
Owner’s Manual
SunStat®View
Programmable Thermostat
Model 500750
The SunStat View model 500750 is designed to operate either a 120 VAC or
240 VAC resistance oor heang system. It comes with an easy setup wizard, a
typical program ready to go, and a GFCI inside to meet safety needs.
Please follow this manual for installaon and operang instrucons. Leave
these instrucons with the homeowner.
Installaon
Cautions to Follow
You are required to thoroughly read all installaon instrucons and product
safety informaon before beginning the installaon of this product. FAILURE
TO COMPLY WITH PROPER INSTALLATION AND MAINTENANCE INSTRUCTIONS
COULD RESULT IN DAMAGE TO THE SYSTEM OR ELECTRIC SHOCK CAUSING
PROPERTY DAMAGE, PERSONAL INJURY AND/OR DEATH. Was is not
responsible for damages resulng from improper installaon and/or
maintenance.
Local building or plumbing codes may require modicaons to the informaon
provided. You are required to consult the local building and plumbing codes
prior to installaon. If this informaon is not consistent with local building or
plumbing codes, the local codes should be followed.
CAUTION: This product requires electrical wiring. It is recommended that
this product is installed by a qualied technician. Local codes may require
this product be installed by an electrician. Prior to installaon, consult
your local codes for what is acceptable in your area. To the extent this
informaon is not consistent with local codes, the local codes should be
followed.
ALWAYS: Wire all circuits as Class 1, Electric Light and Power Circuits
ALWAYS: Wire all circuits with insulaon rated 600V minimum.
ALWAYS: Mount this control only to a grounded metallic box or a nonmetallic
box.
ALWAYS: Use power supply wires suitable for at least 90°C.
WARNING: High voltage – disconnect power supply before servicing.
WARNING: The GFCI (ground-fault circuit interrupter) in this thermostat
control does not protect against shock if both bare conductors are touched
at the same me.
WARNING: Do not exceed 15 amps on this thermostat control. Doing so will
cause risk of re hazard and damage.
WARNING: Make sure the house power supply voltage matches the voltage
rang of the oor heang system. Do not apply 240 VAC to a 120 VAC rated
system. Connecng the wrong voltage may cause overheang and damage
to the system, the control, oor coverings, etc.
Parts Needed
Contents of package:
Unpack the thermostat control and make sure everything is in good condion.
Do not use a damaged control or part. The package comes with these items:
(1) Thermostat
(1) Thermostat oor sensor
(4) Wire nuts (Marees®)
(2) Mounng screws
(1) Screwdriver
Tools and supplies needed:
- No. 2 Phillips screwdriver
- Hole saw (if installing in an exisng wall)
- Wire strippers, wire cuers, and other electrical tools
- Electrical wall box (plasc or metal)*
*NOTE: A single-gang extra-deep box allows sucient space to connect 1 or 2
heang mats or cables. For 3 heang mats or cables, a 4-inch square extra-deep
electrical box with a single-gang “mud ring” is necessary. Alternately, a juncon
box may be installed to connect mulple heang mats or cables, then run
power supply wire from the juncon box to the control electrical box. See the
Installaon Instrucons provided with the oor heang system for
more details.
Locang the Control
Find a suitable locaon for the control. It is designed for indoor dry locaon only.
It may be placed on an insulated or uninsulated wall, preferably an interior wall
to avoid overheang from outside sun heat. Keep it away from water sources
such as sinks, showers, and bathtubs as well as heat sources such as hot-water
piping, heat ducng, wall-mount lighng, and direct sunlight. Locate it at a
suitable height, normally about 4-1/2’ to 5’ (1.4 m to 1.5 m) from the oor.
Mounng the Electrical Box
When mounng on an exisng wall, cut the opening for the electrical box for the
control. To make it easier to pull the wiring, wait to install the electrical box unl
aer all wiring is drawn into this opening.
When mounng on an open wall, secure the electrical box for the control to the
wall stud.
When mounng on an open wall, conduit from the electrical box to the oor is
recommended (check local codes for requirements) for addional protecon.
Install one conduit for the oor sensor. Install another conduit for the oor
heang system power leads. Refer to the Installaon Instrucons supplied with
the oor heang system for addional installaon details.
Wiring
WARNING: Turn o power at the circuit breaker before doing any electrical
work.
House Wiring
A qualied person should run a dedicated circuit from the main circuit breaker
panel to the control locaon. If a dedicated circuit is not possible, it is acceptable
to tap into an exisng circuit. However, there must be enough capacity to
handle the load (amps) of the oor heang system being installed and any
possible appliance, such as a hair dryer or vacuum cleaner. Avoid circuits that
have ballasted lighng, motors, exhaust fans, or hot tub pumps due to possible
interference.
The circuit breaker should be rated 20 amps for total circuit loads) up to
15 amps. A 15 amp circuit breaker may be used for total circuit loads up to
12 amps. A GFCI (ground-fault circuit interrupter) or AFCI (arc-fault circuit
interrupter) type circuit breaker may be used if desired, but is not necessary.
WARNING: Do not exceed 15 amps on this thermostat control. Doing so
will cause risk of re hazard and damage.
Pull power supply wiring to the control locaon. Leave about 6 to 8 inches (15
to 20 cm) of wire for connecons later. This wiring should be size 12 or 14 AWG
following appropriate local code requirements.
Floor Sensor
Pull the oor sensor wire up the wall (or conduit) to the control locaon, leaving
about 6 inches (15 cm) of wire for connecon later. The sensor wire may be cut
shorter if desired, but do not cut it shorter unl the sensor is fully installed (see
below).
Note: If the sensor wire is not long enough to reach the control locaon, it may
be extended an addional 15 feet (4.5 m) using minimum 20 AWG 2-conductor
unshielded wire, or an addional 50 feet (15 m) using shielded wire. When
using shielded wire, the “shield” must be connected to the lower sensor
terminal, nearest to Bus A. A juncon box may be required by local code for the
connecon to this extension wire.
Aer the oor heang system is completely installed according to its
instrucons, secure the thick sensor p to the oor. It must be located halfway
between heang wires and at least 1 foot into the heang area. Use hot-glue to
secure the sensor p and wire in place. Do not cross over a heang wire. Avoid
placing it in an area where heang wires are spaced further apart than the rest
of the oor, like a large gap between mats or cables. Avoid placing it in an area
where a heat duct or recessed light will cause improper measurements. Try to
avoid locang it where future items such as a clothes hamper or similar could
trap heat and cause improper measurement.
Finish securing the sensor wire along the oor and up the wall. At the control
locaon, cut the sensor wire shorter if needed, leaving at least 6 to 8 inches (15
to 20 cm) of wire for connecons later. Re-strip the sensor wire ends 1/8” to
3/16” (3 mm to 4.5 mm) long. If the ends are stripped longer than this they may
short-circuit, resulng in an error code.
Mat or Cable Power Leads
Pull the power lead wires from the oor heang system into the control
locaon. Leave about 6 to 8 inches (15 to 20 cm) of wire for connecons.
!
!
!
!
!
!
!