Doc. # BA001252 – 06/2021 (Rev. B) wienet IP SWITCH UMS 8-C / UMS 8G-C 1 DE / EN
HINWEIS
Personal, welches dieses Gerät installiert, programmiert, in Betrieb nimmt oder wartet,
muss diese Anleitung gelesen und verstanden haben.
WARNUNG
•Das Personal muss gründlich mit allen Warnungen, Hinweisen und Maßnahmen gemäß
dieser Montageanleitung vertraut sein.
•Ggf. erforderliche Schutzmaßnahmen und Schutzeinrichtungen müssen den gültigen
Vorschriften entsprechen.
•Beschädigte Produkte dürfen weder installiert noch in Betrieb genommen werden.
•Das Gerät darf nicht geöffnet werden.
•Führen Sie keine Fremdobjekte in das Gerät ein!
•Halten Sie das Gerät von Wasser und Feuer fern!
Weitere Beschreibungen finden Sie im Internet unter www.wieland-electric.com
1Funktionsbeschreibung
Das Gerät ist ein Unmanaged Indust ri al Ethernet Switch mit acht Ethernet-Ports (UMS 8G-C
mit acht Gigabit-Ports) für industrielle Anwendungen und ka nn in i ndus tr ieller Umgebung
eingesetzt werden.
HINWEIS
Verwenden Sie das Gerät nur gemäß seiner Bestimmung. Beachten Sie dazu insbesondere
die Angaben im Abschnitt "Technischen Daten".
2Funktionselemente und Anzeigen
Pinbelegungen und Verbindungen
RJ45
10 / 100 BASE-T (X)
Pin
1
2
3
4
5
6
7
8
Signal
Tx+
Tx-
Rx+
Rx-
1000 BASE-T
Pin
1
2
3
4
5
6
7
8
Signal
BI_DA+
BI_DA-
BI_DB+
BI_DC+
BI_DC-
BI_DB-
BI_DD+
BI_DD-
Versorgungs-/ Signalanschlüsse
Pin
V2+
V2-
11
14
V1+
V1-
F.G.
Signal
12–48 V DC
0 V
Relais = EIN, wenn P1
und P2 = EIN
12–48 V DC
0V
⏚
LEDs
Name
LED
Status
Beschreibung
P1/P2 grün

Stromversorgung P1,P2 nicht angeschlossen

Stromversorgung P1,P2 istaktiv
P-Fail rot

Kein Fehler oder Gerät AUS

Fehler (fehlende Spannung P1 oder P2)
RJ45
grün

Nicht an Netzwerk angeschlossen
•
Datenübertragung

Netzwerk angeschlossen
gelb

Nicht an Netzwerk angeschlossen oder an Netzwerk mit
10 Mbps angeschlossen
•
Datenübertragung

Netzwerk angeschlossen (100/1000 Mbps)
= aus; = an;•= blinkt
NOTE
Personnel which installs, programs, operates or maintains this device must have read and
understood these instructions.
WARNING
•The personnel must be thoroughly familiar with all warnings, notes and procedures de-
scribed in these installation instructions.
•
Where necessary, safety precautions and safety devices must comply with the applicable
regulations.
•Damaged products must neither be installed nor put into operation.
•The unit must not be opened.
•Do not insert any objects into theunit!
•Keep the unit away from fire and water!
Additional information canbe found at www.wie land-electric.com
1Function description
The device is an unmanaged industrial Ethernet switch with eight Ethernet ports (UMS 8G-C
wit height Gigabit ports) for industrial applications and can be used in industrial environ-
ment.
NOTE
Use the device only as intended. Especially observe the specifications in the section "Tech-
nical data".
2Functional elements and indicators
Pin assignments and connections
RJ45
10 / 100 BASE-T (X)
Pin
1
2
3
4
5
6
7
8
Signal
Tx+
Tx-
Rx+
Rx-
1000 BASE-T
Pin
1
2
3
4
5
6
7
8
Signal
B I _ DA+
BI_DA-
BI_DB+
BI_DC+
BI_DC-
BI_DB-
BI_DD+
BI_DD-
Power connectors
Pin
V2+
V2-
11
14
V1+
V1-
F.G.
Signal
12–48 V DC
0V
Relay contact = ON,
when P1 and P2 = ON
12–48 V DC 0 V
⏚
LEDs
Name
LED
Status
Description
P1/P2 green

