
PART-WINDING START (SYSTEM #1)
Unitswithvoltagesof208/230and380/415havetwocompres-
sorcontactorsandincludepartwindingstart.Onstart-up,timer
4TR prevents contactor 2M from being energized until 1
second after contactor 1M is energized. This 1-second delay
reduces the LRAof the compressor substantially. Refer to the
electrical data in Table 3or 4.
PUMPDOWN (SYSTEM #1)
Whenthecompresorisrunningatpartloadandwhentheliquid
cooling requirementbecomes satisfied, contact TC-1 will open
to de-energize relay 16R. Contact 16R-2 will open tode-ener-
gize liquid line solenoidvalve 1LLS, and no refrigerant will flow
to the 20 ton side of the cooler. Contact 16R-1 will open but
contact1R-2 will keepthe20 toncompressorin operationuntil
the low side of the system is pumped out and low pressure
control LP opens to shut the No. 1 system down.
ANTI-SHORT CYCLING (SYSTEM #1)
WhenlowpressurecontrolLP openstode-energizethe20ton
compressor and the condenser fans, relay 1R will also be
de-energized. 1R-1 opensand de-energizes 1MP.When 1MP
is re-energized, contacts 1MP close after a 2 minute delay
which provides anti-short cycle protection.
OIL FAILURE (SYSTEM #1)
If the oil to suction pressure differential drops below 14 psig (±2),
1 OPA in the oil pressure control will close and energize timer
2TR. If this low pressure condition exists for more than 90
seconds, 2TR contac will open to shut down the compressor
and condenser fans.
HIGH / LOW PRESSURE LOCKOUT (SYSTEM #1)
If the compressor discharge pressure exceeds398 psig or the
suction pressure drops below 30 psig, 1HP or 1LP will open
and shut downthecompressor #1 andoutdoorfans #1, #2and
#3. At the same time, lockout relay 18R will energize. 18R-1
willopenandpreventtheunitfromrestartingwhen1HP or1LP
closes. The unit can be reset by momentarily opening the unit
disconnect switch provided 1HP and 1LP have closed. After
reset, the unit will start after the 2 minute time delay provided
there is a call for cooling.
COMPRESSOR NO. 2 OPERATION
When the third stage of the TC (81) calls for cooling.:
1. TC-5 closes and energizes relay17R. 17R-1 will energize
compressor protector module 2MP, and after a 2 minute
time delay 2MP contacts will close. Contact 17R-3 closes
energizing contactors 3M, 6M, relays 7R, 21R, and timer
5TR. 17R-2 energizes liquid line solenoid valve 2LLS, and
liquid refrigerant will flow to the expansion valve.
2. Relay 7R contacts close, with 7R-1 and 7R-2 closing in
parallel withcontacts 17R-1 and 17R-3 respectively main-
taining operation during the pumpdown cycle.
3. Contactor 3M energizes compressor #2, and contactor 6M
energizes the condenser fans #4, #5 and #6. 21R opens
to de-energize compressor crankcase heater 2CCH while
the compressor runs.
4. After 2 minutes, low pressure bypass timer 5TR-1 opens.
Ifthecompressorsuctionpressureremainsabnormallylow
after initial start-up, the compressor circuit will lock out as
described in the HIGH / LOW PRESSURE LOCKOUT
section.
When the fourth stage of the TC (81) calls for cooling:
1. Contacts TC-7 will close to energize relay 11R and 12R.
2. When relay 11R is energized condenser fan No. 5 will start
up, providing the temperature of the outdoor air is above
the 45°F set point of thermostat 4TH. When relay 12R
closes, condenser fan No. 6 will start.
NOTE: If the temperature of the O.D. air is above the 75
°
F
set point of 5TH, condenser fan No. 6 will already
be in operation.
3. Contact TC-8 will open to de-energize compressor sole-
noid valve 4SOLand 5SOLand the 30ton compressor will
operate at full capacity.
PART-WINDING START (SYSTEM #2)
Unitswithvoltagesof208/230and380/415havetwocompres-
sorcontactorsand includepartwindingstart.Onstart-up,timer
8TR prevents contactor 4M from being energized until 1 sec-
ond after contactor 3M is energized. This 1-second delay
reduces the LRA of the compressor substantially. Refer to the
electrical data in Table 3 or 4.
PUMPDOWN (SYSTEM #2)
When the compresor #2 is running at part load and when the
third stage of the TC becomes satisfied, contact TC-5 will
open and de-energize relay 17R. Contact 17R-2 will open to
de-energize liquid line solenoid valve 2LLS, and no refrigerant
will flow to the 30 ton side of the cooler. Contact 17R-1 will
open but contact 7R-2 will keep the 30 ton compressor in
operation until the low side of the system is pumped out and
low pressure control 2LP opens to shut the unit down.
ANTI-SHORT CYCLING (SYSTEM #2)
When low pressure control 2LP opens to de-energize the 30
ton compressor and the condenser fans, relay 7R will also be
de-energized. 7R-1 opens and de-energizes 2MP. When 2MP
is re-energized, contacts 2MP close after a 2 minute delay
which provides anti-short cycle protection.
OIL FAILURE (SYSTEM #2)
If the oil to suction pressure differential drops below 14 psig (±2),
2 OPA in the oil pressure control will close and energize timer
6TR. If this low pressure condition exists for more than 90
seconds, 6TR contact will open to shut down the compressor
and condenser fans.
HIGH / LOW PRESSURE LOCKOUT (SYSTEM #2)
If the compressor discharge pressure exceeds398 psig or the
suction pressure drops below 30 psig, 3HP or 2LP will open
and shut downthecompressor#2 andoutdoorfans#4,#5 and
#6. At the same time, lockout relay 19R will energize. 19R-1
will open and prevent the unit from restarting when 3HP ( or
2LP closes. The unitcan be reset by momentarily opening the
unit disconnect switch provided 3HP and 2LP have closed.
After reset, the unit will start after the 2 minute time delay
provided there is a call for cooling.
570.05-N4Y
Unitary Products Group 9