Zennio Lumento C4 Guide

© Zennio Avance y Tecnología S.L. Edition 8 Further information www.zennio.com Page 1/2
Lumento C4
4-channel constant current PWM dimmer for DC LED loads
ZDI-RGBCC4 TECHNICAL DOCUMENTATION
FEATURES
•Control of constant current RGBW LED loads or 4 independent channels
•Output currents: 220 mA, 300 mA, 350 mA, 500 mA, 550 mA, 630 mA,
700 mA, 750 mA, 900 mA and 1000 mA
•External 12-30 VDC power supply
•LED test function
•Integrated KNX BCU (TP1-256)
•Dimensions 165 x 44 x 23 mm
•Surface-mounted inside panels or boxes
•Conformity with the CE, UKCA, RCM directives (marks on the back side)
Figure 1: Lumento C4
Programming button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe mode.
Programming LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. During the start-up
(reset or after KNX bus failure) and if the device is not in safe mode, it emits a red flash.
Test button: if this button is held for more than 3 seconds, the device enters the test mode.
Test LED: it indicates which channel (red=channel 1/R, green=channel 2/G, blue=channel 3/B) is being tested during test mode. In addition, it shows
errors in the installation and/or parameterization (see section “test LED error identification”).
GENERAL SPECIFICATIONS
CONCEPT
DESCRIPTION
Type of device
Electric operation control device
KNX supply
Voltage (typical)
29 VDC SELV
Voltage range
21-31 VDC
Maximum
consumption
Voltage
mA
mW
29 VDC (typical)
8
232
24 VDC¹
10
240
Connection type
Typical TP1 bus connector for 0.8 mm Ø rigid cable
External power supply
12-30 VDC
Operation temperature
0 .. +55 °C
Storage temperature
-20 .. +55 °C
Operation humidity
5 .. 95%
Storage humidity
5 .. 95%
Complementary characteristics
Class B
Protection class
III
Operation type
Continuous operation
Device action type
Type 1
Electrical stress period
Long
Degree of protection
IP20, clean environment
Installation
Independentdevice to be surface-mountedinside electricalpanels or boxes.
The installation is also possible in false ceiling. Connect the device as near
as possible to both, the load to dimmer and the external power supply.
Minimum clearances
Not required
Response on KNX bus failure
Data saving according to parameterization
Response on KNX bus restart
Data recovery according to parameterization
Operation indicator
The programming LED indicates programming mode (red). The Test LED
indicates the following events: red light on with test mode (red), green light
on with test mode (green), blue light on with test mode (blue), white light on
withtestmode (white), powersupplyreversepolarity (orange), powersupply
error (blinking orange), inconsistency between parametizered current and
switch position (blinking white), overheating error on level 1 (blinking red)
and level 2 (red).
Weight
96 g
PCB CTI index
175 V
Housing material
PC FR V0 halogen free
¹ Maximum consumption in the worst-case scenario (KNX Fan-In model).
3
4
5
7
8
6
1
2
1. KNX
connector
2. Programming
button
3. Test button
4. Output
channels
5. Test LED
6. Current
selector switch
7. Programming
LED
8. External
power supply

© Zennio Avance y Tecnología S.L. Edition 8 Further information www.zennio.com Page 2/2
SAFETY INSTRUCTIONSANDADDITIONAL NOTES
•Installation should only be performed by qualified professionals according to the laws and regulations applicable in each country.
•Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for the entire
KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other
accessories, in case of being installed.
•The facility must be equipped with a device that ensures the omnipolar sectioning. Installation of a 10 A mini-circuit-breaker is
recommended. To prevent accidents, it must remain open in case of manipulation of the device.
•Once the device is installed (in the panel or box), it must not be accessible from outside.
•Keep the device away from water (condensation over the device included) and do not cover it with clothes, paper or any other material
while in use.
•The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at
https://www.zennio.com/en/legal/weee-regulation.
OUTPUTS SPECIFICATIONS AND CONNECTIONS
CONCEPT
DESCRIPTION
Number of outputs
4
Output type
Solid state switching device
Maximum load per output
1000 mA
Output currents
220 mA, 300 mA, 350 mA, 500 mA, 550 mA, 630 mA, 700 mA, 750 mA,
900 mA or 1000 mA.
Load type
Constant Current LED load
Short-circuit protection
YES
Overload protection
NO
Overheating protection
YES
Connection method
Screw terminal block (0.2 Nm max.)
Cable cross-section
0.2-1.5 mm² (IEC) / 16-30 AWG (UL)
EXTERNAL POWER SUPPLY SPECIFICATIONS AND CONNECTIONS
CONCEPT
DESCRIPTION
Voltage
12-30 VDC
Current
4000 mA
Connection method
Pluggable screw terminal block (0.4 Nm max.)
Cable cross-section
0.5-2.5 mm² (IEC) / 28-12 AWG (UL)
WIRING AND ASSEMBLY DIAGRAMS
LED
Each LED load must be connected according to its positive and the negative terminals. Respect always
the maximum current allowed by the loads.
Correspondence
1
: Red
2
: Green
3
: Blue
4
: White
+:
Positive terminal
-:
Negative terminal
External power supply:
+ and - terminals of external power supply (
constant
voltage) from 12 to 30 VDC.
It is recommended to use the closest external power
supply value to the load working voltage.
Assembly:
Screw mounting, 2 holes of
3.5 mm diameter. Screws not
included.
SEVERAL LOADS CONNECTED TO THE SAME OUTPUT
Power restriction: It is mandatory to fulfil the next restriction
regarding the power connected to one output channel:
OUTPUT CURRENT SELECTOR SWITCH
*it is mandatory that the output current chosen by ETS
parameter and the current selected with the switchmatch. On
the contrary, the load cannot be controlled and the test LED will
blink in white.
TEST LED ERROR IDENTIFICATION
Depending on the color, the test LED indicates different errors:
Color
Error
Blinking white
Output current selection
Blinking orange
No auxiliary power supply detected
Continuous orange
Wrong auxiliary power supply polarization
Blinking red
Overheating level 1
Continuous red
Overheating level 2
Right load wiring
✓
Wrong load wiring
Important warning: the following rules when not
considered may result in load or device irreversible
damages