Xinje XMP2-32 series User manual

XINJE
XMP2-32 series
Integral industrial controller
Operating manual
Xinje Electronic Co.,Ltd

Catalog
1. XMP2-32 introduction..................................................................................................................4
1-1 Performance and characteristic...........................................................................................4
1-2 Specs...................................................................................................................................4
1-2-1 General specs...........................................................................................................4
1-2-2 HMI specs................................................................................................................5
1-2-3 PLC specs................................................................................................................5
1-2-4 Product type.............................................................................................................6
1-2-5 Name rule ................................................................................................................6
1-3 Part name............................................................................................................................7
1-3-1 LED display.............................................................................................................8
1-3-2 Download port.........................................................................................................8
1-3-3 Com port..................................................................................................................9
1-3-4 Port A and B ............................................................................................................9
1-4 Outline dimension...............................................................................................................9
2. In-out specs and exterior layout..................................................................................................10
2-1 Input specs and layout ......................................................................................................10
2-2 Output specs and layout....................................................................................................11
3. PLC function and using...............................................................................................................13
3-1 PLC instruction.................................................................................................................13
3-2 Soft component range.......................................................................................................14
3-3 Build a project...................................................................................................................16
3-4 Communication function..................................................................................................18
3-4-1 Com port................................................................................................................18
3-4-2 Communication parameters...................................................................................18
3-4-3 Communication mode ...........................................................................................20
4. HMI function and using..............................................................................................................21
4-1 HMI function....................................................................................................................21
4-2 Build a project...................................................................................................................23
5. The extension ability...................................................................................................................25
5-1 Summarization..................................................................................................................25
5-2. Extend MA model............................................................................................................26


0B1. XMP2-32 introduction
1-1 Performance and characteristic
XMP2-32R-E ( relay output type ) and XMP2-32T-E ( transistor output type ) are integrated with
HMI ( MP series ) and PLC ( XC2 series ) perfectly. They can totally instead of HMI and PLC in
control system with the premiss of meeting the control requests. Small profile can save space and
improve the maintenance convenience.
◆XMP2-32=MP760-T + XC2-32
◆Integrated with logical control, analog quantity in-out, HMI ( human machine interface )
On-off input: 16 points
On-off output: 16 points
uHMI screen: editing simply and directly, rich function, touchable display area
◆ LCD display: 480×234 pixel, 7 inch screen, LCD life can reach 0.5 million hours
◆ 26 function keys, function setting freely, sensitive and precise key-press
◆ Support high speed count, high speed pulse, external interrupt
◆ Mix function designed download port: the same cable for downloading HMI and PLC
program
◆ Waterproof level is IP20
◆ Close construction, save the space of electric control cabinet
◆ Simple, modern and decent appearance
1-2 Specs
1-2-1 General specs
Input voltage AC220V or DC24V
Power Less than 10W (TYP2.0W)
Instant power off
allowance
Less than 20ms
Voltage endurance AC1000V-10mA 1minute between signal and ground
Insulated impedance
DC500V about 10MΩ ( between signal and ground )
Operating
temperature
0~50℃
Conservation
temperature
–10~60℃
Environment
temperature
20~85% (no dew)
Oscillation
endurance
10~25Hz ( X,Y, Z direction for 30 minutes 2G )

Anti-jamming Voltage noise: 1000Vp-p
Air condition No causticity gas
Protect construction
According to IP20
1-2-2 HMI specs
1-2-3 PLC specs
Specs
Item XMP2-32
Programexecuting format Loop scan format, time scan format
Programformat Instruction, C language and ladder chart
Processing speed 0.5us
Power cut retaining Use Flash ROM and Li battery
User program’s capacity 128KB
I/O points Input 16 points, output 16 points
Interior coil’s points (M) 8767
Points 640
Timer
(T)Specs
100mS timer:Set time 0.1~3276.7 seconds
10mS timer:Set time 0.01~327.67 seconds
1mS timer:Set time 0.001~32.767 seconds
Points 640
Counter
(C)Specs 16 bits counter:set value K0~32767
32 bits counter:set value -2147483648~2147483647
Data Register(D)2612 words
Flash ROM Register(FD)
512 words
Type TFT 256-colour LCD
Screen dimension
7 inch
Use life Over 50000 hours, 25℃, 24 hours operating
Display area 480*234
Contrast Unable to change
Character setting Chinese, English, Japanese, Korean, etc.
Character size Free size and font
Characteristic
Touch mode Digital mode touch
Picture 8MB Flash ROM
Register Data 4KB SRAM
Communicate
port RS-232/RS-485
Interface
Download port RS-232

