ABB Relion 615 series User manual

Relion® 615 series
Voltage Protection and Control
REU615
IEC 60870-5-103 Point List Manual


Document ID: 1MRS757055
Issued: 2013-02-21
Revision: C
Product version: 4.0 FP1
© Copyright 2013 ABB. All rights reserved

Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license
and may be used, copied, or disclosed only in accordance with the terms of such
license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
http://www.abb.com/substationautomation

Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.

Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.

Table of contents
Section 1 Introduction.......................................................................5
This manual........................................................................................5
Intended audience..............................................................................5
Product documentation.......................................................................5
Product documentation set............................................................5
Document revision history.............................................................6
Related documentation..................................................................6
Symbols and conventions...................................................................7
Symbols.........................................................................................7
Document conventions..................................................................7
Functions, codes and symbols......................................................8
Section 2 IEC 60870-5-103 data mappings...................................11
Overview...........................................................................................11
Supported functions..........................................................................11
Indications and controls....................................................................13
General Data(FUN=0) IEC 60870-5-103 standard......................13
General Data(FUN=10) - 615-specific.........................................14
LD0.MVGAPC1 Multipurpose binary inputs (1)...........................15
LD0.MVGAPC2 Multipurpose binary inputs (2)...........................15
LD0.SRGAPC1 Multipurpose binary outputs - flip-flop
resets (1).....................................................................................15
LD0.SRGAPC2 Multipurpose binary outputs - flip-flop
resets (2).....................................................................................16
LD0.SPCGGIO1 Multipurpose binary outputs (1)........................16
LD0.SPCGGIO2 Multipurpose binary outputs (2)........................17
LD0.SEQRFUF1 Fuse failure protection.....................................17
CTRL.CCRDIF1 Current circuit failure protection........................18
LD0.TPOSSLTC1 Tap position...................................................18
LD0.SECRSYN1 Synchrocheck indications ...............................18
LD0.FRPFRQ1 Frequency protection (1)....................................18
LD0.FRPFRQ2 Frequency protection (2)....................................19
LD0.FRPFRQ3 Frequency protection (3)....................................19
LD0.FRPFRQ4 Frequency protection (4)....................................19
LD0.FRPFRQ5 Frequency protection (5)....................................20
LD0.FRPFRQ6 Frequency protection (6)....................................20
LD0.MAPGAPC1 Multipurpose analog protection function
(1)................................................................................................20
LD0.MAPGAPC2 Multipurpose analog protection function
(2)................................................................................................21
Table of contents
REU615 1
Point List Manual

