ABB Eagle User manual

• Maximumprotection
• Maximumuptime
• Maximumpeaceofmind
Self-Powered Single Phase Recloser
for up to 27kV
—
Eagle

—
Maximizing Reliability
with a Safe, Reliable,
and Simple Solution

—
Table of contents
004 Eagle Overview
005–006 Interface
007 No Arcing Design
008 Battery-Free Operation
009 Hassle-Free and Secure Wi-Fi
Communication
010 Mounting
011 Technical Specifications
012–013 Dimensions
014–015 Software Features
016 Ordering Guide
017 Accessories
018 Service & Support

4EAGLE SELF-POWERED SINGLE PHASE RECLOSER
—
Eagle Overview
Self-Powered Single Phase Recloser
for up to 27kV
Fused overhead distribution
lateral protection
Utilities generally deploy fuse-blowing or fuse-
saving protection techniques for lateral circuit
protection. Fuse based lateral circuit protection
has major drawbacks in terms of the outages
experienced by customers for transient faults.
Since majority of the faults on overhead
distribution circuits are transient, the outages,
service calls, dispatching crews, and replacement
of fuses all add up to be very expensive in time
and money. Additionally, these outages
contribute significantly to SAIFI (system average
interruption frequency index) and MAIFI
(Momentary Average Interruption Frequency
Index) reliability indices.
Superior overhead distribution
lateral protection using Eagle
ABB’s Eagle is a single phase self-powered
vacuum interrupting recloser. It can be mounted
directly to the pole as a new installation or a
replacement to oil filled single-phase reclosers. It
can be installed separately on single phase
laterals or in a group of three for a three-phase
lateral circuit.
Eagle recloser drastically improves the reliability
indices for utilities simply by eliminating the
sustained interruptions experienced by the
customers due to fuse-blowing schemes and
momentary interruptions due to fuse-saving
schemes. By reducing the number of truck rolls,
the utility can save on operational costs and at
the same time avoid revenue losses due to
outages.
Eagle provides highest interrupting rating among
its class with higher BIL (basic insulation level)
and continuous current rating providing
application from major three-phase feeder
laterals to the end-of-line single phase laterals.
Ratings
• 15/27 kV
• 125 kV BIL
• 200A continuous current
• 8 kA Interrupting
• 3 reclosing shots
• 10,000 operations
Highlights
• Self-Powered
• No Battery – No Maintenance
• Interruption in Vacuum
• “No arcing” design
• Integrated Electronics
• Encrypted Wireless Communication
• Double Insulator Mounting
• Platform independent user interface

5LA PROTEZIONE DELLE PERSONE AL PRIMO POSTO
—
Interface
Intuitive and Easy to Use Interface
Upper Contact (H1)
Lower Contact (H2)
Aux Power (12VDC)
Vent
Connection/
Disconnection Ring
Operating Handle
(Open/Close/Reset Lockout)
Embedded Vacuum Interrupter
Non-Reclose/HLT Handle
& Wi-Fi Activation
Operations Counter
Recloser Position
Indicator
Light Sensor for
Wi-Fi Activation
(option to enable
via NR handle)
Lockout Beacon (LED)
up to 12hrs after Lockout

6EAGLE SELF-POWERED SINGLE PHASE RECLOSER
—
Interface
Intuitive and Easy to Use Interface
Status Indication
The Eagle has a conventional and reliable status
indicator semaphore which is directly linked to
the vacuum interrupter. The alternating material
color bands make the indicator cup highly visible
during the daytime as well as during the night.
Current Sensing
The Eagle uses a Rogowski coil CT for sensing the
load and fault currents. This provides a highly
accurate measurement for protection as well as
load profiling. Since it is not a conventional CT,
saturation is not a concern at the highest fault
current levels.
Mount Latching Mechanism
The Eagle has a latching mechanism on the H1
terminal that latches to the mounting clip. The
fuse clip and the latch ensure that the Eagle does
not drop open unless it is engaged at the H1
terminal ring.
An LED is provided for Lockout indication. Once
the recloser goes to lockout state, the LED flashes
periodically giving easily identifiable signal to the
utility crew investigating the fault.