High speed processing
function
High speed count、pulse output、external interrupt
Setting of time scan space 0~99mS
Password protection 6 bits ASCII
Self diagnose function Power on self-diagnose、Monitor timer、grammar check
1-2-4 Product type
XMP-32 series
Relay output Transistor output
XMP2-32R-E XMP2-32T-E
XMP2-32R-C XMP3-32T-C
NOTE:
-E means the power supply is AC220V
-C means the power supply is DC24V
1-2-5 Name rule
1 2 3 4
1: series name XMP
2: PLC type 2: XC2 series
3: I/O points 32: input 16/output 16 points
4: output type R: relay output
T: transistor output

1-3 Part name
Display and touch
area
Number key
Function key
Power point
Product label
Input pointOutput point
Com
port
Download
port
USB、CJ45 port

1-3-1 LED display
PWR: Power supply
RUN: program running
STOP: program stop
1-3-2 Download port
nThe port is RS-232 standard and double function designed, is able to download PLC program
and HMI program.
Pin2 RXD
Pin3 TXD
Pin5 GND
Pin7 RTS
nUsed as RS-485 com port: for HMI connecting with slave device
Cable connection figure:
Attention:
(1) Do not cut the power when downloading, or you have to download again
(2) The cable of downloading HMI program is the same as the downloading PLC program
(3) Do not download when XCPPro and Touchwin software are both running
(4) RS-232 download port is only used to download, do not use it in other way
Pin1
A
Pin9 B
Pin6 PRT (when HMI connecting with slave device, short pin
5&6 )
Pin8 DOWNLOAD ( short pin 5&8 to forced-download HMI
program )

1-3-3 Com port
The port is RS-232 standard, is used to connect PC and HMI.
Pin2 RXD
Pin3 TXD
Pin5 GND
1-3-4 PortAand B
The port is RS-485 standard, is used to connect meter, inverter, extension model, etc.
Attention:
A, B port and RS-232 com port are the same port, can not be used at the same time.
1-4 Outline dimension
Outline dimension ( mm ):

Installate dimension ( mm ):
1
B2. In-out specs and exterior layout
2-1 Input specs and layout
Input specs:
Input connection figure:
Input signal voltage DC24V±10%
Input signal current 7mA/DC24V
Input ON current Above 4.5mA
Input OFF current Below 1.5mA
Input response time About 10ms
Input signal format Point input or NPN
collector open transistor
Circuit insulation Photo-electricity coupling
insulation
Input action display LED is ON when input ON

24V+
24V-
R3
R4
R2
R1
X11
X00
COM
+5V
R5R6
LED
I=7mA
Sensor
DC power
supply
Input point arrangement:
2-2 Output specs and layout
Relay output:
Interior power Below AC250V、DC30V
Circuit insulation Machine insulation
Action indication LED light
Resistor load 3A
Induction load 80VA
Max
load Light load 100W
Open creepage current No
Minimum load DC5V 2mA
OFF→ON 10msResponse
time ON→OFF 10ms
Transistor output:
Interior power Below DC5~30V
Circuit insulation Optical coupling insulation
Action indication LED light
Resistor load 0.8A
Induction load 12w/DC24V
Max
load Light load 1.5W/DC24V

Output connection figure:
uRelay output:
+24V
circuitdrive
relay
Y*3
Y*2
Y*1
Y*0
M
5A~10A
Load
~
AC power
<AC250V
Relay output
To avoid burning PLC basic circuit
set a fuse every 4 points
supply
uTransistor output connection
use suitable fuse for the load
To avoid burning PLC basic circuit
DC power
DC5~30V
Load
Load
Load
Load
1A
circuitdrive
photo-electricity
Y*4
Y*5
Y*6
Y*7
supply
Output point arrangement:
Open creepage current < 0.1 mA
Minimum load DC5V 2mA
OFF→ON 0.2msResponse
time ON→OFF 0.2ms

