WEG CFW300 User manual

Quick Installation Guide
CFW300 Micro Drive
1 SAFETY INSTRUCTIONS
This quick installation guide contains the basic information necessary to commission the CFW300. It has
been written to be used by qualified personnel with suitable training or technical qualification for operating
this type of equipment. The personnel shall follow all the safety instructions described in this manual
defined by the local regulations. Failure to comply with the safety instructions may result in death, serious
injury, and/or equipment damage.
2 SAFETY WARNINGS IN THE MANUAL
NOTE!
It is not the intention of this guide to present all the possibilities for the application of the
CFW300, as well as WEG cannot take any liability for the use of the CFW300 which is not
based on this guide.
For further information about installation, full parameter list and recommendations, visit the
website www.weg.net.
DANGER!
The procedures recommended in this warning have the purpose of protecting the user
against death, serious injuries and considerable material damage.
ATTENTION!
The procedures recommended in this warning have the purpose of avoiding material damage.
NOTE!
The information mentioned in this warning is important for the proper understanding and
good operation of the product.
High voltages are present.
Components sensitive to electrostatic discharge.
Do not touch them.
Mandatory connection to the protective ground (PE).
Connection of the shield to the ground.
3 PRELIMINARY RECOMMENDATIONS
DANGER!
Always disconnect the main power supply before touching any electrical component
associated to the inverter. Several components can remain charged with high voltages or
remain in movement (fans) even after the AC power is disconnected or switched off. Wait at
least ten minutes after turning of f the input power for the complete discharge of the power
capacitors. Always connect the grounding point of the inverter to the protection earth (PE).
The XC10 connector does is not USB compatible, therefore, it cannot be connected to
USB ports.
This connectors ser ve only as interface between the CFW300 frequency inver ter and its
accessories.
NOTE!
Frequency Inverter may inter fere with other electronic equipment. Follow the precautions
recommended in manual available in www.weg.net.
Do not per form any withstand voltage test!
If necessary, contact the manufacturer.
ATTENTION!
Electronic boards have components sensitive to electrostatic discharges.
Do not touch directly on components or connectors. If necessary, first touch the grounding
point of the inverter, which must be connected to the protection earth (PE) or use a proper
grounding strap.
ATTENTION!
When the inverter is stored for a long period, it becomes necessary to per form the capacitor
reforming. Refer to the procedure recommended in www.weg.net.
4 ABOUT THE CFW300
The CF W300 frequency inverter is a high-performance product which allows speed and torque control of
three-phase induction motors. This product provides the user with the options of vector (VVW ) or scalar
(V/f) control, both programmable according to the application.
5 TERMINOLOGY
Tab l e 1: Terminology of the CFW300 inverte rs
Product
and Series
Model Identification
Brake Degree of
Protection
Hardware
Vers ion
Software
Vers ion
Frame
Size
Rated
Current
Phase
Number
Rated
Volt age
Ex.: CFW300 A0 1P6 S 2 NB 20 --- ---
Available
options
CFW300
Refer to Table 2 Blank = standard
NB = without braking reostática Sx = special software
DB = with braking reostática Blank = standard
20 = IP20 Hx = special hardware
Tab l e 2: Ava ilable options for each field of the nomenclature according to the rated current and voltage of the inve rter
Frame Size Output Rated
Current N° of Phases Rated Voltage Brake
A
01P6 = 1.6 A
S = single-phase power supply
1 = 110...127 Vac
NB
02P6 = 2.6 A
04P2 = 4.2 A
06P0 = 6.0 A
01P6 = 1.6 A
2 = 200...240 Vac
02P6 = 2.6 A
04P2 = 4.2 A
06P0 = 6.0 A
07P3 = 7.3 A
01P6 = 1.6 A
T = three-phase power supply
02P6 = 2.6 A
04P2 = 4.2 A
06P0 = 6.0 A
07P3 = 7.3 A
01P6 = 1.6 A
D = DC power s upply 3 = 280...340 Vdc
02P6 = 2.6 A
04P2 = 4.2 A
06P0 = 6.0 A
07P3 = 7.3 A
B10P0 = 10.0 A B = single-phase or three-phase power supply or DC 2 = 200...240 Vac
or 280...3 40 Vdc DB
15P2 = 15. 2A T = three-phas e power supply or DC
6 RECEIVING AND STORAGE
The CF W300 is supplied packed in a cardboard box. There is an identification label affixed to the outside
of the package, identical to the one affixed to the side of the inverter.
Verify whether:
The CF W300 identification label corresponds to the purchased model.
Any damage occurred during transportation.
Report any damage immediately to the carrier.
If the CF W300 is not installed soon, store it in a clean and dry location (temperature between -25 ºC and
60 ºC (-13 ºF and 140 ºF)), with a cover to prevent dust accumulation inside it.
7 IDENTIFICATION LABEL
Production order
Rated input data
(voltage, current and
frequency)
Serial number
Manufacturing date (14 corresponds
to the week and I to the year)
Rated output data
(voltage, current and frequency)
WEG stock item
Model (Inver ter
intelligent code)
Figure 1: Description of the CFW300 identification label
8 DIMENSIONS
View of th e mounting base Front view Side view
PLA
B
H
Frame
Size
A B H L P Weight Mounting
Bolt
Recommended
Torque
mm
(in)
mm
(in)
mm
(in)
mm
(in)
mm
(in)
kg
(lb) N.m (Ibf.in)
A35 .0 (1.37) 50.1 ( 1. 9 7 ) 157.9 (6.22) 70.0 (2.76) 148 .4 ( 5,8 4) 0.900 (1.98) M4 2 (1 7.7 )