Power input P1, P2 is inactive

Power input P1, P2 is active
P-Fail red

No error or device is OFF

Error (no voltageP1 or P2)
RJ45
green

Not connected to network
•
Data is transmitting

Connected to network
yellow

Connected to networkat 10 Mbps or not linked
•
Data is transmitting

Connected to network (at 100/1000Mbps)
= off; = on;•= flashes
1
2
3
4
5
Montageanleitung (Original)/ Installation instruction (translation from original)
wienetIPSWITCH UMS 8-C 83.040.1281.0
UMS 8G-C (8 Gigabit-Ports) 83.040.1283.0
Unmanaged Industrial Ethernet Switch mit/with 8 Ethernet-Ports
Wieland Electric GmbH
Brennerstraße 10
– 14
96052 Bamberg
Phone
+49 9519324-0
Fax
+49 9519324-198
info@wieland
-electric.com
www.wieland-electric.com
Doc. # BA001252 – 06/2021 (Rev. B) wienet IP SWITCH UMS 8-C / UMS 8G-C 2 DE / EN
3Montage
Anbringen auf Trägerschiene (Bild 4)
1. Kippen Sie das Gerät etwas nach hinten.
2. Haken Sie das Gerät oben auf der Schiene ein.
3. Drücken Sie das Gerät nach unten und gegen die Schiene, bis es einrastet.
4. Prüfen Sie, ob das Gerät fest auf der Tragschiene sitzt.
Anschluss an Spannungsversorgung
•Geeignete Spannungsversorgungan wienet Switch anschließen.
•Anschluss zweier separater Stromquellen für eine redundante Spannungsversorgung (P1,
P2) möglich.
Anschluss von Netzwerkgeräten
Schließen Sie Ihre Netzwerkgeräte über Standard-UTP/STP-Kabel mit RJ45 Steckverbindern
an den w ienet Switch an.
4Demontage (Bild5)
WARNUNG
Schalten Sie die Spannungsversorgung aus und trennen Sie das Gerät vom Netz.
Drücken Sie das Gerät nach unten, und kippen Sie es nach oben.
5Technische Daten
WARNUNG
•Verwenden Sie nur Kabel mit mindestens AWG 20 am Stromanschluss, die auf eine Be-
triebstemperatur bis 85 °C ausgelegt sind.
•Das Gerät muss in einem Gehäuse vom Typ 1 installiert werden.
Switch-Eige nschaf ten
UMS 8-C
UMS 8G-C
Ethernet
Anschlüsse (RJ45)
8× 10/100 Base-T(X)
8× 10/100/1000Base-T(X)
Übertragungsrate (RJ45)
10/100 Mbps
10/100/1000Mbps
Übertragungsreichweite
bis zu 100 m (4-wire Cat.5e, Cat.6 RJ45 Kabel)
Übertragungsstandard
IEEE 802.3, IEEE 802.3u, IEEE802.3x
zusätzlich UMS 8G-C: IEEE802.3ab (1000BaseT)
Jumbo Frame
–
9 KBytes
Auto MDI/MDI-X
ja
Spannungsversorgung
Redundante Einspeisung
ja (P1, P2)
Eingangsspannungsbereich
12 – 48 V
Eingangsstrom
max. 1,5 A
Leistungsaufnahme
4,7 W
5,8 W
Fehlerausgang
1 Relais-Ausgang, 24 V DC, 1 A
Verpolschutz
ja
Überlaststrom
ja
Allgemeine Daten
Betriebsumgebungstemperatur
-10 …+60 °C
Lagertemperatur
-40 …+85 °C
Relative Luftfeuchte
10 …95% RH, keine Kondensation
Montageauf
DIN Hutschiene35 mm(EN60715)
Schutzart
IP30
MTBF
820.306h
1.988.083h
Gewicht
460 g
450 g
Gehäusematerial
Metall
Anschlusstechnik
Anschlusstechnik
Schraub-Klemme, 6-pol.
Anschlussvermögen
0,25 …2,5 mm²(AWG26– AWG 12)
Abisolierlänge
8 – 9 mm
Modulerdung
durch ⏚ Erdungsschraube und Aufrasten auf geerdete
Hutschiene (Achtung: niederimpedant durchführen)
Schock und Vibration
Schock, Vibration, Freier Fall
IEC60068-2-27 / IEC 60068-2-6 / IEC 60068-2-32
Normen und Zulassungen
EMV
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5 ,
EN 61000-4-6, EN 61000-4-8
Sicherheit
UL62368
FCC
FCC, Class A
Zulassung
CE
3Installation
Mounting on support rail (see fig. 4)
1. Tilt the unit slightly backwards.
2. Fit theunit over top hat rail.
3. Push downwards and against the rail forlocking.
4. Check that theunit is locked into position.
Connecting to power
•Prepare a suitable power source and connect to the wi enet switch.
•You can connect two independent DC input sources for power auto-backup if necess ary
(P1, P2).
Connecting to network device by Ethernet
Connect your device by standard UTP/STP cable with RJ45 connectors to the wienet switch.
4Removal from DIN rail (see fig. 5)
WARNING
Switch mains power off and disconnect the device from the supply network.
Push the device down, and tilt upwards.
