manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ABB
  6. •
  7. Inverter
  8. •
  9. ABB PVI-3.8/4.6-I-OUTD User manual

ABB PVI-3.8/4.6-I-OUTD User manual

In addition to what is explained below, the safety and installation information provided in the
installation manual must be read and followed. The technical documentation and the interface
and management software for the product are available at the website.
The device must be used in the manner described in the manual. If this is not the case the
safety devices guaranteed by the inverter might be ineffective.
Quick Installation Guide
PVI-3.8/4.6-I-OUTD
ABB Solar inverters
1.
Labels and SymbolsInverter Models and Components
2.
Lifting and transport
4.
Choice of installation location
EN
Assembly Instruction
6.
List of supplied components
3.
Choice of installation location
5.
Input conguration (DC)
7.
8.
Grounding of the DC inputs
The labels on the inverter have the Agency marking, main technical data and identication of the equipment and manufacturer
V
dc max
I
dc max
V
dc MPP
V
dc, Full Power
I
sc max
V
acr
f
r
I
ac max
P
acr (cos
φ
=
±0.9)
P
acr (cos
φ
= 1)
MODEL:
PVI-3.8- I-OUTD
IP65
5minutes
520 V
90 - 520 V
2x12.5 A
160 - 470 V
2x22 A
Made in Italy
DINVVDE 0126-1-1
PROTECTIVE CLASS: I
230 V 1Ø
50 Hz
(*): 16 A for G83/1 UK Version
3800W @ 45°Camb.
3800 W @ 50°Camb.
18.2 A(*)
-25to+60 °C
-13to+140 °F
SOLAR INVERTER
www.abb.com/solar
V
dc max
I
dc max
V
dc MPP
V
dc, Full Power
I
sc max
V
acr
f
r
I
ac max
P
acr (cos
φ
=
±0.9)
P
acr (cos
φ
= 1)
MODEL:
PVI-4.6- I-OUTD
IP65
5minutes
520 V
90 - 520 V
2x14 A
180 - 470 V
2x22 A
Made in Italy
DINVVDE 0126-1-1
PROTECTIVE CLASS: I
230 V 1Ø
50 Hz
4600W @ 45°Camb.
4600 W @ 50°Camb.
22.5 A(*)
-25to+60 °C
-13to+140 °F
SOLAR INVERTER
www.abb.com/solar
The labels attached to the equipment must NOT be removed, damaged, dirtied, hidden,etc...
If the service password is requested, the eld to be used is the serial number -SN: YYWWSSSSSS-
In the manual and/or in some cases on the equipment, the danger or hazard zones are indicated with signs, labels, symbols or icons.
Always refer to instruction
manual
General warning - Important
safety information Hazardous voltage Hot surfaces
IP65
Protection rating of
equipment Temperature range
With isolation
transformer
Direct and alternating
currents, respectively
Positive pole and negative
pole of the input voltage
(DC)
Always use safety clothing
and/or personal safety
devices
Point of connection for
grounding protection
Time need to discharge
stored energy
5
01
Inverter model
02
Inverter Part Number
03
Inverter Serial Number
04
Week/Year of manufacture
PVI-X.X-I-OUTD-X
P/N:PPPPPPPPPPP
WO:XXXXXXX
SO:SXXXXXXXX Q1
SN:YYWWSSSSSS WK:WWYY
01
02
04
03
The models of inverter to which this guide refers are available in 2 power ratings: 3.8 kW and 4.6 kW.
Two types are available for each model: Standard or with DC disconnect switch (Version -S).
STANDARD VERSION - S VERSION
01
03
04
05
02
06 08
17 18 19 20
13 14 15 1609 11 1210
22 23 24 25
17 18 19 20
13 14 15 161209 1110
21 22 23 24 25
UNO
POWER ALARM GFI
ESC UP DOWN ENTER
07
Main components
01 Bracket 06 LED Panel 11 Positive Grounding Connector 16 RJ45 Connectors 21 DC Disconnect switch
02 Locking screw 07 Display 12 Grid standard rotary selectors 17 DC Input terminal block 22 Input connectors (MPPT1)
03 Heat sink 08 Keyboard 13 Channel conguration switch 18 AC Output terminal block 23 Input connectors (MPPT2)
04 Stand-by Button 09 Negative Grounding Connector 14 Internal battery 19 Alarm terminal block 24 AC cable gland
05 Front cover 10 Grounding conguration wiring 15 RS485 line termination switch 20 Signal terminal block 25 Service cable glands
Transport and handling
Transport of the equipment, especially by road, must be carried out with by suitable ways and means for protecting the
components from violent shocks, humidity, vibration, etc.
