Zennio inBOX DIM Guide

© Zennio Avance y Tecnología S.L. Edition 1 Further information www.zennio.com Page 1/ 4
inBOX DIM
Universal Dimmer for Flush Mounting - 1 Output (250W@230VAC / 200W@110V) / 2 A/D inputs
ZDI-IBD Technical Documentation
FEATURES
▪1 channel for R L C loads and for dimmable CFL and LED lamps.
▪Automatic detection of R L C load type.
▪Automatic frequency detection.
▪Dimming pattern selection for CFL and LED lamps.
▪Optional manual dimming control.
▪2 inputs configurable as
▪Binary input.
▪Temperature probe.
▪Motion sensor.
▪10 logical functions.
▪External 110/230VAC 50/60Hz power supply.
▪Total data saving on KNX bus failure.
▪Integrated KNX BCU.
▪Dimensions Ø50 x 26mm.
▪Can be mounted within distribution boxes, junction boxes or wall
back boxes.
▪Conformity with the CE directives (CE-mark on the back side).
Programming/test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe
mode. If this button is held for more than 3 seconds, the device enters the test mode.
Programming/Test LED: programming mode indicator (red). When the device enters into safe mode, it blinks (red) every half second. The manual
mode is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it emits a red flash.
1. Output status LEDs
2. Programming/Test button
3. Programming/Test LED
4. Inputs
5. External power supply
6. Output
7. Output control buttons
8. KNX connector
Figure 1. inBOX DIM
GENERAL SPECIFICATIONS
CONCEPT
DESCRIPTION
Type of device
Electric operation control device
KNX
supply
Voltage (typical)
29VDC SELV
Voltage range
21…31VDC
Maximum
consumption
Voltage
mA
mW
29VDC (typical)
8.2
237.8
24VDC(1)
10
240
Connection type
Typical bus connector TP1 for rigid cable 0.80mm Ø
External power supply
110/230VAC 50/60Hz
Operation temperature
0ºC to +40ºC
Storage temperature
-20ºC to +55ºC
Operation humidity
5 to 95% RH (no condensation)
Storage humidity
5 to 95% RH (no condensation)
Complementary characteristics
Class B
Protection class
II
Operation type
Continuous operation
Device action type
Type 1
Electrical stress period
Long
Degree of protection
IP20, clean environment
Installation
Independent device to be mounted inside distribution boxes, junction boxes or wall
back boxes.
Minimum clearances
Not required
Response on KNX bus failure
Data saving according to parameterization
Response on KNX bus restart
Data recovery according to parameterization
Operation indicator
The programming LED indicates programming mode (red) and test mode (green).
Each output LED indicates its status (fixed = active output; flashing = dimming error)
Weight
43g
PCB CTI index
175V
Housing material
PC FR V0 halogen free
(1) Maximum consumption in the worst case scenario (KNX Fan-In model)
3
6
8
2
4
1
7
5

© Zennio Avance y Tecnología S.L. Edition 1 Further information www.zennio.com Page 2/ 4
SUPPORTED LOADS
▪R = Resistive
▪L = Inductive
▪C = Capacitive
▪CFL = Dimmable Compact Fluorescent Lamps
▪LED = Dimmable LED lamps
LOAD COMBINATION
▪If combining resistive (R) with inductive (L) loads, please do not exceed a 50% share
for the resistive load.
▪If combining resistive (R) with capacitive (C) loads, please do not exceed a 50%
share for the resistive load.
▪NEVER connect capacitive loads and electronic transformers with inductive
loads in the same channel.
▪Do not combine in the same channel CFL or LED lamps with R L C loads.
▪It is not advisable to combine different models of CFL lamps, LED lamps or
transformers in the same channel since correct operation can be affected.
OVERHEATING PROTECTION
▪When the ambient temperature is too high the universal
dimmer actuator will regulate itself, at a maximum of 20%.
▪Once the ambient temperature decreases, the dimmer will
resume normal operation. Please, refer to user manual.
INPUTS SPECIFICATIONS AND CONNECTIONS
CONCEPT
DESCRIPTION
Number of inputs
2
Inputs per common
2
Operation voltage
+3.3VDC in the common
Operation current
1mA @ 3.3VDC (per input)
Maximum impedance
Approx. 3.3kΩ
Switching type
Dry voltage contacts between input and common
Connection method
Screw terminal block
Maximum cable length
30m
NTC probe length
1.5m (up to 30m)
NTC accuracy (@ 25ºC)
±0.5ºC
Temperature resolution
0.1ºC
Cable cross-section
0.5mm² to 1mm² (20-16AWG)
Maximum response time
10ms
Any combination of the next accessories is allowed in the inputs:
Temperature
probe references:
ZN1AC-NTC68E
ZN1AC-NTC68F
ZN1AC-NTC68S
ZAC-SQAT-W/S/A
Up to two motion sensors
can be plugged into the
same device input
(parallel wiring)
Motion sensor cable
screw terminal.
Motion sensor reference:
ZN1IO-DETEC-P(1)
ZN1IO-DETEC-X
Temperature Probe
Motion Sensor
Switch/Sensor/
Push Button
(1) The micro switch number 2 in the ZN1IO-DETEC-P sensor must be in Type B position to work properly.
Motion sensor reference:
ZN1IO-DETEC
ZN1IO-DETEC-N
ZN1IO-DETECT-P(1)
R
L
C
CFL
LED
NOT!