5Technical data
WARNING
•It is recommended to use at least 20 AWG cables. The cables need to be resistant to at
least 85 °C on the power connector.
•The device needs to be installed inside a type 1 housing.
Switch properties
UMS 8-C
UMS 8G-C
Ethernet
Connectors (RJ45)
8× 10/100 Base-T(X)
8× 10/100/1000Base-T(X)
Transfer rate (RJ45)
10/100 Mbps
10/100/1000Mbps
Transfer range
up to 100 m (4-wire Cat.5e, Cat.6 RJ45 cable)
Ethernet standard
IEEE 802.3, IEEE 802.3u, IEEE802.3x
additional UMS 8G-C: IEEE 802.3ab (1000BaseT)
Jumbo Frame
–
9 KBytes
Auto MDI/MDI-X
yes
Power supply
Redundant power supply
yes (P1, P2)
Dual input voltage
12 – 48 V
Input current
max. 1.5 A
Power consumption
4.7 W
5.8 W
Fault output
1 relay output, 24 VDC, 1 A
Reverse polarity protection
yes
Overload current
yes
General data
Ambient operating temperature
-10 …+60 °C
Storage temperature
-40 …+85 °C
Ambient relativehumidity
10 …95% RH, non-condensing
Mounting on
DIN rail 35 mm (EN 60715)
Degree of protection
IP30
MTBF
820,306h
1,988,083h
Weight
460 g
450 g
Housing material
metal
Connectors
Wiring
screw terminal, 6 pin
Rated conductor size
0.25 …2.5 mm²(AWG26– AWG 12)
Conductor strip length
8 – 9 mm
Module earth
by ⏚ screw and by snapping onto earthed DIN rail
(Caution: must be with low impedance)
Shock and vibration
Shock, vibration, free fall
IEC60068-2-27 / IEC 60068-2-6 / IEC 60068-2-32
Norms and approvals
EMC
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5 ,
EN 61000-4-6, EN 61000-4-8
Safety
UL62368
FCC
FCC, Class A
Approval
CE
WARNUNG
WARNING
AVERTISSEMENT
•Dieses Produkt ist für die Versorgung durch eine UL-zertifi-
zierteStromversorgung oder eine Gleichstromquelle vor-
gesehen, die für den Einsatz bei mindestens 75 °C geeignet
ist, Der Ausgang muss SELV oder ES1 entsprechen und für
12–48 V DC(min. 1,5 A) ausgelegt sein. Wenn Sie weitere
Unterstützung benötigen, wenden Sie sich bitte an Wie-
land. Siehe www.wieland-electric.com.
•Stellen Sie sicher, dass die Betriebsspannung an der Span-
nungsversorgung korrekt ist, bevor Sie das Gerät anschlie-
ßen. Die Spannungsversorgung sollte einen geerdeten An-
schluss haben.
•Öffnen Sie niemals das Gerät. Aus Sicherheitsgründen
sollte das Gerät nur von einer qualifizierten Fachkraft ge-
öffnet werden
•Dieses Gerät ist nicht für die Verwendung an Orten geeig-
net, an denen sich Kinder aufhalten können.
•This product is intended to be supplied by a UL certified
power supply or DC source suitable for use at minimum
Tma 75 °Cwhose output meets SELV or ES1 and is rated
12–48 V DC, 1.5 A minimum. If you need further assistance,
please contact Wieland E lectric
for further information.See
www.wieland-electric.com.
•Ensure that the voltage of the power source is correct be-
fore connecting the equipment to a power outlet.
The power outlet socket should have grounded connec-
tion.
•Never open the equipment. For safety reasons, the equip-
ment should be opened only by qualified skilled person.
•This equipment is not suitable for use in locations where
children are likely to be present.
•Ce produit est destiné à être alimenté par une alimentation
certifiée UL ou une source de courant continu adaptée à
une utilisation à au moinsTma 75 °C dont la sortie satisfait
les conditions SELV ou ES1 et est évaluée à 12–48VCC, 1,5 A
minimum. Si vous avez besoin d'une aide supplémentaire,
veuillez contacter Wieland Electric pour plus d'informa-
tions. Voir www.wieland-electric.com.
•Assurez-vous que la tension de la source d'alimentation est
correcte avant de connecter l'équipement à une prise de
courant. La prise de courant doit avoir une prise de terre.
•N'ouvrez jamais l'équipement. Pour des raisons de sécu-
rité, l'équipement ne doit être ouvert que par une per-
sonne qualifiée.
•Cet équipement ne convient pas à une utilisation dans des
lieux pouvant accueillir des enfants

