2.3 Required Power Supply Facility Capacity and
Connection Cables
"Table 2-1 Power Supply Capacity and Power Cables" shows the required power supply
facility capacity and connection cables.
The rated input voltage for the welder is three-phase, 480V.
The welder supports a voltage compensation circuit so that the equipment can operate at a
power voltage within ±10%fluctuations of the rated value. All the same, it is recommended
to use a power source as stable as possible. If fluctuations in power supply voltage exceed
10%of the rated value , power welding conditions cannot be guaranteed and problems may
occur.
Diameter of the input power cable and the fuse capacity must be in compliance with Table 2-1.
Install a non-fuse breaker (NFB) or a switch with fuse for each welder.
The non fuse breaker used should be the same capacity of the fuse indicated in Table 2-1,
and the tripping time at 600%of the rated current should be one second or longer. (General
motor breakers satisfy these requirements.) If breaker capacity is insufficient or primary
voltage is too high, the breaker will be tripped at power on.
Table. 2-1 Power Supply Capacity and Power Cables
Power Supply Capacity 30 kVA
Fuse Rated Current 75 A (rated voltage: 480V)
Input Cable 14 mm2or more
Exclusive-use base metal
cable 60 ㎜2or more (cable length: 5 m or less)
80 ㎜2or more (cable length: 5 m or more) *1
Ground Cable 14 ㎜2or more
*1: Be sure to use cables for welding. Also, use cables with sufficient thickness for
pulse welding or current of 250A or more.
Excessively small gauge cables may result in poor welding and cause abnormal
heating resulting in burn or fire.
2.4 Combination with Earth Leakage Breaker
When the welder is used in a construction site, in a place with high humidity, or on an iron
plate, iron framework, or surface plate with high conductivity, a leakage breaker should be
installed according to the proper regulations or laws. In such a case, connect a leakage
breaker of current sensitivity 30 mA for each welder. The welder may malfunction because of
the inverter operations depending on the model or current sensitivity of the leakage breaker.
Therefore, select a proper one for inverter drives.