LD0.MAPGAPC3 Multipurpose analog protection function
(3)................................................................................................21
LD0.MAPGAPC4 Multipurpose analog protection function
(4)................................................................................................21
LD0.MAPGAPC5 Multipurpose analog protection function
(5)................................................................................................21
LD0.MAPGAPC6 Multipurpose analog protection function
(6)................................................................................................22
LD0.XRGGIO130 Alarm and warning..........................................22
LD0.PHPTOV3 Phase overvoltage protection - stage 3..............22
LD0.PHPTOV2 Phase overvoltage protection - stage 2..............22
LD0.PHPTOV1 Phase overvoltage protection - stage 1..............23
LD0.PHPTUV3 Phase undervoltage protection - stage 3............23
LD0.PHPTUV2 Phase undervoltage protection - stage 2............23
LD0.PHPTUV1 Phase undervoltage protection - stage 1............24
LD0.PSPTUV2 Positive-sequence undervoltage protection
- stage 2.......................................................................................24
LD0.PSPTUV1 Positive-sequence undervoltage protection
- stage 1.......................................................................................24
LD0.NSPTOV2 Negative-sequence overvoltage protection
- stage 2.......................................................................................24
LD0.NSPTOV1 Negative-sequence overvoltage protection
- stage 1.......................................................................................25
LD0.ROVPTOV1 Residual overvoltage protection - stage 1.......25
LD0.ROVPTOV2 Residual overvoltage protection - stage 2.......25
LD0.ROVPTOV3 Residual overvoltage protection - stage 3.......25
LD0.XGGIO130 Physical binary I/O signals (status only)...........26
LD0.XGGIO120 Physical binary I/O signals (status only)...........26
LD0.XGGIO110 Physical binary I/O signals (status only)...........26
LD0.XGGIO100 Physical binary I/O signals (status only)...........27
LD0.OLATCC1 On-load tap changer controller...........................27
LD0.LSHDPFRQ1 Load shedding - instance 1...........................28
LD0.LSHDPFRQ2 Load shedding - instance 2...........................28
LD0.LSHDPFRQ3 Load shedding - instance 3...........................28
LD0.LSHDPFRQ4 Load shedding - instance 4...........................29
LD0.LSHDPFRQ5 Load shedding - instance 5...........................29
LD0.ARCSARC1 Fault arc protection - stage 1...........................29
LD0.ARCSARC2 Fault arc protection - stage 2...........................30
LD0.ARCSARC3 Fault arc protection - stage 3...........................30
LD0.PHIPTOC1 Phase overcurrent protection -
instantaneous stage 1 ................................................................30
LD0.PHHPTOC1 Phase overcurrent protection - high stage
1...................................................................................................30
LD0.PHLPTOC1 Phase overcurrent protection - low stage
1...................................................................................................31
Table of contents
2REU615
Point List Manual

LD0.T2PTTR1 Thermal overload protection (2)..........................31
LD0.CMMXU1 Phase currents (1) limit supervision....................31
LD0.VMMXU1 Phase voltage (1) limit supervision......................32
LD0.RESVMMXU1 Residual voltage (1) limit supervision...........32
CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure
protection.....................................................................................32
CTRL.DCXSWI1 Disconnector (1) - controllable object..............33
CTRL.DCXSWI2 Disconnector (2) - controllable object..............33
CTRL.ESXSWI1 Earth switch - controllable object.....................33
CTRL.DCSXSWI1 Disconnector (1) - non-controllable
object...........................................................................................34
CTRL.DCSXSWI2 Disconnector (2) - non-controllable
object...........................................................................................34
CTRL.DCSXSWI3 Disconnector (3) - non-controllable
object...........................................................................................34
CTRL.ESSXSWI1 Earth switch (1) - non-controllable
object...........................................................................................34
CTRL.ESSXSWI2 Earth switch (2) - non-controllable
object...........................................................................................34
LD0.LEDGGIO1 LHMI LED indications Type 1 (2 states)...........35
LD0.LEDGGIO1 LHMI LED indications Type 2 (3 states)...........35
Class 2 data measurands.................................................................35
Class 2 private measurand data (6 and 7)..................................37
Section 3 Interoperability profile for 615 series IEC
60870-5-103...................................................................39
Physical layer...................................................................................39
Electrical interface.......................................................................39
Optical interface...........................................................................39
Transmission speed....................................................................39
Link layer..........................................................................................39
Application layer...............................................................................40
Transmission mode for application data......................................40
COMMON ADDRESS of ASDU..................................................40
Selection of standard information numbers in monitor
direction.......................................................................................40
System functions in monitor directions...................................40
Status indications in monitor direction....................................40
Supervision indications in monitor direction...........................41
Earth fault indications in monitor direction..............................41
Fault indications in monitor direction......................................41
Auto-reclosure indications in monitor direction.......................42
Measurands in monitor direction............................................43
Generic functions in monitor direction....................................43
Table of contents
REU615 3
Point List Manual

Selection of standard information numbers in control
direction.......................................................................................43
System functions in control direction......................................43
Generic functions in monitor direction....................................43
Basic application functions..........................................................44
Miscellaneous..............................................................................44
Section 4 Glossary.........................................................................45
Table of contents
4REU615
Point List Manual