7
—
No Arcing Design
Easy to Use and Safe to Operate
The Eagle is designed such that there is no arcing during installation, closing, or
opening. The opening occurs in vacuum interrupter prior to disconnection and
closing happens in vacuum interrupter after connection.
CLOSE VI
CLOSE VI
New Installation in 4 steps
Reclosing after Lockout in 3 steps
Manual Opening with Visual Break in 3 steps
1. Prepare
1. Open
1. Fix Fault
3. Connect
3. Visual Break
3. Close
2. Hang
2. Disconnect
2. Reset
4. Close
RESET LOCKOUT

8EAGLE SELF-POWERED SINGLE PHASE RECLOSER
—
Battery-Free Operation
Mechanical Closing Operation without
Relying on Batteries
For recloser designs that rely on batteries, the
batteries can lose power and render the recloser
ineffectual in closing back in the circuit after an
extended lockout period. With degrading battery
performance over a few years, the guaranteed
maintenance and operational inefficiency
inspired a completely battery-free design on the
ABB Eagle. The recloser consists of a mechanical
closing mechanism, which can be utilized to
manually close the recloser using the main
operating handle.
Battery-Free Manual Mechanical Closing
Eliminates:
Battery performance and replacement concerns
Costly battery replacement programs
Stocking, shelf-life and inventory of batteries
Additional battery charging kits
Special hot stick tools and hardware
Battery replacement training for linemen
Taking down the unit to close when battery fails
CLOSE VI

9SOLUZIONI PASSIVE, ATTIVE E PREVENTIVE
—
Hassle-Free and Secure Wi-Fi
Communication
Eagle uses a platform independent web-based
interface that allows secure communication with
Eagle over WI-Fi without the need for
• Recloser attachments
• Specialized hot stick tools
• USB dongles or transceivers
• Software installation
• Driver installation
• IT department clearances or administrator
rights
• Specialized training
Eagle provides communication options that allow
from simple to highly sophisticated device access
steps to meet utility specific guidelines without
compromising security
• 128-Bit encryption with WPA2 level security
• System level cyber security implementation
• Security logs with accurate timestamp
Wi-Fi network access options
• Always keeping Wi-Fi network ON
• Auto-disable Wi-Fi after 15 minutes of inactivity
(configurable time)
• Re-activation of Wi-Fi using light pulses (no hot
stick required) OR
• Re-activation of Wi-Fi using non-reclose handle
(hot stick operation)
• Hiding the SSID – hidden network connection
• 50ft range in direct line of sight
Web-HMI access options
• Role based user access – password for each role
• Varying access to settings per user role
• Automatic logout after 15 minutes of inactivity

10 EAGLE SELF-POWERED SINGLE PHASE RECLOSER
—
Mounting
Easy Replacement of Existing Equipment
Pole Mounted Hydraulic Recloser Replacement
Easily replace an existing hydraulic single phase
recloser by using a standard double insulator
mount with varying mount spacing
configurations.
Mounting Variations
Three reclosers – one for each phase, can be
mounted on the same pole for a three-phase
configuration.
Crossarm Mounted Fuse Cutout Replacement
Easily replace an existing fuse cutout by using a
20° double insulator mount or simply add the ABB
Eagle in parallel to the existing cutout (with the
fuse tube removed).
DIMENSION “A” REPLACEABLE COOPER RECLOSERS
12” TypeE,4E,V4E,4H,V4H,L,V4L
11.25” Type D
23.25” Type DV
AA
Double Insulator with 11.25”
and 12” Mount Spacing
Double Insulator with
23.25” Mount Spacing
Double Insulator with 20°
Crossarm Mount3-Phase Configuration

