© Zennio Avance y Tecnología S.L. Edition 8 Further information www.zennio.com Page 2/2
SAFETY INSTRUCTIONSANDADDITIONAL NOTES
•Installation should only be performed by qualified professionals according to the laws and regulations applicable in each country.
•Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for the entire
KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other
accessories, in case of being installed.
•The facility must be equipped with a device that ensures the omnipolar sectioning. Installation of a 10 A mini-circuit-breaker is
recommended. To prevent accidents, it must remain open in case of manipulation of the device.
•Once the device is installed (in the panel or box), it must not be accessible from outside.
•Keep the device away from water (condensation over the device included) and do not cover it with clothes, paper or any other material
while in use.
•The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at
https://www.zennio.com/en/legal/weee-regulation.
OUTPUTS SPECIFICATIONS AND CONNECTIONS
Solid state switching device
220 mA, 300 mA, 350 mA, 500 mA, 550 mA, 630 mA, 700 mA, 750 mA,
900 mA or 1000 mA.
Constant Current LED load
Screw terminal block (0.2 Nm max.)
0.2-1.5 mm² (IEC) / 16-30 AWG (UL)
EXTERNAL POWER SUPPLY SPECIFICATIONS AND CONNECTIONS
Pluggable screw terminal block (0.4 Nm max.)
0.5-2.5 mm² (IEC) / 28-12 AWG (UL)
WIRING AND ASSEMBLY DIAGRAMS
Each LED load must be connected according to its positive and the negative terminals. Respect always
the maximum current allowed by the loads.
Correspondence
+ and - terminals of external power supply (
voltage) from 12 to 30 VDC.
It is recommended to use the closest external power
supply value to the load working voltage.
Assembly:
Screw mounting, 2 holes of
3.5 mm diameter. Screws not
included.
SEVERAL LOADS CONNECTED TO THE SAME OUTPUT
Power restriction: It is mandatory to fulfil the next restriction
regarding the power connected to one output channel:
OUTPUT CURRENT SELECTOR SWITCH
*it is mandatory that the output current chosen by ETS
parameter and the current selected with the switchmatch. On
the contrary, the load cannot be controlled and the test LED will
blink in white.
TEST LED ERROR IDENTIFICATION
Depending on the color, the test LED indicates different errors:
No auxiliary power supply detected
Wrong auxiliary power supply polarization
Important warning: the following rules when not
considered may result in load or device irreversible
damages