Lifting
The means used for lifting must be suitable to bear the weight of the equipment.
Unpacking and checking
The components of the packaging must be disposed on in accordance with the regulations in force in the country of
installation.
When you open the package, check that the equipment is undamaged and make sure all the components are present.
If you nd any defects or damage, stop unpacking and consult the carrier, and also promptly inform the Service ABB.
Equipment weight
Model Mass weight
PVI-3.8-I-OUTD
PVI-4.6-I-OUTD-S
PVI-4.6-I-OUTD
PVI-4.6-I-OUTD-S 24 Kg
UNO
POWER ALARM GFI
ESC UP DOWN ENTER
Environmental checks
- Consult the technical data to check the environmental parameters to be observed
- Installation of the unit in a location exposed to direct sunlight must be avoided as it may cause:
1. power limitation phenomena in the inverter (with a resulting decreased energy production by the system)
2. premature wear of the electrical/electromechanical components
3. premature wear of the mechanical components (gaskets) and of the user interface (display)
- Do not install in small closed rooms where air cannot circulate freely
- To avoid overheating, always make sure the ow of air around the inverter is not blocked
- Do not install in places where gases or ammable substances may be present
- Do not install in rooms where people live or where the prolonged presence of people or animals is
expected, because of the noise (about 50dB(A) at 1 m) that the inverter makes during operation
Installations above 2000 metres
On account of the rarefaction of the air (at high altitudes), particular conditions may occur:
- Less efcient cooling and therefore a greater likelihood of the device going into derating because of
high internal temperatures
- Reduction in the dielectric resistance of the air that, in the presence of high operating voltages (DC
input), can create electric arcs (discharges) that can reach the point of damaging the inverter
All installations at altitudes of over 2000 metres must be assessed case by case with the ABB
Service department.
Installation position
- Install on a wall or strong structure capable of bearing the weight of the equipment
- Install in safe, easy to reach places
- If possible, install at eye-level so that the display and status LEDs can be seen easily
- Install at a height that considers the heaviness of the equipment
- Install vertically with a maximum inclination of +/- 5°
- Choose a place with enough space around the unit to permit easy installation and
removal of the object from the mounting surfaces; comply with the indicated minimum
distances
- For a multiple installation, position the inverters side by side; if the space available does
not allow this arrangement, position the inverters in a staggered arrangement as shown
in the gure so that heat dissipation is not affected by other inverters
Final installation of the inverter must not compromise access to any disconnection
devices that may be located externally.
Please refer to the warranty terms and conditions available on the website and
evaluate any possible exclusion due to improper installation.
15
cm
20
cm
10cm 10cm
Wall/Pole mounting
During installation, do not place the inverter with its front facing towards the ground.
- Position the bracket
01
so that it is perfectly level on the wall and use it as a boring template.
- Make the 3 holes required, using a drill with a 10 mm diameter bit. The depth of the holes should
be about 70 mm. On the bracket
01
there are 5 holes with which to secure it: just 3 are enough to
support the inverter if installed on stable, robust supports.
- Secure the bracket to the wall
B
or to the pole
A
with the no. 3 10 mm wall plugs supplied with
it (Step 1). Check the stability of the bracket and if necessary use all the xing points (5) there are
on the bracket
- Hook the inverter to the bracket spring corresponding with the insertion point in the bracket on the
back of the inverter (Step 2).
- Proceed to anchor the inverter to the bracket
01
by tightening the locking screw
02
located on the
lower side (Step 3).
- Unscrew the 4 screws and open the front cover
05
in order to make all the necessary connections.
