
FORM 201.24-EG1
7
YORK INTERNATIONAL
ALTERNATIVE REFRIGERANTS- Contact yournearestYORK of-
ficeforinformationandavailabilityonalternativeHFCrefrigerants.
ELECTRICALOPTIONS:
MULTIPLEPOINT POWERSUPPLYCONNECTION-
Standard field power wiring connection on all models is Multiple
PointPower Connection to factory provided Terminal Blocks. Two
fieldsupplied electrical power circuitswith appropriate branch cir-
cuit protection provide power to each of two motor control center
cabinets,located on either side of theControl panel on the frontof
the chiller. Each cabinet contains starter elements for one com-
pressor.
Optional to the Terminal Blocks for field power connection are
Non-FusedDisconnectsorCircuitBreakerSwitcheswithexternal,
lockablehandles.
SINGLE POINT POWER CONNECTION - (Factory Mounted) An
optionalconfiguration for field connection of a single electrical cir-
cuitto:either TerminalBlock or Non-Fused Disconnect Switch with
lockableexternalhandle (in compliance with Article 440 of N.E.C.,
to isolate unit power supply for service). Factory wiring is pro-
vided from the Terminal Block or Disconnect Switch to Factory
suppliedindividual system CircuitBreakers,Non-Fused Disconnect
switchwithexternal, lockable handle or J Class Fuses/FuseBlock
ineachofthetwo compressor motor control centers. (Note: Single
PointNon-Fused Disconnect Switch willnot be supplied withindi-
vidualsystemNonFusedDisconnectSwitcheswithexternal,lock-
able handles in each of the two compressor motor control cen-
ters).
65 Ka HIGH VOLTAGE PROTECTION - Non-Fused Disconnect
Switch with fuses (200 & 575V) or Circuit Breakers (230, 380, &
460V) are used for applications where customers have a require-
ment for single point wiring with high “fault current” withstanding
capability.Thisoptionprovidesbetween50Kaand65Kawithstand
protectiontotheequipment.
BUILDING AUTOMATION SYSTEM INTERFACE (Factory
Mounted) – Provides means to reset the leaving chilled liquid
temperature or percent full load amps (current limiting) from the
BAS (Factory Mounted):
• Printed circuit board to accept 4 to 20 milliamp, 0 to 10 VDC,
or dry contact closure input from the BAS.
• AYORK ISN Building Automation System can provide a Pulse
WidthModulated (PWM) signal direct to the standard control
panel via the standard onboard RS485 port.
FLOW SWITCH – The flow switch or its equivalent must be fur-
nished with each unit. 150 PSIG (10.5 bar) DWP – For standard
units.JohnsonControlsmodelF61MG-1CVapor-proofSPDT,NEMA
4X switch (150 PSIG [10.5 bar] DWP), -20°F to 250°F- (29°C to
121°C), with 1" NPTconnection forupright mounting in horizontal
pipe. (Field mounted)
DIFFERENTIALPRESSURESWITCH-Alternativetotheabovemen-
tionedFlow Switch. Pretemco Model DPS 300A-P4OPF-82582-S
(20.7barmax working pressure).SPDT5 amp 125/250VACswitch.
Range:0 - 2.8bar,deadband:0.003- 0.005bar,with1/4 NPTE pres-
sure connections.
LANGUAGE LCD ANDKEYPAD - Standarddisplay languageand
keypadisinEnglish.Spanishis available as an option.
PRINTER KIT - Printer for obtaining printout ofunit operating and
history data. (Field Mounted)
MULTIPLE UNIT SEQUENCE CONTROL (Field Mounted) - Se-
quencingControlwith automatic unit sequencing. Necessary items
for operation and control of up to eight units with parallel water
circuits. Includes software and mixed liquid temperature sensor
(interconnecting wiring by others).
PRESSURE VESSEL CODES - Coolers and condensers can be
supplied in conformance with the following pressure codes:
A.S.M.E.(Standard)
CHICAGOCODE RELIEF VALVES (FactoryMounted)- Unitwillbe
providedwith relief valves to meet ChicagoCode requirements.
ACCESSORIES:
FLANGES (Weld Type) –Consistsof150PSI(10.5bar)standard
cooler (150 lb) R.F. flanges to convert to flanged cooler-connec-
tions and includes companion flanges. (Field mounted)
FLANGES (Victaulic Type) – Consists of (2) Flange adapter for
grooved end pipe (standard 150 PSI [10.5 bar] cooler). Includes
companion flanges. (Field mounted)
VIBRATIONISOLATION:
• Neoprene Isolators – Recommended for normal installations.
Provides very good performance in most applications for the
least cost. (Field mounted)
•1" Spring Isolators – Level adjustable, spring and cage type
isolators for mounting under the unit base rails. 1" nominal de-
flection may vary slightly by application. (Field mounted)
•2"Seismic Spring Isolators– RestrainedSpring-Flex Mountings
incorporate a rugged welded steel housing with vertical and
horizontal limit stops. Housings designed to withstand a mini-
mum1.0gaccelerated force in all directions to 2".Leveladjust-
able,deflection may varyslightlyby application. (Field-mounted)
ALTERNATIVE CHILLEDFLUIDAPPLICATIONS:
Standard waterchillingapplicationrangeis40°Fto50°F(4.4°Cto
10°C)Leaving Chilled WaterTemperature. Toprotect against nui-
sancesafetytripsbelow 40°F(4.4°C)andreducethepossibility of
cooler damage due to freezing during chiller operation, the unit
microprocessorautomatically unloads the compressors at abnor-
mallylowsuction temperature (pressure) conditions,priortosafety
shutdown.
•Process Brine Option – Process or other applications requir-
ing chilled fluid below 40°F (4.4°C) risk water freezing in the
evaporator, typically overcome by using antifreeze. For these
applications,thechiller system incorporates brine (ethylene or
propyleneglycolsolution),andthesystemdesignLeavingChilled
FluidTemperaturemustbeprovided on theorderformtoensure
proper factory configuration.
•Thermal Storage Option – Thermal Storage equires special
capabilitiesfrom a chiller, including the ability to‘charge’ an ice
storagetank, then possibly automatically resetfor operation at
elevatedLeavingChilled Fluid Temperaturesas required by au-
tomaticbuildingcontrols. The Thermal Storage Option provides
Ice Storage duty Leaving Chilled Fluid setpoints from 25°F to
15°F(-4°C to -10°C) minimumduringchargecycle,with a Reset
rangeof36°F (20°C) supply fluid temperature.
Accessories & Options