B35 .0 (1.37) 50.1 ( 1. 9 7 ) 198.9 (8.08) 70.0 (2.76) 158.4 (6.24) 1.34 0 (2.9 8) M4 2 (17. 7 )
Dimension tolerance: ±1,0 mm (±0,039 in)
Figure 2: Inverter dimensions for mechanical installation
9 INSTALLATION AND CONNECTION
Environmental Conditions
Avoid:
Direct exposure to sunlight, rain, high humidity or sea-air.
Inflammable or corrosive gases or liquids.
Excessive vibration.
Dust, metallic particles or oil mist.
Environment conditions permitted for the operation of the inverter:
Temperature surrounding the inverter: 0 ºC to 50 ºC ( 32 ºF to 122 ºF) – IP20.
For temperatures surrounding the inver ter higher than the specifications above, it is necessar y to apply
of 2 % of current derating for each degree Celsius, limited to an increase of 10 ºC (50 ºF).
Air relative humidity: 5 % to 95 % non-condensing.
Maximum altitude: up to 1000 m (3.300 ft) - rated conditions.
From 1000 m to 4000 m (3.300 ft to 13.200 ft) – 1 % of current derating for each 100 m above 1000 m
of altitude.
Pollution degree: 2 (according to EN50178 and UL508C), with non-conductive pollution. Condensation
must not originate conduction through the accumulated residues.
10 ELECTRICAL INSTALLATION
DANGER!
The following information is merely a guide for proper installation. Comply with applicable
local regulations for electrical installations.
Make sure the AC power supply is disconnected before starting the installation.
The CFW300 must not be used as an emergency stop device. Provide other devices
for that purpose.
2
2
1
1
5
4
3
1 - power terminals
2 - grounding points
3 - connector of the
communication accessory
4 - control terminals
5 - conne ctor of th e I/O
expansion accessory
Frame
Size
Recommended Torque
Grounding
Points
Power
Terminal
N.m Lbf.in N.m Lbf.in
A and B 0.8 7. 2 0.8 7. 2
Figure 3: Power terminals, grounding points and recommended tightening torque
10 .1 POWER CONNECTIONS
Description of the power terminals:
L/L1, N/L2, L3 (R,S,T): power supply connection.
U, V and W: connection for the motor.
-UD: negative pole of the DC power supply.
+UD: positive pole of the DC power supply.
+BR, BR: connection of the braking resistor (available for frame size B models).
PE: grounding connection.
(a) Frame size A DC power supply (b) Frame size A single-phase and three-phase power supply
Shielding
Negati ve pole of the DC power s upply (-UD)
Shielding
Shielding
Shielding
Fuses
Positiv e pole of the D C power supply (+UD)
Disconnecting
switch
Fuses
Fuses Fuse s
PE
Disconnecting
switch
PE
PE -UD+UD
PE V
PEW UV
U W
Power
supply
PE L1 L2 L3
L1/ L
L2/N
L3*
Negati ve pole of the DC powe r supply (-UD)
Positiv e pole of the DC power s upply (+UD)
Power
supply
Disconnecting
switch
Disconnecting
switch
PE
-UD
-UD
+BR
+BR
+UD
+UD
BR
BR
PE
L1/ L
L2/N
L3
Power
supply
PE V
PEW UV
U W
PE
PE L1
L1 L2
L2 L3
L3
PE
PE V
V
PE
PE W
WU
UV
V
U
UW
W
Power
supply
(*) The powe r termin al L3 is not ava ilable in mode ls of fram e size
A single-phase
Only ava ilable f or the 10-A mod el (see table 2).
Only ava ilable f or the spe cific models of fr ame size A (s ee table 2).
(c) Frame size B DC power supply (d) Frame size B single-phase a nd thre e-phase power supply
Figure 4: (a) to (d) Power and grounding connections
10.2 INSTALLATIONS ACCORDING TO EUROPEAN DIRECTIVE OF ELECTROMAGNETIC
COMPATIBILITY
The CF W300 inverter series, when properly installed, meet the requirements of the directive of the
electromagnetic compatibility.
These inverters were developed for professional applications only. Therefore, the emission limits of
harmonic currents by the standards EN 61000-3-2 and EN 61000-3-2/A 14.
10 . 2 .1 Conformal Installation
1. Shielded output cables (motor cables) with shield connected at both ends, motor and inverter, by meanse
of a low impedance to high frequency connection. Maximum motor cable length and conduced and
radiated emission levels according to Table 6.
2. Shielded control cables, keeping the separation distance from other cables according to Table 3.2 the
user's manual.
3. Grounding of the inver ter according to instruction of the 3.2.4 Grounding Connections the user's manual.
4. Grounded power supply.
5. Use short wiring to ground the external filter or inver ter.
6. Ground the mounting plate using a flexible braid as short as possible. Flat conductors have lower
impedance at high frequencies.
7. Use sleeves for cable conduits whenever possible.
The CF W300 is suitable for application in a circuit able to supply not more than 30.000 symetric Arms
maximum of 127 / 240 V, when protected by fuses classified as indicated below:
Tab l e 3: L ist of models of CFW300 series, main electric al spe cifications
Inverter
Number of Input Phases
Power Suppl y Rated Volt age
Frame Size
Output Rated Current
Overload Currents
Maximum Motor
Circuit Breaker
Recommended Fuse
Power Wire Size
Grounding Wire Size
Dynamic Braking
I²t [A² s]
Current
Recommended Fuse WEG
Maximum Current
Recommended
Resistor
Braking rms Current
Power Wire Si ze for
DC+ and BR Terminals
[Arms]
1 min
[Arms]
[HP/ kW ]
[A]
WEG
[A]
mm²
(AWG)
mm²
(AWG)
(Imax)
[A]
[Ω]
[A]
mm²
(AWG)
CF W3 00A0 1P6 S1NB20 111 0 .. .12 7 Va c A1.6 2.4 0.25/0.18 10.0 MPW40-3-U010 166 20 FNH00-20K-A 1.5 (16) 2.5 (14)
Dynamic braking
not available
CFW300A02P6S1NB20 1110 .. .12 7 Va c A2.6 3.9 0.5/0.37 16.0 MPW40-3-U016 166 20 FNH00-20K-A 2.5 (14) 2.5 (14)
CFW300A04P2S1NB20 1110. ..127 Va c A4.2 6.3 1/0.75 20.0 MPW40-3-U020 660 35 FNH00-35K-A 2.5 (14) 4.0 (12)
CFW300A06P0S1NB20 1110 ...12 7 V a c A6.0 9.0 1.5 /1. 32 32.0 MPW40-3-U032 660 40 FNH00-40K-A 4.0 (12) 4.0 (12)