© Zennio Avance y Tecnología S.L. Edition 1 Further information www.zennio.com Page 3/ 4
ERROR NOTIFICATIONS
ERROR
LED BEHAVIOR
VISUAL NOTIFICATION
Short circuit
The two LEDs blink alternately each
0.25 seconds.
When the output is locked, the
programming LED blinks in blue
(please, refer to user manual).
Voltage Surge
The two LEDs o blink simultaneously
each 0.25 seconds.
When the output is locked, the
programming LED lights in blue
(please, refer to user manual).
Overheating
The two LEDs blink each second.
Supply Voltage Failure
One LED blinks each second.
Anomalous Frequency
The two LEDs blinks (during 1
second) sequentially and they remain
1 second turned off.
Parameterization Error
One LED blink each second while the
other LED blinks each 0.25 seconds.
0
0.5
1 0
0.5
1.5 1
1.5
2 2
2.5
2.5 3
3.5
3
0
1
1 0
0.5
2 1
1.5
2 2
2.5
3 3
3.5
3
0
0.5
1
1.5
2
2.5
3
0
0.5
1
1.5
2
2.5
3
0
0.5
1
1.5
2
2.5
3
0
0.5
1
1.5
2
2.5
3
Status
LEDs
TIME (s)
Prog. LED
(blue)
Status
LEDs
TIME (s)
Prog. LED
(blue)
Status
LEDs
TIME (s)
Status
LEDs
TIME (s)
Status
LEDs
TIME (s)
Status
LEDs
TIME (s)

© Zennio Avance y Tecnología S.L. Edition 1 Further information www.zennio.com Page 4/ 4
SPECIFICATIONS AND CONNECTIONS OF EXTERNAL POWER SUPPLY
Fuse protection of
supply to power
source
Voltage
250V
Current
10A
Response type
F (Fast acting)
Connection method
Screw terminal block
Cable cross-section
0.5mm² to 4mm² (20-12AWG)
OUTPUT SPECIFICATIONS AND CONECTIONS
Contact type
Solid state switching device
Load protection
Yes; overheating, voltage surge and short-circuit protection
Dropping voltage
Negligible
Connection type
Screw terminal block
Recommended cable section
0.5mm² to 4mm² (20-12AWG)
Cable type
Stranded or solid wire
Response time
Negligible
LOADS AND POWER (@ 25ºC ambient temperature around the device)
230VAC
110-125VAC
RLC
Up to 250W
Up to 200W
CFL and LED(1)
Up to 250W
Up to 200W
SAFETY INSTRUCTIONS
•Installation should only be performed by qualified professionals according to the laws and regulations applicable in each country.
•Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for the entire
KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other
accessories, in case of being installed.
•The facility must be equipped with a device that ensures the omnipolar sectioning. Installation of a 10A mini-circuit-breaker is
recommended. To prevent accidents, it must remain open in case of manipulation of the device.
•Once the device is installed (in the panel or box), it must not be accessible from outside.
•Keep the device away from water and do not cover it with clothes, paper or any other material while in use.
•The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at
http://zennio.com/weee-regulation.
DIMMER OUTPUT WIRING DIAGRAM
(1) for leading edge, the maximum load could change depending on the load type. Please refer to the link
http://zennio.com/download/technical_note_inBOX_DIM_list_en.