- Once the connections have been made, close the cover by tightening the 4 screws on the front to a
minimum tightening torque of 1.5 Nm.
A
B
UNO
POWER ALARM GFI
ESC UP DOWN ENTER
1
3
2
Available components Quantity
Bracket for wall mounting 1
Bolts and screws for wall mounting 3 + 3
M6x10 screw 1
D.18 Washer 4
L-key, TORX TX20 1
M20 Cable gland 1
M32 Cable gland 1
Two-hole gasket for M20 signal cable
glands and cap TGM58 1 + 1
Available components Quantity
Jumpers for conguration of the
parallel input channels 2
Connector for connecting the con-
gurable relay 2
Connector for the connection of the
communication and control signals 2
Male quick t connectors 4
Female quick t connectors 4
Inadditiontowhatisexplainedinthis guide, the safetyand installationinformationprovided in the installationmanualmustbe read and followed.
Thetechnicaldocumentationandtheinterfaceandmanagementsoftwarefor the productare availableat the website.
XXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXX
ABBsolarinverters
Technical documentations 1
All versions of the inverter are equipped with two input channels (therefore with double maximum power point tracker MPPT) independent of each other, which
can however be connected in parallel using a single MPPT.
Conguration of independent channels (default conguration)
This conguration involves the use of the two input channels (MPPT) in independent
mode. This means that the jumpers between the two channels (positive and negati-
ve) of the DC input terminal block
17
must not be installed and the switch
13
located
on the main board must be set to “IND”. N.B.: Independent channel conguration
can only be used in the event that the negative input pole is grounded (Negative
Grounding).
Conguration of parallel-connected channels
This conguration uses the two input channels (MPPT) connected in parallel. This
means that the jumpers between the two channels (positive and negative) of the
DC input terminal block
17
must be installed and the switch
13
located on the main
board must be set to “PAR”.
17
13
13
The conguration of the grounding of the inputs must be done before any connections or testing takes place. No pole of the array can have
earthing connection points located outside the inverter. Incorrect conguration may cause damage to the system and photovoltaic panels!
For the correct operation of some types of photovoltaic panels it may be necessary to ground one of the two input poles (positive or negative), or to have both
of the input poles oating in regards to ground potential. In order to achieve this, it is possible to vary the Grounding conguration by connecting the wiring
10
for connector
09
(negative grounding) to connector
11
(positive grounding), or inserting the wiring into the support provided (oating conguration).
Positive or oating grounding must NOT be used in the case of INDEPENDENT input channel conguration.
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
09 11
10
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
09 11
10
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
09 11
10
Negative input pole grounding Positive input pole grounding “Floating” grounding
12.
Output connection (AC)
14.
Commissioning
15.
Instruments
PVI-3.8_4.6-I-OUTD-Quick Installation Guide EN-RevB
EFFECTIVE 2014-03-13
© Copyright 2014 ABB. All Rights Reserved.
Specications subject to change without notice.
10.
Connection of the communication and control signals
11.
Line cable and protection devices
16.
Structure of the display menu
17.
Characteristics and technical data
9.
Input connection (DC)
13.
Setting the grid standard
Contact us
www.abb.com/solarinverters
LEDs and BUTTONS, in various combinations, can be used to view the status or carry out complex actions that are described more fully in the manual.
080706
LED
POWER
GREEN On if the inverter is working correctly. Flashes when
checking the grid or if there is insufcient sunlight.
ESC It is used to access the main menu, to go back to the previous menu
or to go back to the previous digit to be edited
LED
ALARM
YELLOW The inverter has detected an anomaly. The anomaly
is shown on the display.
UP It is used to scroll up the menu options or to shift the numerical scale
in ascending order
LED
GFI
RED Ground fault on the DC side of the PV generator. The
error is shown on the display.
DOWN It is used to scroll down the menu options or to shift the numerical
scale in descending order
ENTER It can be used to conrm an action, to access the submenu for the
selected option (indicated by the > symbol) or to switch to the next
digit to be edited
ABB inverters are equipped with a graphic Display
07
, consisting of 2 lines of 16 characters each, which can be used to:
- Display the operating state of the inverter and the statistical data
- Display the service messages for the operator
- Display the alarm and fault messages for the operator
- Changing the settings of the inverter
During the normal operation of the inverter the display cycles through the GENERAL INFORMATION. This information relates to the input and output parame-
ters and the inverter identication parameters. By pressing ENTER it is possible to lock scrolling on a screen to be constantly displayed.