This manual suits for next models

3

Other Wieland Switch manuals

Wieland SNO 4063K-A User manual

Wieland

Wieland SNO 4063K-A User manual

Wieland wienet FS8 Series User manual

Wieland

Wieland wienet FS8 Series User manual

Wieland SIN 1 Series User manual

Wieland

Wieland SIN 1 Series User manual

Wieland wienet UMS 5-C-4G-1SFP-W User manual

Wieland

Wieland wienet UMS 5-C-4G-1SFP-W User manual

Wieland SNA 4043KE User manual

Wieland

Wieland SNA 4043KE User manual

Wieland wienet IP SWITCH UMS 8-W-M12 User manual

Wieland

Wieland wienet IP SWITCH UMS 8-W-M12 User manual

Wieland SIN 1 Series User manual

Wieland

Wieland SIN 1 Series User manual

Wieland SNO 4003K User manual

Wieland

Wieland SNO 4003K User manual

Wieland UMS 6-C-1G-4PoE-1SFP-W User manual

Wieland

Wieland UMS 6-C-1G-4PoE-1SFP-W User manual

Wieland samos User manual

Wieland

Wieland samos User manual

Popular Switch manuals by other brands

NETGEAR FS516 - Switch Specifications

NETGEAR

NETGEAR FS516 - Switch Specifications

MDT Technologies Glass Push Button II Smart Technical manual

MDT Technologies

MDT Technologies Glass Push Button II Smart Technical manual

Rutenbeck USB 4xUp Mounting instructions

Rutenbeck

Rutenbeck USB 4xUp Mounting instructions

iNels RFSA-61MI quick start guide

iNels

iNels RFSA-61MI quick start guide

Commercial Electric HPSA21CWB user guide

Commercial Electric

Commercial Electric HPSA21CWB user guide

PCB Piezotronics IMI Sensors 685B Series Installation and operating manual

PCB Piezotronics

PCB Piezotronics IMI Sensors 685B Series Installation and operating manual

Sunricher SR-ZG2833PAC-S4 instruction manual

Sunricher

Sunricher SR-ZG2833PAC-S4 instruction manual

HP J4850A Installation and getting started

HP

HP J4850A Installation and getting started

Siemens SIMATIC NET RUGGEDCOM RS900L installation manual

Siemens

Siemens SIMATIC NET RUGGEDCOM RS900L installation manual

Sonifex Redbox RB-DSD8 Handbook

Sonifex

Sonifex Redbox RB-DSD8 Handbook

EUCHNER STA-TW Series operating instructions

EUCHNER

EUCHNER STA-TW Series operating instructions

Extron electronics SW USB Pro Series user guide

Extron electronics

Extron electronics SW USB Pro Series user guide

Brocade Communications Systems VDX 6940 Series datasheet

Brocade Communications Systems

Brocade Communications Systems VDX 6940 Series datasheet

Sonoff ZBMINI user manual

Sonoff

Sonoff ZBMINI user manual

QNO QMP1005G user manual

QNO

QNO QMP1005G user manual

Network Technologies SE-DVI-2 Installation and operation manual

Network Technologies

Network Technologies SE-DVI-2 Installation and operation manual

Vega VEGACAP 66 operating instructions

Vega

Vega VEGACAP 66 operating instructions

LEONI eol 1x2 Operation manual

LEONI

LEONI eol 1x2 Operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.