Section 1 Introduction
1.1 This manual
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
1.2 Intended audience
This manual addresses the communication system engineer or system integrator
responsible for pre-engineering and engineering for communication setup in a
substation from an IED perspective.
The system engineer or system integrator must have a basic knowledge of
communication in protection and control systems and thorough knowledge of the
specific communication protocol.
1.3 Product documentation
1.3.1 Product documentation set
The application manual contains application descriptions and setting guidelines
sorted per function. The manual can be used to find out when and for what purpose
a typical protection function can be used. The manual can also be used when
calculating settings.
The communication protocol manual describes a communication protocol
supported by the IED. The manual concentrates on vendor-specific implementations.
The engineering guide provides information for IEC 61850 engineering of the
protection IEDs with PCM600 and IET600. This guide concentrates especially on
the configuration of GOOSE communication with these tools. The guide can be
used as a technical reference during the engineering phase, installation and
commissioning phase, and during normal service. For more details on tool usage,
see the PCM600 documentation.
The engineering manual contains instructions on how to engineer the IEDs using
the different tools in PCM600. The manual provides instructions on how to set up a
PCM600 project and insert IEDs to the project structure. The manual also
1MRS757055 C Section 1
Introduction
REU615 5
Point List Manual

recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 61850 and other
supported protocols.
The installation manual contains instructions on how to install the IED. The
manual provides procedures for mechanical and electrical installation. The chapters
are organized in chronological order in which the IED should be installed.
The operation manual contains instructions on how to operate the IED once it has
been commissioned. The manual provides instructions for monitoring, controlling
and setting the IED. The manual also describes how to identify disturbances and
how to view calculated and measured power grid data to determine the cause of a
fault.
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.
1.3.2 Document revision history
Document revision/date Product version History
A/2010-06-11 3.0 First release
B/2012-05-11 4.0 Content updated to correspond to the
product version
C/2013-02-21 4.0 FP1 Content updated to correspond to the
product series version
Download the latest documents from the ABB Website
http://www.abb.com/substationautomation.
1.3.3 Related documentation
Name of the document Document ID
IEC 60870-5-103 Communication Protocol Manual 1MRS756710
Section 1 1MRS757055 C
Introduction
6REU615
Point List Manual

1.4 Symbols and conventions
1.4.1 Symbols
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence
of a hazard which could result in corruption of software or damage
to equipment or property.
The information icon alerts the reader of important facts and
conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to
understand that under certain operational conditions, operation of damaged
equipment may result in degraded process performance leading to personal injury
or death. Therefore, comply fully with all warning and caution notices.
1.4.2 Document conventions
A particular convention may not be used in this manual.
• Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
• Push-button navigation in the LHMI menu structure is presented by using the
push-button icons.
To navigate between the options, use and .
• HMI menu paths are presented in bold.
Select Main menu/Settings.
• LHMI messages are shown in Courier font.
To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks.
The corresponding parameter values are "On" and "Off".
• IED input/output messages and monitored data names are shown in Courier font.
When the function starts, the START output is set to TRUE.
1MRS757055 C Section 1
Introduction
REU615 7
Point List Manual

