<3. Parameter Setting > 3-15
IM 01C50T01-02EN
(2) Auto Release Time
Thisparametercanbeusedtosettheautorelease
timeofLoopTestandSimulation(See3.5.14).
• Proceduretocallupthedisplay
Devicesetup→Diag/Service→TestDevice→
AutoReleaseTime
Selectfrom10minutes,30minutes,60
minutes,3hours,6hoursor12hours.
Defaultsettingis10minutes.
NOTE
Ifthetransmitterisequippedwiththeintegral
indicator,theLCDdisplaysF.O.
3.5.3 Burnout Function
(1) Sensor burnout
Conguretheburnoutmodeinthecaseofsensor
failureordisconnection.
• Proceduretocallupthedisplay
Devicesetup→Basicsetup→AOBasicSetup
→AOSensorBODir:SelectHigh,Low,User
CongorOff.
→AOSensorBOUnit:SelectmAor%
→AOSnsBOUsrVal:Outputsusersetvalue
within3.6to21.6(mA)or-2.5to110(%)
Whenthesensorfailureisdetected,the
transmitteroutputsoneofthefollowingvalues.
Low:Outputs3.6mA
High:Outputs21.6mA
User(mA):OutputsusersetvalueinmA.
Settablewithin3.6to21.6mA.
User(%):Outputsusersetvaluein%.
Settablewithin-2.5to110%.
Off:TheburnoutoutputisNOTdened
Duringsensorburnouttime,anyofAL.09,AL.10
to13orAL.22alarmmessageisgenerated.(See
Chapter4fordetails.)
(2) Burnout in hardware failure
Theoutputstatusofthetransmitterinhardware
failureissetusingaslideswitchontheMAIN
assembly.Thecurrentsettingcanbecheckedin
parameter“PVAlrmtype”.
• Proceduretocallupthe“AOAlrmtype
parameter”display
Devicesetup→Basicsetup→AOBasicSetup
→AOAlrmtyp
Hi:Morethan110%output(21.6mA)
Lo:Lessthan-5%output(3.2mA)
3.5.4 Integral Indicator Display Mode
Whenanintegralindicatorisspeciedwiththe
transmitter,thedisplayitemsanddisplaycyclecan
becongured.
(1) Process Variable Display
ProcessvariablesthatcanbedisplayedinYTAare
shownintheTable3.1.Acycleofuptofourdisplays
(DispOut1,DispOut2,Disp%,DispmA)canbe
shownbyassigningvariablestotheparameters.
Indicatevaluesofprocessvariableswiththe
indicationlimits–99999to99999.
F0305.ai
P SP T F
%
Table 3.1 Process Variable Display
Process variable Disp Out1 Disp Out2
Sensor1
Sensor1−Terminal
Terminal
Sensor2
Sensor2−Terminal
Sensor1−Sensor2
Sensor2−Sensor1
Averege
SensorBackup
PV
SV
TV
QV
Notused ─
NOTE
Even if abnormality or disconnection of the
terminal block temperature sensor occurs,
AL22 may not be output and AL04 may be
generated.
CAUTION
There is a time lag between sensor failure and
sensor abnormality detection.
Since the failed measurement value is output, the
current output also becomes undefined.
When an error is detected, it becomes the output
set with this parameter.
However, when sensor burnout is set to OFF, it
may be held with indefinite measurement value,
so please understanding this point.