Press ESC to access the three main menus, which have the following functions:
-STATISTICS: Displays the statistics
-SETTINGS: Modify the settings of the inverter
-INFO: View service messages for the operator
Refer to the manual for details regarding use and functions available in the menu
Check for correct polarity in the input strings and absence of any leakage to ground in the PV generator. When exposed to sunlight, the PV
panels supply DC direct voltage to the inverter. The inside of the inverter may only be accessed after the equipment has been disconnected
from the grid and from the photovoltaic generator.
For the string connections it is necessary to use the quick t connectors (multicontact or weidmüller) located on the bottom of the mechanic
22
23
.
- Crimp the Multicontact/Weidmüller MC4/WM4 quick t connector counterparts (supplied) to the string cables or to the cables wired to the DC disconnect
switches (external)
- Connect all the strings included in the design of the system and always check the tightness of the connectors
- If some of the string inputs should not be used you must proceed to verify the presence of covers on DC input connectors and then install them should they be
absent: this operation is necessary for the tightness of the inverter and to avoid damaging the free connector that could be used at a later date.
Load protection breaker (AC disconnect switch) and line cable sizing
To protect the AC connection line of the inverter, we recommend installing a device for protection against over current and leakage with the following character-
istics:
PVI-3.8-TL-OUTD PVI-4.6-TL-OUTD
Type Automatic circuit breaker with differential thermal magnetic protection
Nominal Voltage / Nominal Current 230 Vac / 20 A 230 Vac / 25 A
Magnetic protection characteristic B/C
Number of poles 2
Type of differential protection A/AC
Differential sensitivity 30 mA
ABB declares that the ABB transformerless inverters, in terms of their construction, do not inject continuous ground fault currents and therefore there is no requirement
that the differential protection installed downstream of the inverter be type B in accordance with IEC 60755 / A 2.
Characteristics and sizing of the line cable
Three-pole cable required. The cross-section of the AC line conductor must be sized in order to prevent unwanted disconnections of the inverter from the grid
due to high impedance of the line that connects the inverter to the power supply point.
Cross-section of the line conductor (mm2) Maximum length of the line conductor (mt)
PVI-3.8-I-OUTD PVI-4.6-I-OUTD
4 mm² 15 m 11 m
6 mm² 23 m 16 m
10 mm² 40 m 28 m
16 mm² 64 m 45 m
The values are calculated in nominal power conditions, taking into account:
1. a power loss of not more than 1% along the line. 2. copper cable, with HEPR rubber insulation, laid in free air
max 16 mm²
13 ÷ 21 mm
Each cable which must be connected to the connectors of the communication and control signals must pass through one of the two service cable glands
25
.
An M20 cable gland (that takes cables from 7 mm to 13 mm in diameter) and a gasket with two holes to insert into the cable gland which enables two separate
cables of a maximum diameter of 5 mm to be accommodated, are available.
Warning! To ensure environmental protection IP65 it is necessary to x the cable glands to the inverter chassis with a minimum tightening
torque of 7 Nm
Connection to the RS485 communication line
The RS485 communication port is the inverter’s communication port. The ABB inverters use
an RS485 HALF-DUPLEX communication line made up of two transmission and reception
cables (+T/R and –T/R) and a communication reference cable (RTN): all three cables must be
connected in daisy-chain conguration. The chain connection can be made without distinction
by using the RJ45 connector couples
15
(one for in and one for out) or the terminal block
20
.The last inverter in the daisy chain must be “terminated” or the 120 Ohm communication line
termination resistance must be activated by switching the dip-switch
14
.
Using the alarm terminal block
Terminal block
19
connecting to the congurable relay that allows connection of external
devices which, according to the mode selected in the menu “SETTINGS > Alarm” can, for
example, signal malfunctions. The operating modes that can be set are: Production and Alarm.