CFW300A01P6S2NB20 1200... 240 Vac A1.6 2.4 0.25/0.18 6.3 MPW40-3-D063 166 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A02P6S2NB20 120 0...24 0 Vac A2.6 3.9 0.5/0.37 10.0 MPW40-3-U010 166 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A04P2S2NB20 120 0...240 Vac A4.2 6.3 1/0.75 16.0 MPW40-3-U016 166 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A06P0S2NB20 12 00... 240 Vac A6.0 9.0 1. 5/ 1.3 2 16. 0 MPW40-3-U016 660 20 FNH00-20K-A 2.5 (14) 4.0 (12)
CFW300A07P3S2NB20 1200 ...240 Va c A7.3 11. 0 2/1.5 20.0 MPW40-3-U020 660 25 FNH00-25K-A 2.5 (14) 4.0 (12)
CFW300A01P6T2NB20 3200... 240 Vac A1.6 2.4 0.25/0.18 2.5 MPW40-3-D025 500 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A02P6T2NB20 320 0...240 Vac A2.6 3.9 0.5/0.37 6.3 MPW40-3-D063 500 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A04P2T2NB20 320 0...240 Vac A4.2 6.3 1/0.75 10.0 MPW40-3-U010 500 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW30 0A06P0T2N B20 3200...240 Va c A6.0 9.0 1.5/1. 32 10 .0 MPW40-3-U010 500 20 FNH00-20K-A 2.5 (14) 4.0 (12)
CFW300A07P3T2NB20 3200...240 Vac A7.3 11. 0 2 /1.5 16.0 MPW40-3-U016 500 20 FNH00-20K-A 2.5 (14) 4.0 (12)
CFW300A01P6D3NB20 1280... 340 Vdc A1. 6 2.4 0.25/0.18 2.5 MPW40-3-D025 - 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A02P6D3NB20 128 0...3 40 Vd c A2.6 3.9 0.5/0.37 6.3 MPW40-3-D063 - 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A04P2D3NB20 128 0...3 40 Vdc A4.2 6.3 1/0.75 10.0 MPW40-3-U010 - 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A06P0D3N B20 1280...34 0 Vdc A6.0 9.0 1.5 /1.32 10. 0 MPW40-3-U010 - 20 FNH00-20K-A 2.5 (14) 4.0 (12)
CFW300A07P3D3NB20 1280...34 0 Vdc A7.3 11. 0 2 /1.5 16.0 MPW40-3-U016 - 20 FNH00-20K-A 2.5 (14) 4.0 (12)
CFW300B10P0B2DB20 1/3 200...240 Vac ou
280...340 Vdc B10.0 15 .0 3/2.2 25.0 MPW40-3-U025 300 35 FNH00-35K-A 2.5 (14) 4.0 (12) 11 39 10 2.5
(14)
CFW300B15P2T2DB20 3200...240 Vca ou
280...340 Vcc B15. 2 22.8 5/3.7 25.0 MPW40-3-U025 685 35 FNH00-35K-A 4.0 (12) 4.0 (12) 11 39 10 2.5
(14)
DANGER!
The inverter must be connected to a protective ground (PE).
Use a minimum wire gauge for ground connection equal to the indicated in Table 3.
Connect the inverter grounding connections to a ground bus bar, to a single ground point
or to a common grounding point (impedance ≤ 10 Ω).
The neuter conductor of the line that feeds the inverter must be solidly grounded; however
this conductor must not be used to ground the inverter.
Do not share the grounding wiring with other equipment that operate with high currents
(e.g.: high voltage motors, welding machines, etc.).
NOTE!
The wire gauges listed in Table 3 are guiding values. Installation conditions and the maximum
permitted voltage drop must be considered for the proper wiring sizing.
10.3 CONTROL CONNECTIONS
DI1DI1
DI2DI2
DI3DI3
DI4DI4
+10 V+10 V
GNDGND
GNDGND
1
1
10
10
11
11
12
12
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
(+) AI1 (-)
(+) AI1 (-)
(0 to 20) mA
(0 to 20) mA
(4 to 20) mA
(4 to 20) mA
(0 to 10) V
(0 to 10) V
Counter
clockwise
Counter
clockwise
Clockwise
Clockwise
AI1
AI1
24 V
External supply
DO1-RL-NCDO1-RL-NC
DO1-RL-NODO1-RL-NO
DO1-RL-CDO1-RL-C
(a) NPN Configuration
(b) PNP Configuration
Connector Description (*)
1DI1 Digital input 1
2DI2 Digital input 2
3DI3 Digital input 3
4DI4 Digital input 4
5GND Reference 0 V
6AI1 Analog in put 1 (Current)
7GND Reference 0 V
8AI1 Analog input 1 (Tension)
9+10 V Reference +10 Vdc for potentiometer
10 DO1-RL-NC Digital outpu t 1 (NC contact of relay 1)
11 DO1-RL-C Digital outpu t 1 (Common point of relay 1)
12 DO1-RL-NO Digita l output 1 (NO contact of relay 1)
(*) For further information, refer to the detailed specification in ta ble 7.
- The CF W300 inverters are supplied with the digital inputs config ured
as active low (NPN). In order to change the co nfiguration, check the
use of paramete r P271 in the programming manual of the CFW300.
- Analog inpu t AI1 is set for input 0 to 10 V; in order to change it, check
parameter P233 of the programming ma nual of the CFW300.
Figure 5: (a) and (b) Signals of C300 control c ard connector
For the correct connection of the control, use:
1. Gauge of the cables: 0.5 mm² (20 AWG) to 1.5 mm² (14 AWG).
2. Ma ximum torque: 0.5 N.m (4.50 lbf.in).
3. Wiring of the connector of the control board with shielded cable and separated from the other wiring
(power, command in 110 V / 220 Vac, etc.).
10 .3.1 Emission and Immunity Levels
Tab l e 4: Emission and immunity levels
EMC Phenomenon Basic Standard Level
Emission:
Mains terminal disturbance voltage
Freque ncy range: 150 kHz to 30 MHz) IEC/EN 61800-3 It depends on the i nverter model on the length of the
cabo motor cable. Refer to Table 6
Electromagnetic radiation disturbance
Freque ncy Range: 30 MHz to 1000 MHz)
Immunity:
Electrostatic disc harge (ESD) IEC 61000-4-2 4 kV for contact discharg e and 8 kV for air discharge
Fast transient-Burst IEC 61000-4-4
2 kV / 5 kHz (coupling capacitor) input cables
1 kV / 5 kHz control cables and remote HMI cables
2 kV / 5 kHz (coupling capacitor) motor cables
Conducted Radio-Frequency
Common Mode IEC 61000-4-6 0.15 to 80 MHz; 10 V; 80 % AM (1 kHz)
Motor, control and remote HMI cables
Surges IEC 61000-4-5
1.2/50 μs, 8/20 μs
1 kV line-to-line coupling
2 kV line-to-ground coupling
Radio-Frequency Electromagnetic
Field IEC 61000-4-3
80 to 1000 MHz
10 V/m
80 % AM (1 kHz)
English
In order to comply with UL508C sta ndard, u se fuses UL ty pe J.
13259186

