Extension ED module
XL-2AD2DA-V-ED
Fast manual
Thanks for purchasing XINJE XL series PLC and extension module. This manual will
introduce the electric features and using method of XL series extension ED module. Please
read this manual carefully before using the products, make sure the wiring operation is safe.
Features of analog extension module
XL-2AD2DA-V-ED
2 channels analog input: voltage input mode, 0~5V or 0~10V.
2 channels analog output: voltage output mode, 0~5V or 0~10V.
12-bit high precision analog input, 10-bit high precision analog output.
As the special function ED module of XL, XL series PLC can connect 1 XL-
2AD2DA-V-ED module.
Safety precautions
Control system design attentions
Dangerous!
Make sure design the safety circuit, to ensure that the control system can still work
safety when the external power supply cut off or PLC broken.
Make sure set emergency braking circuit, protection circuit, interlock circuit of forward-
reverse running in PLC external circuit and upper-lower limit switch to prevent from
machine damage.
In order to make the equipment safe operation, please design external protection circuit
for important output signal.
PLC CPU will close all the output when detecting the system error; the output will lose
control when the PLC circuit has problem. Please design suitable external control circuit
to ensure the device working normally.
If the PLC relay or transistor unit is broken, the output cannot be ON or OFF.
The PLC is designed for indoor environment, the lightning protection must be installed
in the power supply system to avoid PLC and other device damage.
Installation and wiring attentions
Dangerous!
Do not use the PLC in the following environment: dust, soot, corrosive gases,
flammable gas, high temperature, condensation, vibration, impact, lightning, fire.
Do not let the metal scrap and wire head drop into the ventilation hole of PLC, otherwise
it will cause fire or error operation.
Do not cover the ventilation hole of PLC, otherwise it will cause fire, error operation.
The I/O wiring must be fixed enough, otherwise the bad contactor will cause fault.
Attention!
It can use external power supply for extension module DC24V power.
Please use shield cable for high frequency I/O wiring to avoid interference.
Run and maintenance
Dangerous!
Please connect all the cable include PLC, extension module and BD board after shutting
down the power supply.
Please operate as the manual for online operation, forced output, RUN, STOP.
Attention!
Please discard the product as industrial waste.
Make sure cut off the power supply when installing or uninstalling the extension card.
Product information
Naming rule
XL– 2 AD 2 DA - V - ED
① ② ③ ④ ⑤ ⑥ ⑦
①Product series XL: XL series extension module
②Analog input channel: 2: 2 channels
③Analog input AD: analog input
④Analog output channel: 2: 2 channels
⑤Analog output DA: analog output
⑥I/O type V: voltage type for input and output
⑦Module type ED: left extension ED module
Basic parameters
XL series PLC can connect 1 extension ED module, the type is not limited.
Table 1: analog extension module XL-2AD2DA-V-ED general specifications
Terminal specifications
When wiring the module, its connector shall meet the following requirements:
(1) stripping length: 9mm;
(2) flexible conductor with tubular bare end 0.25-1.5mm2;
(3) flexible conductor with tubular pre-insulated end 0.25-0.5 mm2.
Product dimension and installation
Installation
Do not install the module in below environment:
Direct sunlight
Environment temperature out of range 0-50℃
Environment humidity out of range 35%-85% RH
Condensation as severe changes in temperature
Corrosive gas and flammable gas
Dust, iron filing, salt, fume
Vibration and impact
Spray oil, water and medicine
Strong magnetic field and strong electric field
XL series extension ED module can be installed in com3 port of XL series PLC.
Note: please cut off the power before operation!
Product dimension (Unit: mm)
XL series extension ED module dimension is shown as below:
Electric design reference
I/O address
XL series extension ED module will not occupy I/O unit, the transformed value is stored in
PLC register. The following is the PLC register corresponding to each channel.