The ALARM contact can be used only with systems that ensure a safety isolating additional at least (supplementary insulation in relation to
the DC input voltage)
Using the REM terminal block
The REM terminal block
20
, if suitably congured, allows the “Remote ON/OFF” function to be used: this function allows remote disconnection of the inverter
from the grid
For further information regarding the conguration and use of the communication and control signals terminal block, please see the manual
16
201913
15
The inverter commissioning procedure is as follows:
- Switch the integrated switch
21
(version –S) to the ON position or close the external switches: If the input voltage applied to one of the two input channels is
greater than the minimum starting voltage, the inverter will start up.
- The message “Initializing...Please Wait” will be displayed; Depending on the input voltage value, the inverter will show various messages on the display and
change the behaviour of the three LED
06
:
INPUT VOLTAGE DISPLAY MESSAGE LED STATUS DESCRIPTION
Vin < Vstart Waiting Sun
Green = FLASHING
Yellow = OFF
Red = OFF
The input voltage is not sufcient to permit connection to the grid.
Vin > Vstart Missing Grid
Green = FLASHING
Yellow = ON
Red = OFF
There is sufcient input voltage to permit connection to the grid: the in-
verter waits until there is grid voltage to carry out the parallel connection.
The inverter is powered ONLY by the voltage coming from the photovoltaic generator: presence of grid voltage alone IS NOT SUFFICIENT to permit
the inverter to start up.
- With the inverter in “Missing Grid” status, close the AC switch downstream the inverter so as to supply the grid voltage to the inverter: the inverter performs
the grid voltage check, measures the photovoltaic generator insulation resistance against earth and carries out other self-diagnosis checks. During the
checks before the parallel with the grid, the green LED keeps ashing, the others are off.
During the grid voltage check and measurement of the insulation resistance, the values for the grid voltage and frequency and the insulation
resistance measured by the inverter are shown on the display. The inverter ONLY creates a parallel with the grid if the grid parameters fall within the
range foreseen by current regulations and if the insulation resistance falls within the set parameters.
- If the preliminary checks for parallel connection to the grid are successful, the inverter connects to the grid and begins to export power to the grid. At this
stage, the display shows the inverter’s parameters in cycles. The green LED stays lit whereas the others are off.
Before connecting the inverter to the distribution grid it is necessary to set the country standard by manipulating the two rotary switches
12
.
Note: The settings become xed after 24 hours of operation of the inverter (the PV generator simply has to be under power).
Switch Country Grid Standard
(name displayed)
Display
language
Switch Country Grid Standard
(name displayed)
Display
language
1 2 1 2
0 0 NON-ASSIGNED ENGLISH 1 F BRAZIL @ 220V (BRAZIL) ENGLISH
0 1 GERMANY VDE 0126 @ 230V Single Phase (VDE 0126) ENGLISH 2 0 CLC/FprTS 50549 (TURKEY LV) ENGLISH
0 5 ENEL GUIDA @ 230V Single Phase (ENEL) ENGLISH 2 1 ANRE no.30/17.V.2013 (ROMANIA) ENGLISH
0 6 SPAIN RD 1699 @ 230V (RD 1699) SPANISH 2 2 Slovenian (SLOVENIA) ENGLISH
0 7 UK – G83 @ 230V (UK G83) ENGLISH 2 3 CLC/FprTS 50549 (TURKEY HV) ENGLISH
0 8 UK – G59 @ 230V (UK G59) ENGLISH
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
2
1
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0 9 IRELAND @ 230V (IRELAND) ENGLISH
0 A AUSTRALIA @ 230V (AS 4777) ENGLISH
0DFRANCE @ 230V (FRANCE) FRENCH
0 E NETHERLANDS @ 230V (NETHERL) ENGLISH
0 F GREECE @ 230V (GREECE) ENGLISH