1.4.3 Functions, codes and symbols
Table 1: REU615 functions, codes and symbols
Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent
protection, low stage PHLPTOC1 3I> (1) 51P-1 (1)
Three-phase non-directional overcurrent
protection, high stage PHHPTOC1 3I>> (1) 51P-2 (1)
Three-phase non-directional overcurrent
protection, instantaneous stage PHIPTOC1 3I>>> (1) 50P/51P (1)
Residual overvoltage protection ROVPTOV1 Uo> (1) 59G (1)
ROVPTOV2 Uo> (2) 59G (2)
ROVPTOV3 Uo> (3) 59G (3)
Three-phase undervoltage protection PHPTUV1 3U< (1) 27 (1)
PHPTUV2 3U< (2) 27 (2)
PHPTUV3 3U< (3) 27 (3)
Three-phase overvoltage protection PHPTOV1 3U> (1) 59 (1)
PHPTOV2 3U> (2) 59 (2)
PHPTOV3 3U> (3) 59 (3)
Positive-sequence undervoltage protection PSPTUV1 U1< (1) 47U+ (1)
PSPTUV2 U1< (2) 47U+ (2)
Negative-sequence overvoltage protection NSPTOV1 U2> (1) 47O- (1)
NSPTOV2 U2> (2) 47O- (2)
Frequency protection FRPFRQ1 f>/f<,df/dt (1) 81 (1)
FRPFRQ2 f>/f<,df/dt (2) 81 (2)
FRPFRQ3 f>/f<,df/dt (3) 81 (3)
FRPFRQ4 f>/f<,df/dt (4) 81 (4)
FRPFRQ5 f>/f<,df/dt (5) 81 (5)
FRPFRQ6 f>/f<,df/dt (6) 81 (6)
Three-phase thermal overload protection for
power transformers, two time constants T2PTTR1 3Ith>T 49T
Master trip TRPPTRC1 Master Trip (1) 94/86 (1)
TRPPTRC2 Master Trip (2) 94/86 (2)
Arc protection ARCSARC1 ARC (1) 50L/50NL (1)
ARCSARC2 ARC (2) 50L/50NL (2)
ARCSARC3 ARC (3) 50L/50NL (3)
Table continues on next page
Section 1 1MRS757055 C
Introduction
8REU615
Point List Manual

Function IEC 61850 IEC 60617 IEC-ANSI
Multi-purpose protection MAPGAPC1 MAP (1) MAP (1)
MAPGAPC2 MAP (2) MAP (2)
MAPGAPC3 MAP (3) MAP (3)
MAPGAPC4 MAP (4) MAP (4)
MAPGAPC5 MAP (5) MAP (5)
MAPGAPC6 MAP (6) MAP (6)
Load shedding and restoration LSHDPFRQ1 UFLS/R (1) 81LSH (1)
LSHDPFRQ2 UFLS/R (2) 81LSH (2)
LSHDPFRQ3 UFLS/R (3) 81LSH (3)
LSHDPFRQ4 UFLS/R (4) 81LSH (4)
LSHDPFRQ5 UFLS/R (5) 81LSH (5)
Control
Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
Disconnector control DCXSWI1 I <-> O DCC (1) I <-> O DCC (1)
DCXSWI2 I <-> O DCC (2) I <-> O DCC (2)
Earthing switch control ESXSWI1 I <-> O ESC I <-> O ESC
Disconnector position indication DCSXSWI1 I <-> O DC (1) I <-> O DC (1)
DCSXSWI2 I <-> O DC (2) I <-> O DC (2)
DCSXSWI3 I <-> O DC (3) I <-> O DC (3)
Earthing switch indication ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
ESSXSWI2 I <-> O ES (2) I <-> O ES (2)
Tap changer position indication TPOSSLTC1 TPOSM 84M
Tap changer control with voltage regulator OLATCC1 COLTC 90V
Synchronism and energizing check SECRSYN1 SYNC 25
Condition monitoring
Trip circuit supervision TCSSCBR1 TCS (1) TCM (1)
TCSSCBR2 TCS (2) TCM (2)
Current circuit supervision CCRDIF1 MCS 3I MCS 3I
Fuse failure supervision SEQRFUF1 FUSEF 60
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement CMMXU1 3I 3I
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Three-phase voltage measurement VMMXU1 3U 3U
Residual voltage measurement RESVMMXU1 Uo Vn
Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0
Three-phase power and energy measurement PEMMXU1 P, E P, E
RTD/mA measurement XRGGIO130 X130 (RTD) X130 (RTD)
Frequency measurement FMMXU1 f f
1MRS757055 C Section 1
Introduction
REU615 9
Point List Manual