Definition of Standard IEC/EM 61800 -3: "Adjustable Speed Electrical Power Drives Systems"
Environments::
First Environment: environments that include domestic installations, as well as establishments directly
connected without intermediate transformer to a low-voltage power supply network which supplies
buildings used for domestic purposes.
Second Environment: aincludes all establishments other than those directly connected to a low-voltage
power supply network that supplies buildings used for domestic purposes.
Categories:
Categ ory C1: inver ters with a voltage rating less than 1000 V and intended for use in the First Environment.
Category C2: inverters with a voltage rating less than 1000 V intended for use in the First Environment,
not provided with a plug connector or movable installations. They must be installed and commissioned by
a professional.
Category C3: inver ters with a voltage rating less than 1000 V and intended for use in the Second
Environment only (not designed for use in the First Environment).
NOTE!
A professional is a person or organization familiar with the installation and/or commissioning
of inverters, including their EMC aspects.
10.3.2 Characteristics of the RFI Filter
CFW300 inverters are installed with external filter when it is intended to reduce the disturbance conducted
from the inverter to the power line in the high frequency band (> 150). It is obser ve the maximum levels of
conducted emission of electromagnetic compatibility standards, such as EN 61800-3 and EN 55011.
For further information about the RFI filter model, refer to Table 5.
The figure below demonstrate the connection of the filter to the inverter:
Protective ground
Metal panel (when necessary)
Grounding
rod
External
input
RFI filter
PE
PE PE
W
V
U
Signal and control wiring
Transformer
L1/ L L1 L1/ L
1...12
XC1
PE PE
L2/N L2 L2/N
CFW300 M otor
Power supply
Figure 6: Connection of the RFI filter - general cond itions
Tab l e 5: E xternal RFI filter models for CFW300
WEG Item Name Description
13015 615 CFW300-KFA RFI filter ki t CFW300 frame size A
13015 616 CFW300-KFB RFI filter kit CF W300 frame size B
Table 6: Conducted a nd radiated emission levels, and additional information
Inverter Model Cond ucted Emission – Ma ximum Motor Ca ble Length Radiated Emission
Category C3 Category C2 Category
1CFW300AX XPXS1XX20 ( 1) 27 m (1063 in) 3 m (118 in) C3
2CFW300AX XPXS2X X20 (1) 27 m (1063 in) 20 m (787 in) C3
3CFW300B10P0B2DB20 27 m (1063 in) 27 m (1063 in) C3
- The swi tching frequ ency is 5 kHz.
(1) Where there is an "X", it is assumed as any c orresponding value of Table 2.
10.4 ACCESSORIES
The accessories are hardware resources that can be added in the application with the CFW300.
The accessories are incorporated to the inverters in an easy and quick way by using the concept “Plug and
Play”. The accessor y must be installed or modified with the inverter de-energized. They may be ordered
separately, and are sent in their own package containing the components and manuals with detailed
instructions for their installation, operation and setting.
11 USE OF THE KEYPAD TO OPERATE THE INVERTER
Selects (toggles) display between
the parameter numbe r and its value
position/ content).
Decreases the frequency, parameter
number or parameter value.
Increases the frequency, paramete r
numbe r and parameter value.
Enables/disables the inverter via
acceleration/deceleration ramp
(start/stop, according to P229).
Resets the inverter after a fault
event.
11.1 INDICATIONS OF DISPLAY
Inverter status
Direction of rotation Unit of measurement
(it refe rs to the va lue
of the main display)
Bar graph to monitor the variable
Main display
11. 2 OPERATING MODES OF THE HMI
Monitoring Mode
It is the in itial state of the HMI af ter its successful power-up (withou t
the occurrence of faults, alarms or undervoltage).
Press ke y to go to level 1 of the settin g mode – selec tion of settin g.
Pressing any other key also switches to setting mode.
Monitoring
Setting
level 1
Setting
level 2
Setting Mode
Level 1:
This is the first level of the set ting mode. The parameter nu mber is
shown on the main display.
Use keys and to find the desired parameter.
Press key to go to level 2 of the set ting mo de - cha nge of the
parameter values.
Level 2:
The parameter value is shown on the main display.
Use keys and to set the new val ue in the selected parameter.
Press key to confirm the modification (save the new value).
