). A jumper marked V-BELL connects the
12 VDC supply to the common (C) contact of the alarm relay, via a
3A fuse marked BELL. With the jumper installed across the two
V-BELL pins, the bell or siren can be wired between the N.O.
contact of the relay and the negative (–) supply terminal.
 3RZHU 3DFN .LW 3.
The AC power pack for the MAESTRO-1600 is delivered
separately in kit form, to suit the mains voltage and the particular
regulations in the country of use. The kit includes a step-down
transformer, an AC mains terminal block with a built-in fuse holder
and a 0.3 A fuse, mounting hardware and a terminal identification
sticker. As an essential part of the alarm control system, the power
pack must be installed in the metal cabinet (Fig 3.2) and wired
accordingly (Fig. 3.3).
A. Align the transformer mounting ears with the 2 stand-off screws
on the rear wall of the case and let the screws pass through the
holes. Mount a flat washer, a lock washer and a nut (in this
order) on each screw and tighten both nuts.
B. Place AC mains terminal block with its ground lug over the
stand-off grounding screw, and the hole nearest to the fuse
holder over press nut. Pass a screw (supplied in the kit)
through that hole and thread it into press nut. Tighten screw
well. Put a lock washer and a nut over the stand-off grounding
screw and tighten nut to fasten ground lug to the case.
C. Remove the paper backing from the terminal identification
sticker and attach the sticker to the rear wall of the case, as
close as possible to the AC terminal block.
6DE5110
Figure 3.2 Assembling the PK-1 Power Pack
D. The primary winding of the transformer is already connected to
the terminal block, as shown in Fig. 3.3. Connect the
transformer's 16 VAC winding (the 2 free wires) across the
control module's 16 VAC terminals.
E. Connect AC mains input – Phase (~), Neutral (0) and Ground
() to terminal block (see Fig. 3.3). Make sure your
installation complies with the following safety requirements list:
• Conductors carrying the AC mains voltage should be
physically separated from other conductors used to wire
the alarm system.
• The cross section of the mains input conductors must be
not less than 1.0 mm2(17 AWG).
• The diameter of the plastic conduit for the mains cable
should be at least 16 mm (5/8 in.)
• Insert the plastic conduit as far as 3 cm (1-1/8 in.) into the
metal case, to protect the mains conductors from the sharp
edges of the entry hole.
• All 3 AC power supply leads must be tied together firmly
with a plastic tie wrap close as close as possible to the
terminal block to which these leads are connected.
• The phase (~) input wire must be routed via a single-pole, 3A
exclusively dedicated circuit breaker.
Figure 3.3 AC Mains Input Wiring
 2SWLRQDO (QKDQFHPHQW .LWV
Two optional kits are offered for enhancing the alarm control system:
LK-1: key-operated lock for the front lid of the metal cabinet (see A
below)
TK-1: tamper switch kit (see B below)
A. Assembling the Front Lid Lock Kit (LK-1)
The LK-1 lock kit includes the lock itself and mounting hardware as
shown in Fig. 3.4. To assemble the lock, proceed as follows:
(1) Align the lock with the pre-punched hole in the lid, insert it into
the hole and use the nut to fasten it to the front lid. Tighten the
nut with a spanner wrench.
(2) Mount the rotation limiter over the rotating part of the lock,
making sure that the small cam on the lock body is positioned
between the two teeth that limit the rotation angle.
(3) Mount the lock bar over the rotation limiter.
(4) Use spacer and the screw to tighten the entire lock assembly.
(5) Insert the key into the lock and check whether the rotation
limiter allows the lock to be rotated in the desired direction.
B. Assembling the Tamper Switch Kit (TK-1)
The TK-1 kit includes the tamper switch with two wires soldered to
its terminals and two sheet metal screws. To mount the switch on
the tamper bracket, proceed as follows:
(1) Align the tamper switch with the bracket as shown in Fig. 3.5.
DE5110 7
(2) Use the two sheet metal
screws to fasten the
switch. to bracket. Tighten
the screws well, but do not
overtighten because this
may break the switch.
(3) Verify that the switch
contacts close when the
front lid is closed.
(4) Connect the tamper switch
wires to the zone terminals
of a zone dedicated to
24-hour tamper protection.
Figure 3.4 LK-1 Assembly
 0RXQWLQJ WKH $ODUP &RQWURO &DELQHW
Choose a protected, easily accessible location, preferably where
uninterrupted AC power is available. To open the front lid, simply
swing it on its hinges to the left. The following steps must be taken
before actual mounting:
A. Be sure to assemble the power pack kit within the metal
cabinet (Para. 3.2).
