Instructions condensing Air heaters type XR version XR-GB-4001-a
Page 5/27
Technical details:
Typ TR-4.5 (ERP2018) TR10 TR15 TR20 TR24 TR28 TR40 TR50
Maximum nominal heat input (Nett) kW 10,8 15,7 19,5 23,5 29,0 41,5 51,0
Minimum nominal heat input (Nett) kW 9,0 14,0 14,5 20,0 24,0 35,0 40,0
Maximum heat output kW
Minimum heat output kW 8,3 11,6 13,5 18,4 22,0 32,5 36,6
Efficiency max. power % 93.3 93,0 93,4 92,3 92,1 93,4 92,6
Efficiency min. power % 92,2 92,8 92,8 92,2 91,8 92,9 91,5
Max. air output (+temp. increase) m3/h 2000 2000 1850 3150 3200 4250 5800
Throw horizontal (max.) m 12 12 12 16 16 22 26
Throw vertical (max. warm) m 4 4 4 5 5 6 6
Gas connection G” 1/2” 1/2” 1/2” 1/2” 1/2” 3/4” 3/4”
Electrical connection (50Hz) V 230 230 230 230 230 230 230
Electrical power consumption max. kW 0,200 0,200 0,200 0,190 0,200 0,300 0,425
Electrical power consumption min. kW 0,200 0,200 0,200 0,190 0,200 0,300 0,425
Electrical power consumption
standby
kW 0,004 0,004 0,004 0,004 0,004 0,004 0,004
Electrical consumption Amps max. A 0,9 0,9 0,9 0,8 0,9 1,3 1,8
Emission efficiency, (ηs, flow) % 95.9 93,7 92,5 94,3 93,1 92,4 93,6
Seas. Space heating efficiency % 74,2 72.7 72.9 73,4 72,4 72,5 72.9
NOx emissie (GCV) mg/kWh 93 99 93 97 94 95 96
NOx klasse 4 4 4 4 4 4 4
Flue gas amount max. kg/h 20 30 40 50 55 80 100
Thermostat communication
bussystem (low voltage)
Argus
link
Pressure switch point Pa 120 135 160 135 120 150 150
Sound level dBA 42 42 42 45 45 48 50
Min. suspension height horz. throw M (min.) 1,7 1,7 1,7 1,7 1,7 1,7 1,7
Min. suspension height vertical. throw M (min.) 4,0 4,0 4,0 4,0 4,0 4,0 4,0
Maximum flue / air length m 9 9 9 9 9 9 9
weight kg 50 50 55 67 70 85 100
Nominal supply pressure G20 (H) mbar. 20
Supply pressure (min-max) G20 (H) mbar. 17-25
Gas category II2H3P B/P
Class B23, C13, C33
Max gas consumption G20 (H) m3/h 1,1 1,7 2,1 2,5 3,1 4,4 5,4
d injectors
n x Ømm
2x 1,9 3x 1,9 4x 1,9 5x 1,9 6x 1,9 8x 1,9
10x 1,9
Burner pressure high G20 (H) mbar 15,0 14,5 13,0 12,0 13,0 16,0 15,0
Burner pressure low G20 (H) mbar 10,5 11,5 7,0 8,5 9,0 11,0 9,5
CO2 High (indication) G20 (H) % 8,0 8,2 8,0 8,0 8,0 9,0 8,5
Nominal supply pressure G31 (P) mbar. 30-50
Supply pressure (min-max) G31 (P) mbar. 25-50
Gas category II2H3P B/P
Class B23, C13, C33
Max gas consumption G31 (P) kg/h 0,9 1,2 1,6 1,9 2,4 3,3 4,1
d injectors
n x Ømm
2x 1,4 3x 1,4 4x 1,4 5x 1,4 6x 1,3 8x 1,4
10x 1,4
Burner pressure high G31(P) mbar 23,0 21,3 18,5 16,5 22,5 20,5 20,3
Burner pressure low G31(P) mbar 16,0 17,0 10,0 12,3 15,5 14,5 12,4
CO2 High (indication G30 (B/P) % 9,0 9,3 9 8,8 9,5 9,5 9,7
Nominal supply pressure G30 (B/P) mbar. 30-50
Supply pressure (min-max) G30 (B/P) mbar. 25-50
Gas category II2H3P B/P
Class B23, C13, C33
Max gas consumption G30 (B/P) kg/h 0,7 0,9 1,2 1,4 1,7 2,5 3,1
d injectors
n x Ømm
2x 1,4 3x 1,4 4x 1,4 5x 1,4 6x 1,3 8x 1,4
10x 1,4
Burner pressure high G30(B/P) mbar 18,0 16,5 14,0 13,0 17,5 16,0 16,0
Burner pressure low G30 (B/P) mbar 13,0 13.0 8,0 9,5 12,0 11,5 9,3
CO2 High (indication G30 (B/P) % 9,2 9,2 9,2 9,2 9,2 9,2 9,2