
FORM 160.52-O1
11
YORK INTERNATIONAL
LOW / HIGH LINE VOLTAGE TRIP / RESET VALUES
COMPRESSOR LOW LINE VOLTAGE HIGH LINE VOLTAGE
MOTOR OPERATING POINT OPERATING POINT
SUPPLY VOLTAGE CUTOUT-(V) CUTIN-(V) CUTOUT-(V) CUTIN-(V)
RANGE (V) (ON FALL) (ON RISE) (ON RISE) (ON FALL)
380 305 331 415 414
400 320 349 436 435
415 335 362 454 453
440-480 370 400 524 523
550-600 460 502 655 654
Supply Voltage NONE 0 NONE 0
Range Disabled
The maximum permitted motor current is in terms of %
FLA. The duration of time that the current is limited is in
terms of minutes (to a maximum of 255). If not pro-
grammed, the default value is 100% FLA for 00 min-
utes. (See Programming Systems Setpoints, page 16.)
Thus, no pull down demand limit is imposed following
system start, and the % current limit setpoint is used.
CLOCKThis key displays the day of the week, time
of day and calendar date. If not programmed, the de-
fault value is SUNDAY 12:00 AM 1/1/92 .
(See Programming System Setpoints, page 16.)
DAILY SCHEDULEThis key displays the pro-
grammed daily start and stop times, from Sunday thru
Saturday plus Holiday. If desired, the Control Center
can be programmed to automatically start and stop the
chiller as desired. This schedule will repeat on a 7-day
calendar basis. If the Daily Schedule is not pro-
grammed, the default value is 00:00 AM start and stop
times for all days of the week and the holiday. (Note
that the system will not automatically start and stop on
a daily basis with these default values because 00:00
is an Impossible time for the Micro Board. See Pro-
gramming System Setpoints, page 17.) Finally, one or
more days in the week can be designated as a holiday
(see description under HOLIDAY setpoint) and the
Control Center can be programmed (usually Daily
Schedule setpoint) to automatically start and stop the
chiller on those days so designated. The operator can
override the time clock at any time using the COM-
PRESSOR switch.
Note that if only a start time is entered for a particular
day, the compressor will not automatically stop until a
scheduled stop time is encountered on a subsequent
day.
HOLIDAYThis key indicates which days in the up-
coming week are holidays. On those designated days,
the chiller will automatically start and stop via the holi-
day start and stop times programmed in the DAILY
SCHEDULE setpoint. It will do this one time only and
the following week will revert to the normal daily sched-
ule for that day.
REMOTE / RESET TEMP RANGEThis key displays
the maximum offset of remote LCWT setpoint reset.
This offset is either 10° or 20°F (5.5° or 11.1°C) as pro-
grammed. When in the REMOTE mode, this value is
added to the operator programmed CHILLED LIQUID
TEMP setpoint and the sum equals the temperature
range in which the LCWT can be reset. For example, if
the operator programmed CHILLED LIQUID TEMP
setpoint is programmed with a value of 10°F (5.5°C),
then the CHILLED LIQUID TEMP setpoint can be re-
motely reset over a range of 46°F to 56°F (46 + 10 =
56) (7.7° to 13.3°C). If not programmed, the default
value for this parameter is 20°F (11.1°C).
For additional information on remote LCWT reset, re-
fer to Form 160.49-PW13.
NOTE: If an Energy Management System is interfaced
to the Control Center for the purpose of remote
LCWT setpoint reset, then the operator pro-
grammed REMOTE RESET TEMP RANGE
value determines the maximum value of tem-
perature reset controlled by the Energy Man-
agement System.
DATA LOGGERThis key is used when an optional
printer is connected to the MicroComputer Control
Center. Refer to Form 160.49-N2 for operation instruc-
tions.
SSS MOTOR CURRENT/VOLTSThis key is used on
Solid State Starter applications only. Although this is a
display key, it is used to program the applicable AC
power line voltage range (380VAC, 400VAC, 415VAC,
440-480VAC, 550-600VAC). The MicroComputer Con-
trol Center uses this entry to determine the under-volt-
age and overvoltage shutdown threshold. For each
line voltage category, there is an undervoltage and ov-
ervoltage shutdown threshold. If the AC power line volt-
age exceeds these thresholds for 20 continuous sec-
onds, the chiller shuts down and displays
MON 10:00 AM LOW LINE VOLTAGE
or
MON 10:00 AM HIGH LINE VOLTAGE
This overvoltage and undervoltage protection can be
disabled. Refer to chart below:
For security reasons, a special access code is required
to program the supply voltage range. The supply volt-
age range is programmed at the factory and should
only be changed by a service technician.