After confirming the modific ation, the HMI returns to l evel 1 of the
setting mode.
Figure 7: HMI operating modes
12 START-UP PREPARATION
DANGER!
Always disconnect the main power supply before making any connection.
1. Check if the power, grounding and control connections are correct and firm.
2. Remove all the materials left behind from the installation work from inside the inverter or the cabinet.
3. Verif y the motor connections and if its voltage and current are within the inverter rated value.
4. Mechanically uncouple the motor from the load. If the motor cannot be uncoupled, make sure that any
speed direction (for ward or reverse) will not result in personnel injur y and/or equipment damage.
5. Close the inverter or cabinet covers.
6. Measure the power supply and verify if it is within the allowed range.
7. Apply power to the input: close the input disconnecting switch.
8. Check the result of the first time power-up:
The HMI display indicates:
12 .1 BASIC APPLICATION
Seq Display Indication/Action Seq Display Indication/Action
12
Initialization mode.
Press key to enter the first level of the
parameterization mode.
Press keys or to sele ct the parameter P100.
Press key if you need to change the co ntent of
P100 – “Acceleration T ime” or p ress key for the
next parameter.
3 4
If nece ssary, change the content of “P101 -
Deceleration Time".
Use key to select the param eter P133.
If nece ssary, change the co ntent of “P133 - Minimu m
Sp e e d ”.
Press key for the next parameter.
5 6
If nece ssary, chan ge the content of “ P134 - Maxi mum
Sp e ed".
Press key for the next parameter.
If nece ssary, change the co ntent of “P135 - Output
Maximum Current".
Press key to select parameter P0 02.
7 8
Press key to view the parameter co ntent. Press key that the motor will accelerate up to
3.0 Hz (factory default setting of P133 - Minimum
Freq uency).
Press and hold it until it reaches 60.0 Hz.
910
Press key . The motor will decelerate to a stop. When the motor stops, the disp lay wil l indicate
“r e ady”.
12. 2 TYPE OF CONTROL V/f (P202 = 0)
Seq Display Indication/Action Seq Display Indication/Action
12
Initialization mode.
Press key to enter the first level of the
parameterization mode.
Press keys or to sele ct parameter P202.
34
Press key if you need to change the co ntent of
“P202 – Type of Co ntrol” for P202 = 0 ( V/f).
Press key to select parameter P401.
If nece ssary, change the content of parameter “P401
– Motor Rate d Current” according to the namep late.
Press key for the next parameter.
56
Se necessário altere o conteúdo de "P402 - Rotação
Nominal Motor".
Press key for the next parameter.
If nece ssary, change the co ntent of “P403 - Motor
Rated Frequency".
13 TECHNICAL SPECIFICATIONS
PO WER DATA
Power Supply:
Tolerance: -15 % to +10 %.
Frequência: 50/60 Hz (48 Hz a 62 Hz).
Phase imbalance: ≤ 3 % of the rated phase-to-phase input voltage.
Over voltage according to Category III (EM 61010/UL 508C).
Transient voltages according to Category III.
Maximum of 10 connections per hour (1 every 6 minutes).
Typical efficiency: ≥ 97 %.
Classification of chemically active substances: level 3C2.
Mechanical condition rating (vibration): level 3M4.
Audible noise level: < 60dB.
14 ELECTRONICS/GENERAL DATA
Tab l e 7: Electronics/general data
Control Method Types of control:
- V/f (Scalar)
- VVW: voltage vector control.
PWM SVM (Space Vector Modulation)
Output frequency 0 to 400 Hz, resolu tion of 0.1 Hz
Performance V/F control Speed re gulation: 1 % of the rated speed (with slip compensation)
Speed variation range: 1:20
Vector control
(VVW)
Regulação de veloc idade: 1 % da velocidad e nominal
Faixa de variação de velocidade: 1:30
Inputs Analog 1 insulated input. Levels: (0 to 10) V or (0 a 20) mA or (4 to 20) m A
Linearit y error ≤ 0.25 %
Imped ance: 100 k Ω for vol tage input, 50 0 Ω for current input
Programmable functions
Maximum voltage permitted in the input: 30 Vdc
Inputs Digital 4 isolated inputs
Programmable functions:
- active high (PNP): maximum low level of 10 Vdc / minimum high level of 20 Vdc
- active low (NPN): maximum low level of 5 Vdc / mi nimum high level of 10 Vdc
Maximum input vol tage of 30 Vdc
Input current: 11 mA
Maximum input current: 20 m A
Outputs Relay 1 relay with NO/NC c ontact
Maximum voltage: 250 Vac
Maximum current: 0.5 A
Programmable functions
Power supply 10 Vdc power supply. Maximum capacity: 50 mA