11
SOLUZIONI PASSIVE, ATTIVE E PREVENTIVE
—
Technical Specifications
Technical Specifications for Hardware
Nominal Operating Voltage 15/27kV
Rated Max. Voltage 27kV
Rated Power Frequency 60Hz
Rated Continuous Current 200A
Rated Symmetrical Interrupting Current 8kA
Rated Short-Time Withstand Current 8kA
Rated Short-Time Withstand Duration 0.5s
Rated Peak-Withstand Current 20.8kA
Rated BIL 125kV
RatedPowerFrequencyWetWithstand(60s) 60kV
CreepDistanceH1toH2 668mm
Recloser Unit Weight 20KG(44Lbs)
Auxiliary Power 12VDC(forprogramming)
Operating Temperature -40Cto+60C
Rated Number of Operations 10,000Operations
Ingress Protection IP65
Standards Compliance IEEEC37.60/IEC62271-111
Technical Specifications for Electronics & Software
Modes of Operation Autorecloser
Sectionalizer
Breaker/Switch
Rated operating duty MinO0.2sCO2sCO2sCOLockout
MaxO5sCO5sCO20sCOLockout
Minimum Pickup Fault Current 10A
Minimum current for Wi-Fi communication 5A(1)
Minimum Power-Up Time 25ms
Protection Functions 50/51P(3)
Other Functions 2nd Harmonic Inrush Restraint
Cold Load Pickup
Non-Reclose/Hot Line Tag
Switch On To Fault
Current Sensor Accuracy >50A:±1%
>20A:±2.5%
>10A:±5%
<10A:±1.6A
Operating Curves ANSI/IEC, Recloser, Fuse and Custom Curves
Records EventsandFaultRecords(1000)
InternalDeviceEvents(100)
DisturbanceRecords(250)
LoadProfile(60days)
SecurityLog(1000)
Communication Wi-FiwithWPA2128Bit-Encryption
Auto Disable Feature
Hide SSID Feature
—
(1) Tripping/Reclosing capability is not dependent of availability of certain minimum pre-fault current.
Minimum current noted is for connecting to the unit wirelessly.

12 EAGLE SELF-POWERED SINGLE PHASE RECLOSER
—
Dimensions
Eagle Recloser Dimensions
26.0
660
14.9
378
1.50
38.1
100°
19.3
490.9
9.7
245
H1 Terminal
AUX Power
H2 Terminal
Mechanical
position
indicator
Operation
counter
Flashing LED
lockout indicator
HCEP
Embedded
vacuum
interrupter
Mechanically
operated
OPEN/CLOSE
handle

13
Mounting Bracket Dimensions
Overall Dimensions when Installed
Straight Mount Double Insulator 12” Spacing
(11.25” and 23.25” spacing also available)
20 Leaning Crossarm Mount
Double Insulator
6.00
4.00
12.50
3.63
20.0°
11.88
19.29
9.39
11.85
16.14
6.56
4.25
21.072
92.2
535.24
166.75
108.08
317.5
300.9
152.40
101.60
301.8
489.9
238.6
410.0
11.25
11.85
300.9
11.88
9.39
16.14
25.58
12.50
301.8
489.9
19.29
238.6
285.8
410.0
649.8
317.5
95.0
3.74
676.8
782.9
30.82
649.8
25.58
285.8
11.25
238.6
9.39
92.2
3.63
301.8
11.88
26.65
727.7
28.65
863.9
34.01
166.75
108.08
6.56
4.29
535.2
21.07
667.3
26.27
754.4
29.70
410.0
16.14
907.5
35.73
489.9
19.29

14 EAGLE SELF-POWERED SINGLE PHASE RECLOSER
—
Software Features
Feature Description
Current Protection Functions Threeselectabledelayedcurves(50/51P)withtimedial,timedelay,andblocking
– ANSI/IEEE curves and Definite Time
– Recloser Curves (Electronic and Hydraulic)
– Fuse Curves
– Custom Curves
Cold Load and Inrush Blocking ColdLoadPickupandInrushInhibit(2ndHarmonic)featureavailableforeachcurve
Convenient Dashboard View – Bird’s eye view on device status
– Carry out operations right from the dashboard
– Single Line Diagram with recloser status
– Compatible with all web browsers on all platforms including hand-held devices
Self-Supervision Operation counter, diagnostics and wear monitoring alarms
Security Log Record of logins, changes, and unauthorized access attempts
Role Based Access Permissions based on user roles
(1)Viewer–Logonandviewstatus
(2)Operator–Operatetheunit
(3)Engineer–Settingchanges
(4)Administrator–AccessManagement
Firmware Upgrade Simple and secure firmware upgrade over Wi-Fi
Simple, platform-independent, web browser based intuitive interface