B. If you have an LK-1 lock kit,
assemble it as shown in
Para. 3.3A. If you did not
order the optional lock kit,
insert the plastic plug
supplied with the system into
the hole in the front lid (align
the plug to fit the shape of
the hole before pushing it in).
C. If you ordered tamper switch
kit TK-1, mount it as shown
in Para. 3.3B.
Figure 3.5 TK-1 Assembly
D. A ground strap is supplied with your system (Fig. 3.4). Mount it
in place and tighten it well. The required lock washers and nuts
are packed together with the ground strap.
Mounting and wiring holes are provided on the rear wall of the
cabinet. If necessary, punch out the wiring knockouts at the sides,
to suit your particular installation. Mount the cabinet complete with
the alarm control module and the power pack on the wall, using
the 4 mounting holes at the rear (Fig 1.1). The front lid may be
secured to the cabinet with 4 sheet metal screws, or with the
optional lock (LK-1).
 :LULQJ WKH $ODUP &RQWURO 0RGXOH )LJ 
Caution! Do not connect the AC power or the battery until all
other wiring is completed
.
Wiring instructions are given by order of terminals, from left to right.
Terminals Wiring Information
1 2 3 4
BUS These are the keypad bus terminals for the various
keypads and for the expander module. Each terminal
should be wired to its identically numbered counterpart
in the keypad/display unit or expander module. Refer to
Sec. 8 - Keypad Bus Length Considerations.
Z1 Zone 1 terminal. A normally closed (N.C.) zone loop
will be formed if the alarm contacts of all detectors in
this zone are connected in series between this
terminal and the nearest (–) terminal. A 10 kΩ
End-of-Line (EOL) resistor must complete the series
connected loop at the point most distant from the
zone terminals.
Note: If a zone is defined as a keyswitch zone and
used for arming/disarming, a 10kΩresistor must be
wired across the keyswitch terminals
.
(–) A negative common terminal. Each zone loop is
connected between the respective zone terminal and
a (–) terminal.
Z2 The wiring instructions are the same as for zone 1,
with which zone 2 shares the (–) terminal.
Z3 - Z8 Three pairs of zones, with a (–) terminal between
each pair. Wiring instructions are the same as for the
first pair of zones (Z1 and Z2).
8DE5110
Terminals Wiring Information
PGM 1 This is a programmable open-collector auxiliary
output (100 mA max.). You may program this output
to pull to ground upon communication failure.
Alternatively, you may program it to pull to ground for
as long as the system is armed (for controlling the
alarm memory function in certain detectors), or for
lighting an remotely located LED to indicate that the
system is armed.
An LED with 1kΩresistor in series may be wired
between PGM1 and any one of the 12 V+ terminals,
as shown in Fig. 3.6. A relay can also be wired as
shown with PGM2.
PGM 2 This is a programmable open-collector auxiliary
output (100 mA max.). You may program this output
to pull to ground during exit and entry delays, or to
pull to ground whenever the system is ready - all
zones are secured and ready to be armed. In the first
case, a courtesy light control relay or a warning
buzzer may be wired between PGM2 and any one of
the 12 V+ terminals (Fig. 3.6). In the second case, a
READY LED with a 1kΩresistor in series may be
wired between PGM2 and any one of the 12 V+
terminals.
PGM 3 This is a programmable open-collector auxiliary
output (100 mA max.). You may program this output
to reset smoke detectors after the first detection of
smoke, or to pull to ground upon any alarm and return
to the open circuit state only by disarming or arming
the alarm system (strobe output). In the first case,
PGM3 must be wired as the "ground return" for the
smoke detectors used in the system, as shown in
Figure 3-6. In the second case, a strobe light control
relay may be wired between PGM3 and any one of
the 12 V+ terminals.
ALM This is an open-collector output that pulls to ground
during alarm and returns to the open circuit state
when the alarm times out. It may be used to activate
an auxiliary alarm device.
ALARM The N.O., C and N. C. terminals represent the
corresponding output relay contacts. You may wire
the alarm relay contacts to switch on an external
siren by supplying +12 VDC to the siren as shown in
Fig. 3.7.
Note: If the V-BELL jumper is installed across the
two V-BELL pins, +12VDC is applied to the output
relay C contact. The N.C. contact will also be at
+12VDC potential, but will become "floating" when
an alarm occurs. If you wish to use the output
relay as a "floating" dry contact switch, be sure
to remove the V-BELL jumper!
12 VDC Two pairs of 12 VDC supply terminals. Up to 700 mA
maximum current can be obtained across the [+] and
[–] terminals, but this includes the current. drawn by
the keypads, the zone expander and the various
detectors.