3B3. PLC function and using
3-1 PLC instruction
XMP2-32 series product used XC2 series PLC, the PLC instructions are the same as XC2-32. It
contains SFC instructions, applied instructions and special function instructions. Please refer to
XC Series PLC Manual: paragraph 4, 5,6.
Here listed in-out point definition and distribution of special function instructions for your
information.
1. high speed count
(1) Increment mode: 5 channels
(2) Pulse + direction mode: 2 channels
(3) AB phase mode: 2 channel
2. High speed pulse output
a) T type: Y0, Y1 available, the highest frequency is 200KHz
b) R type: unavailable
Channel Input Counter Highest frequency
CHL1 X0 C600 80KHZ
CHL2 X1 C602 80KHZ
CHL3 X3 C604 10KHZ
CHL4 X6 C606 10KHZ
CHL5 X7 C608 10KHZ
Channel Input
Pulse Direction
Counter Highest frequency
CHL1 X0 X1 C620 80KHZ
CHL2 X3 X4 C622 10KHZ
Channel Input
Phase A Phase B
Counter Highest frequency
CHL1 X0 X1 C630 80KHZ
CHL2 X3 X4 C632 5KHZ

3. Interrupt function
Pointer tag
Channel
Input
Rising interruption
Falling interruption
Disable interruption
instruction
CHL1 X2 I0000 I0001 M8050
CHL2 X5 I0100 I0101 M8051
CHL3 X10 I0200 I0201 M8052
4. Frequency measurement
The point is X1, X6, X7.
5. Pulse width modulation (PWM)
The point is Y0, Y1.
uT type: Y0, Y1 available
uR type: unavailable
6. Precise timer
32 bit precise timer, the timer range is T600 to T618, match with 10 interruption tag.
3-2 Soft component range
Soft
component
Name Range Point
X Input point
X000~X017(octal) 16
Y Output
point Y000~Y017(octal) 16
M0~ M2999
【M3000~M7999 】8000
M Auxiliary
relay M8000~M8767 768
S Process
S0~ S511
【S512~M1023 】1024
T0~T99:100ms not accumulation
T100~T199:100ms accumulation
T200~T299:10ms not accumulation
T300~T399:10ms accumulation
T400~T499:1ms not accumulation
T500~T599:1ms accumulation
T600~T618:1ms with interruption precise time
T Timer
T620~T639:vacant
640
C Counter
C0~C299:16 bits forth counter 640

C300~C599:32 bits forth/back counter
【C600~C619】:one phase high speed counter
【C620~C629】:
Pulse + direction high speed
counter
【C630~C639】:AB phase high speed counter
D0~D999
【D4000~D4999】2000
D Data
register For special using D8000~D8511
D8630~D8729 612
FD0~FD127 128
FD Flash ROM
register For special using
FD8000~FD8383 384
NOTE:
※1. The memorizer area in 【】is the defaulted power failure retentive area, the power
failure retentive area of soft components D, M, S, T, C can be set via FD register. For
the details, please see the following table.
※2. Flash ROM register needn’t set power failure retentive area, its data won’t lose when
power is cut (No battery).
※3. The serial number of input coil and output relay are octal data, other memorizers’
number are all decimal data.
※4. There is no I/O point connected with exterior device can be used as interior relay.
Soft component power failure area setting:
Soft
component Area Function Default value
Power failure
memory area
D FD8202 First address of the power
failure memory area of D 4000 D4000~D4999
M FD8203 First address of the power
failure memory area of M 3000 M3000~M7999
T FD8204 First address of the power
failure memory area of T 640 -
C FD8205 First address of the power
failure memory area of C 320 C320~C639
S FD8206 First address of the power
failure memory area of S 512 S512~S1023
NOTE:
Users can set the power failure memory area by themselves, but the area can not over the soft
component area.

3-3 Build a project
XMP2-32 series products are integrated with XC series PLC and HMI. When editing PLC
program, please use XCPPro software which is the same as XC series PLC.
1. select the product type
Open XCPPro, click “file---change PLC model”:
Select “XMP2-32”:
2. edit the PLC program
After selecting the type, user can edit the program in the software. The editing specs and operating
details please refer to XC Series PLC Edit Software XCPPro Manual.
The interface of software is as below:

3. download program
After editing and saving the program, users need to download them to XMP. Before downloading,
ensure the XMP has connected with computer successfully. (Please refer to chapter 1-3-2 for cable
connection ).
Click to open software serial port configuration
Choose the correct serial port, baud rate and parity or click “check” to choose these parameters
automatically.
When below window shows “connect to PLC succeeded”, it means the connecting is successful.
Click OK to continue.
If the connecting is not successful, the window will show “communication error”. Please check
the serial port and the cable.
After connecting successfully, click to download the PLC program. If the PLC is running, it
will pop up the stop running window, click OK to continue downloading.