10

Section 2 IEC 60870-5-103 data mappings
2.1 Overview
This document describes the IEC 60870-5-103 data points and structures available
in the IED. The point lists describe a superset of all data available through the
standard configuration/s. The tables show the default point definitions. All these
data can be freely remapped in which case PCM600 can provide an updated point
list export of the new outlook.
2.2 Supported functions
Table 2: Supported functions in REU615
Function block UE01 UE02
PHLPTOC1 ●
PHHPTOC1 ●
PHIPTOC1 ●
ROVPTOV1 ●
ROVPTOV2 ●
ROVPTOV3 ●
PHPTUV1 ● ●
PHPTUV2 ● ●
PHPTUV3 ● ●
PHPTOV1 ● ●
PHPTOV2 ● ●
PHPTOV3 ● ●
PSPTUV1 ●
PSPTUV2 ●
NSPTOV1 ●
NSPTOV2 ●
FRPFRQ1 ●
FRPFRQ2 ●
FRPFRQ3 ●
FRPFRQ4 ●
FRPFRQ5 ●
FRPFRQ6 ●
Table continues on next page
1MRS757055 C Section 2
IEC 60870-5-103 data mappings
REU615 11
Point List Manual

Function block UE01 UE02
T2PTTR1 ●
TRPPTRC1 ● ●
TRPPTRC2 ● ●
ARCSARC1 o
ARCSARC2 o
ARCSARC3 o
MAPGAPC1 o
MAPGAPC2 o
MAPGAPC3 o
MAPGAPC4 o
MAPGAPC5 o
MAPGAPC6 o
LSHDPFRQ1 ●
LSHDPFRQ2 ●
LSHDPFRQ3 ●
LSHDPFRQ4 ●
LSHDPFRQ5 ●
CBXCBR1 ● ●
DCXSWI1 ● ●
DCXSWI2 ● ●
ESXSWI1 ● ●
DCSXSWI1 ● ●
DCSXSWI2 ● ●
DCSXSWI3 ● ●
ESSXSWI1 ● ●
ESSXSWI2 ● ●
TPOSSLTC1 ●
OLATCC1 ●
SECRSYN1 ●
TCSSCBR1 ● ●
TCSSCBR2 ● ●
CCRDIF1 ●
SEQRFUF1 ●
RDRE1 ● ●
CMMXU1 ●
CSMSQI1 ●
VMMXU1 ● ●
RESVMMXU1 ●
VSMSQI1 ● ●
Table continues on next page
Section 2 1MRS757055 C
IEC 60870-5-103 data mappings
12 REU615
Point List Manual

Function block UE01 UE02
PEMMXU1 ●
XRGGIO130 o
FMMXU1 ●
● = available in the device variant, o = optionally available in the device variant
2.3 Indications and controls
Table 3: Explanations of the indications and controls table columns
Column name Description
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name The signal may have a defined label that is visible, for example, in ACT.
Description Short description of the signal. See the application function block documentation
for more details.
DPI value IEC 60870-5-103 indication and control values are coded as two-bit values (= DPI).
10 = ON, 01 = OFF
FUN and INF Default function type and information number definition for the signal. Can be
modified via PCM600.
U Signal in use or not as default.
1 = In use, 0 = Not in use
Can be configured via PCM600.
ASDU ASDU type of the signal as default. ASDU type of indications can be modified via
PCM600. ASDU 1 and 2 are indications. ASDU 20 is control.
I General interrogation (GI) setting as default.
1 = In GI, 0 = Not in GI
Can be modified via PCM600.
C Extended DPI coding.
1 = Regular OFF/ON (01/10) values
2 = Four-pole INTERMEDIATE/OFF/ON/ERROR values (00/01/10/11)
2.3.1 General Data(FUN=0) IEC 60870-5-103 standard
Table 4: General Data(FUN=0) IEC 60870-5-103 standard
IEC 61850 name SA name Description DPI value FUN INF U ASDU I C
LD0.LNN0
.LEDRs1.ctlVal - LED reset 10=Reset 0 19 1 20 0 1
.Beh.stVal.(Test) - Test mode 10=On 0 21 1 1 1 1
LD0.I3CGGIO1
.ActSG.ctlVal/stVal - Param setting group 1 10=SG 1 0 23 1 1,20 1 1
.ActSG.ctlVal/stVal - Param setting group 2 10=SG 2 0 24 1 1,20 1 1
.ActSG.ctlVal/stVal - Param setting group 3 10=SG 3 0 25 1 1,20 1 1
.ActSG.ctlVal/stVal - Param setting group 4 10=SG 4 0 26 1 1,20 1 1
Table continues on next page
1MRS757055 C Section 2
IEC 60870-5-103 data mappings
REU615 13
Point List Manual