Safety Protection Overcurrent/phase-phase short circuit in the output
Under/overvoltage
Motor overload
Over temperature in the power module (IGBTs)
Fault / ex ternal alarm
Programming error
Integral keypad
(HMI))
Standard keypad 4 keys: Start/Stop, Up arrow, Down arrow and Programming
LCD Display
View/edition of all parameters
Indication accuracy:
- current: 5 % of the rated current
- speed resolution: 0.1 Hz
Enclosure IP20 Frame s sizes A and B
15 CONSIDERED STANDARDS
Tab l e 8: Considered standards
Safety
standards
UL 508C - power conversion equipme nt
UL 840 - insulation coordination including clearances and creepage distances for electrical equipment
EN 61800-5-1 - safety requirements electrical, thermal and energ y
EN 50178 - electron ic equipment for use in power installations
EN 60204-1 - safety of machine ry. Electrical equipment of machines. Part 1: general re quirements
Note: the final assembler of the machine is resp onsible for installing a safety stop devi ce and a supply
disconnecting device
EN 60146 (IEC 146) - semiconductor converters
EN 61800-2 - adjustable speed electrical power dri ve systems - Par t 2: general requirements - rating
specifications for low voltage adjustable frequency AC power drive systems
Mechanical
standards
EN 60529 - degree s of protection provided by enclosures (IP code)
UL 50 - enclosures for electrical equipment
IEC 60721-3-3 - classification of environmental conditions
Electromagnetic
compatibility
(EMC)
standards (*)
EN 61800-3 - adjustable speed e lectrical p ower drive systems - part 3: EMC product stand ard includi ng
specific test methods
EN 55011 - limits and methods of measurement of radio disturbance characteristics of industrial,
scientific and medical (ISM) radio-frequency equipment
CISPR 11 - industrial, scientific a nd medical (ISM) radio-frequency eq uipment - electromagnetic
disturbanc e characteristic s - limits and methods of measu rement
EN 61000-4-2 - electromagnetic compatibility (EMC) - part 4: testing and measurement techniques -
section 2: electrostatic discharge immunity test
EN 61000-4-3 - electromagnetic compatibility (EMC) - part 4: testing and measurement techniques -
section 3: radiated, radio-frequency, electromagnetic field immunity test
EN 61000-4-4 - electromagnetic compatibility (EMC) - part 4: testing and measurement techniques -
section 4: electrical fast transient/burst immunity test.
EN 61000-4-5 - electromagnetic compatibility (EMC) - part 4: testing and measurement techniques -
section 5: surge immunity test.
EN 61000-4-6 - electromagnetic compatibility (EMC) - part 4: testing and measurement techniques -
section 6: immunity to conducted disturbances, induced by radio-frequency fields.
(*) Compliance with standards upon installation of RFI filter. For further details refer to consulte www.weg.net.
16 MAIN PAREMETERS
The table below contains the mains parameters of the CFW300.
NOTE!
ro = read only parameter.
V/f = parameter available in V/f mode.
cfg = configuration parameter, value can only be changed with the motor stopped.
Param. Description Adjustable Range Factory Setting Prop.
P000 Access to Parameters 0 to 99 99 1
P001 Speed Reference 0 to 9999 ro
P002 Output Speed (Motor) 0 to 9999 ro
P003 Motor Current 0.0 to 40.0 A ro
P004 DC Lin k Voltage (Ud) 0 to 524 V ro
P005 Output Frequ ency (Motor) 0.0 to 400.0 Hz ro
P006 Inverter Status 0 = Ready
1 = Run
2 = Undervoltage
3 = Fault
4 = Self-Tuning
5 = Configuration
ro
P007 Output Voltage 0 to 240 V ro
P0 11 Active Current -40.0 to 40.0 A ro
P012 DI8 to DI1 Status 0 to FF (hexa)
Bit 0 = DI1
Bit 1 = DI2
Bit 2 = DI3
Bit 3 = DI4
Bit 4 = DI5
Bit 5 = DI6
Bit 6 = DI7
Bit 7 = DI8
ro
P022 FI Value in Hz 1 to 3 000 Hz ro
P023 Main SW Ver sion 0.00 to 99.99 ro
P030 Module Temperature 0.0 to 200.0 ºC ro
P037 Motor O verload Ixt 0.0 to 100.0 % ro
P047 CONFIG Status 0 to 999 ro
P048 Present Alarm 0 to 999 ro
P049 Present Fault 0 to 999 ro
P050 Last Fault 0 to 999 ro
P100 Acceleration Time 0.1 to 999.9 s 5.0 s
P101 Deceleration Time 0.1 to 999.9 s 10.0 s
P120 Speed Ref. Backup 0 = Inactive
1 = Active
2 = Backu p by P121
1
P121 Referenc e via HMI 0.0 to 400.0 Hz 3.0 Hz
P124 Multispeed Ref. 1 -400.0 to 40 0.0 Hz 3.0 Hz
P125 Mu ltisp eed Ref. 2 - 400.0 to 40 0.0 Hz 10.0 (5.0) Hz
P126 Multispeed Re f. 3 - 400.0 to 40 0.0 Hz 20.0 (10.0) Hz
P127 Multispeed Ref. 4 -400.0 to 400.0 Hz 30.0 (20.0) Hz
P128 Multispeed Ref. 5 - 400.0 to 40 0.0 Hz 40.0 (30.0) Hz
