PAGE 9
Aquavar IPC Start-Up Genie
CentriPro
CHAPTER 3: FEEDBACK
Feedback Setup allows the conguration of analog inputs (sensors) and other feedback sources.
• Control Feedback Sources: Select the number of feedbacks that are used to
controlling the process variable. The feedbacks referred to are for control, not
for monitoring.
• Feedback 1 Source: The effective feedback signal is made up of up to three
different signals. Select which drive input should be treated as the source of the
rst of these signals. Be sure to properly set the conguration switches A53
and A54 behind the keypad. Switch set to “I” for mA transducer; switch set
to “U” for voltage transducer”.
• Terminal 53 Low Reference
• Low Feedback 1 Value: Enter the minimum feedback value
(in psi, GPM, feet etc.).
• High Feedback 1 Value: Enter the maximum feedback value
(in psi, GPM, feet etc.).
• Feedback 1 Sensor Fault: If enabled, Sensor Fault will display a fault when
sensor voltage or current drops to less than 50% of the minimum value
programmed for that input.
AUTOSET
For basic applications, users are able to set motor information, operation mode and “Autoset” the rest of
the parameters. With support for the most common control congurations, the Genie reduces setup and
conguration time to less than 15 minutes. Autoset parameters vary with application type.
Single Pump Autoset Conguration
Autoset Conguration Constant
Pressure
Level
Control
Flow
Control
Transducer Max Feedback 300 [unit] 300 [unit] 300 [unit]
Transducer Type 4-20mA 4-20mA 4-20mA
Feedback 1 Source AI 33 AI 53 AI 53
PID Performance Normal Fill (Normal) Normal
Sleep Mode Enabled Enabled Disabled
Sleep Frequency 30 Hz 30 Hz N/A
Restart Difference 5 [unit] 5 [unit] N/A
No Water / Loss of Prime Fault Enabled Enabled Enabled
No Water / Loss of Prime Restart Time 10 min. 10 min. 10 min.
Duplex Autoset Conguration
Transducer Max Feedback 300 [unit]
Transducer Type 4-20mA
Feedback 1 Source AI 53
Sleep Frequency 30 Hz
Restart Difference 5 [unit]
No Water / Loss of Prime Fault Enabled
Duty Standby Disabled
Lag Start Frequency 59 Hz
Lag Stop Frequency 35 Hz
Alternation Enabled
Alternation Time 24 hours
Pump Exercise Time 0 s (Disabled)