Panel C
Exhaust requirements
POWER SUPPLY CORD
OR DIRECT WIRE
Where local codes DO NOT permit
connecting the cabinet-ground
conductor to the neutral (white)
wire:
Where local codes permit
connecting cabinet-ground
conductor to the neutral wire of the
power suppl cable:
Where local codes permit
connecting cabinet-ground
conductor to the neutral wire:
Three-wire connection...
B.
POWER SUPPLY CORD
Figure 8
center silver-colored
terminal block screw and
neutral white wire
ground wire (green
with yellow stripes)
1. Disconnect the power suppl .
2. Remove terminal block cover.
3. Install copper three-wire power supply
cord throu h strain relief.
4. Remove the round wire ( reen with
yellow stripes) from under center, silver-
colored terminal block screw and
connect to external round connector
(see Fi ure 8).
5. Connect the neutral wire (white or
center) of the power supply cord to the
center, silver-colored terminal screw of
the terminal block. Connect the other
wires to the outer terminals. Ti hten
screws firmly.
6. Ti hten strain relief screws.
7. Replace the terminal block cover.
external ground connector
DIRECT WIRE
1. Disconnect the power suppl .
2. Remove terminal block cover.
3. Strip 3-1/2 inches of outer coverin from
end of cable. If usin three-wire cable
with I wire, cut the bare wire even with
outer coverin . Strip 1 inch of insulation
from the end of each insulated wire (see
Fi ure 9).
Important: Observe all governing codes
and ordinances.
It is recommended that ou exhaust
our dr er to the outside for best
performance. Moisture and lint indoors
may cause:
• Lint to ather around the dryer where
it can be fuel for a fire.
• Moisture dama e to woodwork,
furniture, paint, wallpaper, carpet,
etc.
• Housecleanin problems and health
problems.
If the washer/dr er is installed in a
confined area such as a bedroom,
bathroom or closet, it must be
exhausted to the outside and provision
must be made for enou h air for
ventilation. Check overnin codes and
ordinances. Also refer to the “Recessed
and closet installation instructions” on
Panel G.
Dura SafeTM vent products are
recommended and are available from
our dealer. See Panel G.
Four-inch diameter vent is required.
Use a heav metal vent. Do not use plastic or
metal foil vent.
• Do Not use non-metal flexible vent, or
exhaust hoods with ma netic latches.
• Do Not exhaust dryer into a chimney,
furnace, cold air vent, attic or crawl space,
or any other vent used for ventin .
• Do Not install flexible vent in enclosed walls,
ceilin s or floors.
Rigid metal vent is recommended to prevent
crushin and kinkin .
Flexible metal vent must be fully extended
and supported when the dryer is in its final
position.
Remove excess flexible vent to avoid
sa in and kinkin that may result in
reduced air flow.
An exhaust hood should cap the exhaust
vent to prevent rodents and insects from
enterin the home.
Exhaust outlet hood must be at least 12
inches from the round or
any object that may be in
the path of the exhaust
(such as flowers, rocks or
bushes, etc.).
If using an existing exhaust
s stem, clean lint from entire
length of s stem and make sure exhaust
hood is not plugged with lint.
Replace any plastic or metal foil vent with
ri id metal or flexible metal vent.
Use clamps to seal all joints. Do not use duct
tape, screws or other fastenin devices that
extend into the interior of the vent to secure
vent.
Service check: Back pressure in any exhaust
system used must not exceed 0.6 inches in
water column measured with an incline
manometer at the point that exhaust vent
connects to dryer.
Direct wire preparation
Figure 9
10-gauge, 3-wire or,
10-gauge, 3-wire with
ground wire (Romex)
3/4" U.L.-listed
strain relief
Bare wire cut short. Wire is not
used. Dryer is grounded through
direct wire cable.
to disconnect
box
red
white
black
NEUTRAL
1"
3-1/2"
wires stripped
of insulation
Figure 10
Shape the end of each
wire into a “U” shaped
hook (see Fi ure 10).
u-shaped
hook
WARNING
Fire Hazard
Use a heavy metal vent.
Do not use a plastic vent.
Do not use a metal foil vent.
Failure to do so can result in death or
fire.
Three-wire connection...
ground wire (green with
yellow stripes)
center silver-colored
terminal block screw and
neutral white wire
external ground connector
Figure 11
4. Install copper, three-wire power supply
cable throu h strain relief.
5. Remove the round wire ( reen with
yellow stripes) from under center, silver-
colored terminal block screw and
connect to external round connector
(see Fi ure 11).
6. Slide the hook end of the neutral (white
or center) wire from the three-wire
power supply cable under the center,
silver-colored terminal screw of the
terminal block. Squeeze the hook end of
the wire to ether. Ti hten screw.
7. Connect the other wires to the
outer terminals usin the same method.
Ti hten screws firmly (see Fi ure 11).
8. Ti hten strain relief screws.
9. Replace the terminal block cover.
WARNING
Fire Hazard
Use a new UL approved 30 ampere
power supply cord.
Use a UL approved strain relief.
Disconnect power before making
electrical connections.
Connect neutral wire (white or center
wire) to center terminal (silver).
Ground wire (green or bare wire) must
be connected to green ground
connector.
Connect remaining 2 supply wires to
remaining 2 terminals (gold).
Securely tighten all electrical
connections.
Failure to do so can result in death,
fire, or electrical shock.
WARNING
Fire Hazard
Use 10 gauge solid copper wire.
Use a UL approved strain relief.
Disconnect power before making
electrical connections.
Connect neutral wire (white or center
wire) to center terminal (silver).
Ground wire (green or bare wire) must
be connected to green ground
connector.
Connect remaining 2 supply wires to
remaining 2 terminals (gold).
Securely tighten all electrical
connections.
Failure to do so can result in death,
fire, or electrical shock.
12" min.
Connect separate copper ground wire
from external ground connector
to approved ground.
separate copper
ground wire
external
ground
connector
ground wire (green
with yellow stripes)
Figure 12
center silver-colored
terminal block screw and
neutral white wire
1. Disconnect the power suppl .
2. Remove terminal block cover.
3. Install solid copper, power supply cord or
cable throu h strain relief.
4. Remove the round wire ( reen with
yellow stripes) from the external round
connector.
5. Connect the round wire ( reen with
yellow stripes) and the neutral (white)
wire of the power supply cord or direct
wire cable to the center, silver-colored
terminal screw of the terminal block.
Connect the other wires to the outer
terminals. Ti hten screws (see Fi ure 12).
6. Connect a separate copper round wire
(No.-10 minimum) from the external
round screw to an adequate round.
7. Ti hten strain relief screws.
8. Replace the terminal block cover.