P129 Multispeed Ref. 6 -400.0 to 400.0 Hz 50.0 (40.0) Hz
P130 Mu ltisp eed Ref. 7 - 400.0 to 40 0.0 Hz 60.0 (50.0) Hz
P131 Multispeed Ref. 8 -400.0 to 40 0.0 Hz 66.0 (55.0) Hz
P133 Minimum Frequency 0.0 to 400.0 Hz 3.0 Hz
P134 Maximum Frequency 0.0 to 400.0 Hz 66.0 (55.0) Hz
P135 Maximum Output Current 0.0 to 40.0 A 1.5 x Inom
P136 Manual Torque Boost 0.0 to 30.0 % 0.0 % V/f
P137 Automatic Torque Boost 0.0 to 30.0 % 0.0 % V/f
P138 Slip Compensation -10.0 to 10.0 % 0.0 % V/f
P139 Output Current Filter 0.000 to 9.999 s 0.005 s
P142 Maximum Output Voltage 0.0 to 100.0 % 100.0 % cfg , V/f
P143 Intermediate Output Voltage 0.0 to 100.0 % 50.0 % cfg , V/f
P145 Field Weakening Start
Frequency
0.0 to 400.0 Hz 60.0 (50.0) Hz cfg, V/f
P146 I nterme diate Frequency 0.0 to 400.0 Hz 30.0 (25.0) Hz cfg, V/ f
P156 Overload Current 0.1 to 2.0 x Inom 1.2 x Inom
P202 Type of Control 0 = V/f
1 = V/f Quadratic
2 to 4 = Not Used
5 = V V W
0cfg
P204 Load/Save Parameters 0 to 4 = Not Used
5 = Load 60 Hz
6 = Load 50 Hz
7 = Load Use r 1
8 = Not Used
9 = Save User 1
10 = Not Used
11 = Load Default S oftPLC
12 to 13 = Reserved
0cfg
Param. Description Adjustable Range Factory Setting Prop.
P220 LOC/REM Selection Source 0 = A lways Lo cal
1 = Always Remote
2 to 3 = Not Used
4 = DIx
5 = Serial/US B (LOC)
6 = Serial/US B (REM)
7 to 8 = Not Used
9 = CO/DN/DP (LOC)
10 = CO/DN/DP (REM)
11 = SoftPLC
0cfg
P221 LOC Reference Sel 0 = HMI Keys
1 = AI1
2 = AI2
3 = Not Used
4 = FI
5 = AI1 + AI2 > 0
6 = AI1 + AI2
7 = E.P.
8 = Multispeed
9 = Serial/USB
10 = Not Used
11 = CO/DN/DP
12 = SoftPLC
13 = Not Used
14 = AI1 > 0
15 = AI2 > 0
16 = Not Used
17 = FI > 0
0 cfg
P222 REM Reference Sel. See Options in P221 3 cfg
P223 LOC Rotation Sel. 0 = Forward
1 = Reverse
2 to 3 = Not Used
4 = DIx
5 = Serial/US B (FWD)
6 = Serial/US B (REV)
7 to 8 = Not Used
9 = CO/DN/ DP (FWD)
10 = CO/DN/DP (REV )
11 = Not Used
12 = SoftPLC
0cfg
P263 DI1 Input Function 0 = Not Used
1 = Run/Stop
2 = General Enable
3 = Not Used
4 = Forwa rd
5 = Reverse
6 = Star t
7 = Stop
8 = Direction of Rotation
9 = LOC/REM
10 = JOG
11 = Increase E.P.
12 = Decelerate E.P.
13 = Multispeed
14 = 2nd Ramp
15 to 17 = Not Used
18 = No Ext. Alarm
19 = No Ext. Fault
20 = Reset
21 to 23 = Not Used
24 = Disab. Flying Start
25 = Regul. DC Link
26 = Lock Pro g.
27 to 31 = Not Used
32 = 2nd Ramp Multispeed
33 = 2nd Ramp E.P. Ac.
34 = 2nd Ramp E.P. De.
35 = 2nd Ramp FWD Run
36 = 2nd Ramp Rev Run
37 = Turn ON / Ac. E.P.
38 = De. E.P. / Turn OFF
39 = Stop
40 = Safet y Switc h
41 = Function 1 Application
42 = Function 2 Application
43 = Function 3 Application
44 = Function 4 Application
45 = Function 5 Application
46 = Function 6 Application
47 = Function 7 Application
48 = Function 8 Application
1cfg
P264 DI2 Input Function See O ptions in P263 8 cfg
P265 DI3 Input Function Se e Optio ns in P263 0 cfg
P266 DI4 Input Function See Options in P263 0 cfg
P267 DI5 Input Function See Optio ns in P263 0 cfg
P268 DI6 Input Function See Options in P263 0 cfg
P269 DI7 Input Function See O ptions in P263 0 cfg
P270 DI8 Input Function See Options in P26 3 0 cfg
P295 Inv. Rated Cu rrent 1.6 to 15.2 A According inverter
model
ro
P296 Line Rated Voltage 0 = Reser ved
1 = 110 / 127 Vac
2 = 200 / 240 Vac or
310 Vdc
According inverter
model
ro
P297 Switching Frequency 2.5 to 15.0 kHz 5.0 kHz cfg
P401 Motor R ated Cur rent 0.0 to 40.0 A 1.0 x Inom cfg
P402 Motor Rated Sp eed 0 to 9999 r pm 1720 (1310) rpm cfg
P403 Moto r Rated Frequen cy 0 to 40 0 Hz 60 (50) Hz cfg
17 FAULTS AND ALARMS
Most common faults and alarms
Fault / A lar m Description Possible Causes
A046
Motor Overload
Motor overload alarm Settings of P156 is too low for the used motor
Overl oad on the motor shaft
A050
Power Module
Overtemperature
Overtemperature alarm from the power
module temperature sensor (NTC)
High temperature at IG BTs: P030 > 90 °C (> 194 °F ) (Frame size A)
and P03 0 > 116 °C (> 240.8 °F) (Fr ame size B)
High am bient temper ature around th e inver ter (> 50 °C (> 122 °F))
and high output current
Blocke d or defe ctive fan
Heatsink is too dirty, preventin g the air f low
A090
External Alarm
Exte rnal alarm via DIx (option “no
external ala rm” in P26 3 to P270)
Wirin g on DI1 to DI8 in puts are open or have poor contact
A700
Remote HMI
Communication
No communication with remote HMI,
but here is freq uency comma nd or
reference for this source
Check i f the com munication interface wi th the HMI is properly
