
Manual 55011 Portable Speed Loop Tester
Woodward 6
Engine Start Amplifier
The START switch adds a positive signal to the input signal for as long as it is held in the START
position. This allows controls with a failsafe feature to start operation. After the start period, the signal is
removed from the system, allowing normal closed-loop operation of the control.
Engine Load
A simulated load is provided through a combination of the LOAD ADJUST potentiometer (10-turn) and the
LOAD ON/OFF switch. The potentiometer adjusts the amount of load which is simulated. The ON/OFF
switch permits adding or subtracting the simulated load instantly to or from the control loop, testing the
control's ability to be stable and to react to load swings.
The LOAD ADJ potentiometer produces a voltage that reduces the amount of actuator signal that the
tester uses to set the MPU signal generator.
Engine Response Amplifier
The ACCELERATION switch slows the response of the tester to a change in actuator signal from the
control. In the upper position, the response is slowed at 30 percent per second. At the lower position, the
response is slowed at 50 percent per second. In the center position, the switch sets fast speed response
to a change in actuator signal. The response rates will not exactly equal the response of any given
engine, so the gain and stability settings on the control will have to be set to the exact positions after the
engine is running.
Range Adjustment
The RANGE potentiometer (10-turn) is used to set the tester for the maximum MPU frequency desired.
The MPU frequency is displayed on the digital frequency meter and is scaled in Hertz. The range
adjustment is set with the control running in closed loop.
Speaker
A small speaker in the tester provides an audible translation of the frequency of the MPU simulation. The
audible signal allows tuning the control “by ear”. This is particularly valuable when establishing stability
and response settings on the control. The speaker may be turned off, if desired.
Power Supply to the Control Under Test
The 35 V terminal strip outputs are used to power the control under test when its requirements do not
exceed a maximum of 1 A. If the output terminals are shorted, the circuit breaker will trip, but will not
cause permanent damage to the power supply. Power is not provided for EGM controls which require 117
Vac or 48 Vdc. All portions of the tester are electronically protected by a circuit breaker (Figure 1-1). After
correcting the cause of the trip, reset the circuit breaker by pushing it in.
Switches SW1 and SW2
These miscellaneous function switches can be wired to the control under test to simulate requirements
such as input from shutdowns, overcurrent warnings, or other discrete inputs to the control being tested.
Load Sensor Test Sequence
Current transformer currents are selected, one phase at a time, by the L.S.T. rotary switch. The number 1
position on the switch is off, with the other three positions establishing a comparable phase in the current
portions of the control. The CT current is 5 A, but in some conditions this may vary slightly. To all tester
voltages to be transmitted to the control without change, use 1 mm² (18 AWG) wire and keep the lead
from the test to the control under 600 mm (2 ft) in length.