After downloading, click to run the PLC program.
2Upload the program
If you want to check the PLC program in XMP2-32, click to upload the program to the PC.
Then click to save the program.
3-4 Communication function
XMP2-32 series support Modbus and free format communication protocol. The instructions please
refer to XC Series PLC Operating Manual paragraph 6-4-1 and 6-4-2.
3-4-1 Com port
XMP2-32 series product have program port ( DB9 pins port ), RS-232 com port ( DB9 pins port )
and RS-485 com port ( A and B point ). Program port can only be used to download PLC program
and HMI pictures. However, RS-232 and RS-485 com port can be used to communicate with other
devices. The communication parameters ( baud rate, data bit, etc ) can be set via software.
RS-485 com port point A means “+” signal, point B means “-” signal.
Attention:
RS-485 and RS-232 com port are the same, do not use them at the same time.
3-4-2 Communication parameters
Communication parameters of RS-232 and RS-485 com port can be set via FLASH register in
XMP.
The defaulted parameters:

0:300bps
1:600bps
2:1200 bps
3:2400 bps
4:4800 bps
5:9600 bps
6:19.2K bps
7:38.4K bps
8:57.6K bps
9:115.2K bps
0:8bits data
1:7bits data
0:2 stop bits
2:1stop bit
0:No check
1:Odd check
2
:
Even check
Station 1, baud rate 19200bps, 8 data bits, 1 stop bit, even check
Station No. Modbus station No. : 1~254, 255(FF) is for free format communication
Baud rate 300bps~115.2Kbps
Data bit 8 or 7 bits
Stop bit 2 or 1 bits
Check Even, odd, no check
Communication parameters setting are as below table:
Attention:
After changing the parameters in Flash register, it is need to reboot the XMP to make the setting
become effective.
Number Function Description
FD8220
Communication mode
( station number )
255 is free format,
1~254 is modbus station number
FD8221 Communication format Baud rate, data bit, stop bit, check
FD8222 ASC timeout judgment time Unit: ms, 0 means no timeout waiting
FD8223 Reply timeout judgment time Unit: ms, 0 means no timeout waiting
FD8224 Start symbol High 8 bits invalid
FD8225 End symbol High 8 bits invalid
com
port
FD8226 Free format setting
8/16 bits cushion,
with/without start bit,
with/without stop bit
FD8221:
15
14
13
12
11
10
9 8 7 6 5 4 3 2 1 0
The way of setting communication parameters:

0:8 bits communication
1:16 bits communication
0: without start symbol
1: with start symbol
0:without end symbol
1
:
with end symbo
l
Reserved
FD8226:
3-4-3 Communication mode
XMP series product support master and slave mode of Modbus communication protocol.
Master format: When PLC is set to be master station, PLC sends request to other slave station
devices via Modbus instructions, other devices respond to the master station.
Slave format: When PLC is set to be slave station, it can only respond to other master devices.
The defaulted status of XMP is Modbus slave mode.
The internal soft unit’s numbers of XMP are corresponded with Modbus station address numbers,
please see the following table:
Coil space: ( Modbus address prefix is “ 0x ” )
Bit component
address
Modbus address
( decimalK )
Modbus address
( hex H )
M0~M7999 0~7999 0~1F3F
X0~X1037(octal) 16384~16927 4000~421F
Y0~Y1037(octal) 18432~18975 4800~4A1F
S0~S1023 20480~21503 5000~53FF
M8000~M8511 24576~25087 6000~61FF
T0~T618 25600~26218 6400~666A
C0~C634 27648~28282 6C00~6E7A
Register space: ( Modbus address prefix is “ 4x ” )
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Modbus communication
Communication address
Table of contents
Other Xinje Controllers manuals
Popular Controllers manuals by other brands

Derale Perfomance
Derale Perfomance 16788 installation instructions

LU-VE
LU-VE R2PR instructions

Clare Controls
Clare Controls CLIQ.host Installation sheet

Vent-Axia
Vent-Axia 475775 Installation and wiring instructions

LEGRAND
LEGRAND 5739 12 Technical sheet

Hewalex
Hewalex OPTI-TEMP Installation and maintenance guide

Belimo
Belimo AFRB24-SR Wiring diagrams

Honeywell
Honeywell BC7000L1000 Wiring diagrams

Pfeiffer Vacuum
Pfeiffer Vacuum DPG 202 operating instructions

ICM Controls
ICM Controls ICM2812ж ICM2812-KIT Installation, operation & application guide

Parker
Parker A4W Series Installation, Service and Parts Information

ALEXANDER ENGEL
ALEXANDER ENGEL TMAX V2 Installation & operation