confi gured i n parameter P312
HMI cable disconnected
F021
Undervoltage on the
DC Link
Undervoltage fault on the intermediate
circuit
Wrong vol tage supply ; check if the da ta on the inver ter label com ply
with the p ower supply an d parameter P29 6
Suppl y voltage too low, producing voltag e on the DC l ink below
the minimum val ue (in P004):
Ud < 250 Vdc in 110 / 127 Vac (P296 = 1) or Ud < 200 Vdc in
200 / 240 Vac (P296 = 2)
Phase fault in th e input
Fault in the pre-charg e circuit
F022
Overvoltage on the DC
Link
Overvoltage fault on the intermediate
circuit
Wrong vol tage supply ; check if the da ta on the inver ter label com ply
with the p ower supply an d parameter P29 6
Supply voltage is too high, producin g voltage on the DC link ab ove
the maximum value (in P004):
Ud > 460 Vdc in 110 / 127 Vac (P296 = 1) or Ud > 410 Vdc in
200 / 240 Vac (P296 = 2).
Load ine rtia is too high or deceleration ramp is too fast
P151 setting is too high
F031
Fault in Communication
with IOs Expansion
Accessory
Main control cannot establish the
communication link with the IOs
expansion accessory
Accessory damaged
Poor connection of the accessory
Proble m in the id entif icati on of the accessory; refer to P027
F032
Fault in Communication
with IOs Communication
Accessory
Main control cannot establish
the communication link with the
communication acccessory
Accessory damaged
Poor connection of the accessory
Proble m in the id entif icati on of the accessory; refer to P028
F051
IG B Ts
Overtemperatures
Overtemperature fault measured
on the temperature sensor of the
power pack
High te mperature at IGBTs: P030 > 100 °C (> 212 °F) (Fra me size A)
e P030 > 126 °C (> 258.8 °F ) (Fram e size B)
High am bient temper ature around the inver ter (>50 °C (>122 °F))
and high output current
Blocke d or defe ctive fan
Heatsink is too dirty, preventin g the air f low
F070
Overcurrent/
Shortcircuit
Overcurrent or short-circuit on the
output, DC link or braking resistor
Short-circuit between two motor phases
IGBTs module in short-circuit or damaged
Star t with too s hort accelerati on ramp
Star t with motor spin ning wi thout the Flying Start function
F072
Motor Overload
Motor overload fault (60 s i n 1.5 x Inom) P156 setting is too low in rela tion to the motor ope rating curre nt
Overl oad on the motor shaft
F080
CPU Fault (Watchdog)
Fault related to the supervision
algor ithm of th e inver ter main CPU
Electric noise
Inverter firmware fault
F081
End of Use r’s Memor y
Fault of end of memory to save user’s
parameter table
Attempt to save (P204 = 9) more than 32 parameter s (with va lues
different from the factory default) on the User parameter table
F082
Fault in the Copy
Function (MMF)
Fault in the copy of parameters Attempt to copy the parame ters from the flash memory m odule to
the inverter with dif ferent software ve rsions
F084
Auto-diagnosis Fault
Fault related to the automatic
identification algorithm of the inverter
hardware
Poor contact in the connection between the main control anthe
power pack
Hardware not compatible with the firmware version
Defect on the inte rnal c ircui ts of the inverter
F091
External Fault
Exte rnal fault via DIx (“no extern al
fault ” in P263 to P270)
Wirin g on DI1 to DI8 in puts are open or have poor contact
F701
Remote HMI
Communication Fault
No communication with the remote
HMI; however, there is command or
frequ ency reference for thi s sourc e
Check that the HMI communication interface is properly configured
in parameter P312
HMI cable disconnected
NOTE!
For further information, refer www.weg.net.
Document: 10003587596 / 00
Other manuals for CFW300
2
Table of contents
Other WEG Inverter manuals

WEG
WEG CFW501 V1.8X Owner's manual

WEG
WEG CFW100 series Quick guide

WEG
WEG CFW-11 Series User manual

WEG
WEG CFW-09 User manual

WEG
WEG CFW300 User manual

WEG
WEG CFW-09 User manual

WEG
WEG MVW3000 Series Owner's manual

WEG
WEG CFW08 Vector inverter User manual

WEG
WEG CFW-11 Series User manual

WEG
WEG CFW-11 Series User manual

WEG
WEG bacnet CFW701 Operating instructions

WEG
WEG DeviceNet CFW500 Operating instructions

WEG
WEG CFW100 series User manual

WEG
WEG CFW-11W G2 RB Series User manual

WEG
WEG Easy Drive CFW10 User manual

WEG
WEG CVW300G2 User manual

WEG
WEG CFW-11 Series Instructions for use

WEG
WEG AG10 Series User manual

WEG
WEG CFW100 series User manual

WEG
WEG bacnet CFW701 User manual