15
Modes of Operation
Eagle can be configured to operate as a simple
single-phase breaker, sectionalizer or a recloser. A
single configuration can be used in multiple
applications at various levels of a feeder.
Cold Load Pickup and 2nd Harmonic Inrush
Restraint
Depending on the protection philosophy, a
simpler cold load pickup can be set up or a more
sophisticated 2nd harmonic inrush blocking can be
configured to avoid nuisance tripping from load
picking up after a sustained outage.
Adaptive Non-Reclose and Hot Line Tag Modes
Toggling the “non-reclose” handle triggers the
recloser into non-reclose / hot ling tag mode. By
default, Eagle enters the non-reclose mode when
the NR handle is engaged. It uses the fastest
available tripping curve to trip and then stops
auto-reclosing. Alternatively, if hot line tag
settings are enabled, the recloser enters hot line
tag mode when the NR handle is engaged. The
protection can be made more sensitive using the
pickup and time multiplier settings. The NR
handle is clearly visible from ground level when
engaged.
Breaker
Cold Load Pickup
2nd Harmonic Inrush Blocking Non-Reclose Mode Hot Line Tag Mode
Non-Reclose Mode Non-Reclose Mode
NR Handle
XHLT = 1.0
tHLT = 1.0
XHLT < 1.0
tHLT < 1.0
Recloser Sectionalizer

16 EAGLE SELF-POWERED SINGLE PHASE RECLOSER
—
Ordering Guide
EGL Product Name
EGL - Eagle Single Phase Recloser
1
Ratings
•1 - 15kV - 200A -125kV BIL-8kA IR
•2 - 27kV- 200A -125kV BIL-8kA IR
•N - No HV Unit
A
ANSI/IEC
•A -ANSI(Green=Open,Red=Closed)
•E -IEC(Green=Closed,Red=Open)
•N - No HV Unit
D20
Mounting Frame
•D10 - Double Insulator 11.25" Mount
•D20 - Double Insulator 12" Mount
•D30 - Double Insulator 23.25" Mount
•C02 - Double Insulator Crossarm Mount 20 Deg
•NNN - No Mounting Frame
A
Arrester Bracket
•A - Arrester Bracket Provided
•N - No Arrest er Bracket
E
Animal Guards
•E -AnimalGuardforEagleMount+Arrester
•M -AnimalGuardforEagleMountOnly
•A -AnimalGuardforArresterOnly
•N -NoAnimalGuards
A
Aux Power
•A - 12VDC Aux Power Adapter (1 per 10)
•Z -12VDC Aux Power Adapter (Custom Qty)
•N - No Aux Power Adapter
Note: Not all combinat ions are valid. Please consult an ABB Sales Representative for details and part number validity.
EGL 1 A D20 A E A

17
—
Accessories
AnimalGuardsforEagle Disconnect & Bypass Switch

18 EAGLE SELF-POWERED SINGLE PHASE RECLOSER
—
Service & Support
Product Warranty
3-year warranty on the recloser
Training
For factory-based training, please contact ABB
customer service
On-site training, commissioning assistance, and
migration training
On-site training sessions are offered upon
request and can be arranged at the customer
facility. Arrangements may be made by
contacting ABB in Lake Mary, Florida.
ABB can provide commissioning assistance
during installation, including migration support
for the development of settings.

19

1YEPTSS0020E003-REV.A - 01.2021 #(gs)
—
The information contained in this
document is for general information
purposes only. While ABB strives to keep
the information up to date and correct,
it makes no representations or
warranties of any kind, express or
implied, about the completeness,
accuracy, reliability, suitability or
availability with respect to the
information, products, services, or
related graphics contained in the
document for any purpose. Any reliance
placed on such information is therefore
strictly at your own risk. ABB reserves
the right to discontinue any product or
service at any time.
—
Contact Us
ABB Inc.
680 Century Point ,
Lake Mary FL 32746
Phone: +1 407 732 2000
Customer service: +1 800 929 7947 ext. 5
+1 407 732 2000 ext. 2510
E-Mail: customer.ser[email protected]om
www.abb.com/mediumvoltage
Other manuals for Eagle
2
Table of contents
Other ABB Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

SINTERIT
SINTERIT SANDBLASTER SLS Original manual

Oval
Oval EL0137 instructions

Halma
Halma Ocean Optics HL-2000-FHSA Installation and operation manual

Endura
Endura FasTrack instruction manual

SCHUNK
SCHUNK VERO-S NSE3 138 Assembly and operating manual

Global
Global WF 1767-70 Series Instruction & parts manual