IEC 61850 name SA name Description DPI value FUN INF U ASDU I C
.ActSG.ctlVal/stVal - Param setting group 5 10=SG 5 0 27 1 1,20 1 1
.ActSG.ctlVal/stVal - Param setting group 6 10=SG 6 0 28 1 1,20 1 1
LD0.TCSSCBR1
.CirAlm.stVal ALARM Trip circuit 1 alarm 10=Alarm 0 36 1 1 1 1
LD0.LEDPTRC1
.Op.general - Global operate 10=Operate 0 68 1 2 0 1
.Str.general - Global start 10=Start 0 84 1 2 1 1
2.3.2 General Data(FUN=10) - 615-specific
Table 5: General Data(FUN=10) - 615-specific
IEC 61850 name SA name Description DPI value FUN INF U ASDU I C
LD0.TRPPTRC1
.Op.general - Trip1 input 10=On 10 1 1 2 0 1
.Tr.general - Trip1 output 10=On 10 2 1 2 0 1
LD0.TRPPTRC2
.Op.general - Trip2 input 10=On 10 3 1 2 0 1
.Tr.general - Trip2 output 10=On 10 4 1 2 0 1
CTRL.LLN0
.Loc.stVal - Local/Remote state 10=Local 10 10 1 1 1 1
.LocRem.Station - Station state 10=On 10 11 1 1 1 1
LD0.LLN0
.LEDRs2.ctlVal - Reset alarm LEDs 10=Reset 10 21 1 20 0 1
.SetSeld.stVal - Param.setting reserved 10=Res 10 80 1 1 1 1
.SetChg.stVal - Param.setting changed 10=Chng 10 81 1 1 1 1
LD0.TCSSCBR2
.CirAlm.stVal ALARM Trip circuit 2 alarm 10=Alarm 10 36 1 1 1 1
DR.RDRE1
.RcdTrg.ctlVal - Trig DR recording 10=Trig 10 41 1 20 0 1
.MemClr.ctlVal - Clear DR memory 10=Clear 10 42 1 20 0 1
LD0.CMSTA1
.RecRs.ctlVal - Reset max.demands 1 10=Reset 10 45 1 20 0 1
LD0.LEDPTRC1 Global protection:
.Str.phsA - Start-phsA 10=Start 10 61 0 2 1 1
.Str.phsB - Start-phsB 10=Start 10 62 0 2 1 1
.Str.phsC - Start-phsC 10=Start 10 63 0 2 1 1
.Op.phsA - Operate-phsA 10=Operate 10 65 0 2 0 1
.Op.phsB - Operate-phsB 10=Operate 10 66 0 2 0 1
.Op.phsC - Operate-phsC 10=Operate 10 67 0 2 0 1
Section 2 1MRS757055 C
IEC 60870-5-103 data mappings
14 REU615
Point List Manual
Other manuals for Relion 615 series
41
This manual suits for next models
1
Table of contents
Other ABB Industrial Equipment manuals