16 VAC AC power input terminals. The system is powered by
16 VAC output from a 40 VA power transformer,
which changes according to the country of use. The
secondary winding of the transformer (the two free
wires extending from the transformer) must be
connected across these terminals.
DE5110 9
Figure 3.6 Control Module Wiring
 6RIWZDUH DQG +DUGZDUH 5HVHW
When installing a new
MAESTRO-1600, you should
always replace the factory
default installer code with a
secret code, known only to
yourself (see Installer's Prog-
ramming Guide, Location 01). In
the User's Guide, the master
Figure 3.7 Connecting a Siren
user is similarly instructed to program a secret master code,
known only to himself.
It is highly unlikely that the user should forget his code, but if he
does - you can help him by performing a "software reset" (see
Location 41 in the Installer's Programming Guide). This reset can
not be carried out without your installer code.
It is also quite unlikely that you lose your installer code, thereby
losing your ability to access the system for reprogramming.
However, if you do lose the code, don't lose hope: you can still
perform a "hardware reset", which will restore the system to the
factory default installer and master codes.
The hardware reset procedure is as follows:
• Use a jumper bar to short together the two CLEAR pins on the
control module (Fig. 3.6 for location of the pins).
• Disconnect all power - the AC mains as well as the battery.
• Reconnect the battery, wait 5 seconds, remove the short circuit
from the CLEAR pins and disconnect the battery once more.
• Reconnect the battery and the AC mains. The system will revert
the default Installer code (160 0) and Master User code (1234 ).
When done, use the factory default installer code to access the
installer mode and program a new secret installer code (see
Location 01 in the Installer Programming Guide). Also inform
the master user that he must reprogram his secret Master Code.
10 DE5110
'/7:2:$<&20081,&$725
 'HVFULSWLRQ DQG 8VH
The DL-1000 communicator module is supplied as part of the
MAESTRO-1600DL.
A board-to-board connector on the DL-1000 left edge (Fig. 4.1)
mates with a socket at upper left edge of the alarm control module.
The communicator is triggered into action by the alarm control
module, and can be programmed to communicate with central
stations or private telephones, as required. The communication
protocol is selected in the course of programming (refer to the
programming manual).
The communicator is designed and programmed to play two roles:
• Event Reporting: Once an event occurs, the communicator
calls the telephone numbers programmed by the installer or by
the user. When communication is established, the
communicator reports the event (or events) by sending DTMF
or pulse code sequences (if the central station mode has been
selected) or two kinds of alarm tone signals (if private telephone
mode has been selected). Acknowledgement is expected from
the called party for each event reported, or else communicator
will report the event repeatedly until factory-programmed
number of message repetitions is exceeded.
• Interaction with a Remote Computer: The DL-1000 and the
control module combine together to handle Download/Upload
requests from a remote computer. These operations require a
remote modem - the RM-1000 - at the remote computer's end of
the line and the RPM-1 software package (see Appendix A).
The remote modem and the software also allow full control of
the alarm system by the remote computer (arming, disarming,
bypassing zones, displaying zone status etc.). To assume
control, the remote station operator establishes telephone
communication with the protected premises (see Chapter 6 in
the programming manual). DTMF code sequences are then sent
by the remote station over the telephone line. The DL-1000
interprets these DTMF codes and transfers commands, new
parameters and data-upload requests to the control module.
The control module will carry out the commands, or reprogram
itself or allow upload, as the case may be.
 2SHUDWLRQ 5RXWLQH
A. Reporting to Central Stations
Once triggered into operation by the occurrence of an event, the
communicator carries out the following sequence of operations:
(1) It seizes the line and waits 10 seconds for dialing tone.
(2) Upon detection of a 2-second long dialing tone, the
communicator starts calling the first-priority telephone number
of the first central station.
Note: Without dial tone, the communicator goes "on hook" for
about 5 seconds, then seizes the line again to wait for dial tone.
If there is still no tone, dialing starts anyway, except in cases
where a hexadecimal "D" is programmed as a prefix to the
telephone number. With a D-prefix, dialing will not take place
unless a dial tone is detected (see the Programming Manual for
additional information).
(3) Once the call is answered, the communicator waits 16 seconds
for a GO-AHEAD signal from the central station. To prolong
this standby period, a hexadecimal E programmed at the end of
the telephone number will introduce an additional 10 second
delay. If there is no GO AHEAD, the communicator will go on
hook and redial the second priority phone number for that
central station.
Note: If there is no second phone number, the first number will
be called again until the preprogrammed maximum number of
dialing attempts is reached.
(4) If a GO-AHEAD signal is received within 16 seconds, the
communicator reports the first event in its transmission queue