FORM 150.52-W1
9
YORK INTERNATIONAL
NOTES (pages 4 - 9)
1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all
other loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to
the system #2 MCA values in the YCAR Tables: -17, add 10 amps; -28, add 9 amps; -40, add 5 amps; -46, add 4 amps; -58, add 3 amps.
2. The recommendation disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the
circuit, per N.E.C. 440 - 12A1.
3. Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs (U.L. Standard 1995, Section 36.1).
Minimum fuse rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
4. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit,
per N.E.C. 440-22. Maximum fuse rating = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
5. Minimum circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit, per circuit per U.L. 1995 Fig. 36.2.
Minimum circuit breaker rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
6. Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit,
per U.L. 1995 Fig. 36.2. Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other compressor RLAs + ( # fans x each
fan motor FLA).
7. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2), or (3)
indicate the number of termination points or lugs which are available per phase. Actual wire size and number of wires per phase must
be determined based on ampacity and job requirements using N.E.C. wire sizing information. The above recommendations are based
on the National Electric Code and using copper connectors only. Field wiring must also comply with local codes.
8. A ground lug is provided for each compressor system to accommodate field grounding conductor per N.E.C. Article 250-54. A control
circuit grounding lug is also supplied. Incoming ground wire range is #6 - 350 MCM.
9. The field supplied disconnect is a “Disconnecting Means” as defined in N.E.C. 100.B, and is intended for isolating the unit from the
available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
SYSTEM #1 SYSTEM #2
MODEL VOLTS COMPRESSOR DATA FAN DATA11, 12 COMPRESSOR DATA FAN DATA11,12
YCAR RLA PW-LRA X-LRA QTY FLA LRA RLA PW-LRA X-LRA QTY FLA LRA
(EA.) (EA) (EA) (EA)
380 116 429 552 3 4.8 23 116 429 552 3 4.8 23
1 SC 460 92 360 463 3 3.8 19 92 360 463 3 3.8 19
575 74 286 368 3 3.1 15.2 74 286 368 3 3.1 15.2
380 148 557 707 3 4.8 23 116 429 552 3 4.8 23
11 SC 460 117 461 585 3 3.8 19 92 360 463 3 3.8 19
575 94 375 475 3 3.1 15.2 74 286 368 3 3.1 15.2
380 148 557 707 3 4.8 23 148 557 707 3 4.8 23
12 SC 460 117 461 585 3 3.8 19 117 461 585 3 3.8 19
575 94 375 475 3 3.1 15.2 94 375 475 3 3.1 15.2
380 165 623 769 3 4.8 23 148 557 707 3 4.8 23
13 SC 460 131 519 641 3 3.8 19 117 461 585 3 3.8 19
575 105 415 513 3 3.1 15.2 94 375 475 3 3.1 15.2
380 165 623 769 4 4.8 23 165 623 769 4 4.8 23
14 SC 460 131 519 641 4 3.8 19 131 519 641 4 3.8 19
575 105 415 513 4 3.1 15.2 105 415 513 4 3.1 15.2
380 207 767 961 4 4.8 23 165 623 769 4 4.8 23
15 SC 460 164 639 801 4 3.8 19 131 519 641 4 3.8 19
575 131 507 635 4 3.1 15.2 105 415 513 4 3.1 15.2
380 207 767 961 4 4.8 23 207 767 961 4 4.8 23
17 SC 460 164 639 801 4 3.8 19 164 639 801 4 3.8 19
575 131 507 635 4 3.1 15.2 131 507 635 4 3.1 15.2
380 237 767 961 4 4.8 23 207 767 961 4 4.8 23
18 SC 460 188 639 801 4 3.8 19 164 639 801 4 3.8 19
575 150 507 635 4 3.1 15.2 131 507 635 4 3.1 15.2
380 237 767 961 5 4.8 23 237 767 961 5 4.8 23
19 SC 460 188 639 801 5 3.8 19 188 639 801 5 3.8 19
575 150 507 635 5 3.1 15.2 150 507 635 5 3.1 15.2
380 288 1105 1424 5 4.8 23 237 767 961 5 4.8 23
2 SC 460 228 910 1173 5 3.8 19 188 639 801 5 3.8 19
575 182 737 950 5 3.1 15.2 150 507 635 5 3.1 15.2
380 288 1105 1424 5 4.8 23 288 1105 1424 5 4.8 23
23 SC 460 228 910 1173 5 3.8 19 228 910 1173 5 3.8 19
575 182 737 950 5 3.1 15.2 182 737 950 5 3.1 15.2