1 0 PORTUGAL @ 230V (PORTUGAL) ENGLISH
1 1 CORSICA @ 230V (CORSICA) FRENCH
1 2 HUNGARY @ 230V (HUNGARY) ENGLISH
1 6 CHECA REPUBLIC @ 230V (CZECH) CZECH
1 7 GERMANY–VDE AR-N-4105 @230V (VDE 4105) GERMAN
1 8 CEI-021 @ 230V INTERNAL Protection (CEI021 IN) ITALIAN
1 9 CEI-021 @ 230V EXTERNAL Protection (CEI021 EX) ITALIAN
1DBELG C10-11 100% @ 230V (C1011 100) FRENCH
1 E BELG C10-11 110% @ 230V (C1011 110) FRENCH
The list of grid standards given in the table was valid at the time of issue of the manual. It will be continually updated as new country standards
with which the inverter is compatible are introduced
Warning! Before performing any of the operations described below, ensure the AC line downstream the
inverter has been correctly disconnected
- Remove the protective lm located on the hole to be used for the AC cables
24
- Insert the M32 cable gland in the hole and secure it using the special M32 lock nut (supplied)
Warning! To ensure environmental protection IP65 it is necessary to x the cable gland to the inverter
chassis with a minimum tightening torque of 8.0 Nm
- Strip 10 mm of sheathing from the AC grid connection cables
- Plug the AC line cable into the inverter, passing it through the previously installed cable gland
- Connect the protective earth (yellow-green) cable to the contact labelled with the symbol on the terminal block
18
Warning! ABB inverters should be earthed (PE) via the terminal with the protective earth label , using a cable with an appropriate cross-
section of the conductor for the maximum ground fault current that the generating system might experience
- Connect the neutral cable (normally blue) to the terminal labelled with the letter N
- Connect the phase cable to the terminal labelled with the letter L
Warning! The AC cables must be tightened on the terminal block with a minimum torque of 1.5 Nm
Once the connection to the terminal board
18
is complete, screw in the cable gland rmly (tightening torque 5.0Nm) and check the tightness.
18
PVI-3.8-I-OUTD PVI-4.6-I-OUTD
Input
Absolute Maximum Input Voltage (Vmax,abs) 520 V
Input Activation Voltage (Vstart) 200 V (adj. 120...350 V)
Input Operating Range (Vdcmin...Vdcmax)0.7 x Vstart...520 V
Rated DC Input Power (Pdcr) 4000 Wp 4800 Wp
Number of Independent MPPTs 2 (6)
Maximum Input Power for each MPPT (PMPPT max) 3000 W
MPPT Input DC Voltage Range (VMPPT min,f ... VMPPT max,f) at Pacr 160...470 V 180...470 V
Maximum DC Input Current (Idc max) / for each MPPT (IMPPT max)25.0 A / 12.5 A 28.0 A / 14.0 A
Maximum Input Short Circuit Current for each MPPT 22.0 A
Maximum Backfeed current (from AC to DC side) Negligible
Number of DC Inputs Pairs for each MPPT 2
DC Connection Type Connettore PV Tool Free WM / MC4
Input protection
Reverse Polarity Protection Yes, from limited current source
Input Overvoltage Protection for each MPPT - Varistor 2
Photovoltaic Array Isolation Control According to local standard
DC Switch Rating (-S Version) Max. 25.0 A / 600 V
Output
AC Grid Connection Type Monophase
Rated AC Power (Pacr) 3800 W 4600 W
Maximum AC Output Power (Pac max)4200 W (1) 5000 W (2)
Rated AC Grid Voltage (Vacr) 230 V
AC Voltage Range 180...264 Vac (4)
Maximum AC Output Current (Iac max)18.2 A (3) 22.5 A
Inrush Current Negligible
Maximum Output Fault Current <25Arms (100mS)
Rated Output Frequency (fr)50 Hz / 60 Hz
Output Frequency Range (fmin...fmax)47...53 / 57...63 Hz (5)
Nominal Power Factor (Cosphiacr) >0.995 adj. ± 0.9 with Pacr= 3.8 kW >0.995 adj. ± 0.9 with Pacr= 4.6 kW
Total Harmonic Distortion of Current < 2%
AC Connection Type Screw terminal block
Output protection
Anti-Islanding Protection According to local standard
Maximum AC Overcurrent Protection 20.0 A 25.0 A
Output Overvoltage Protection - Varistor 2 (L - N / L - PE)
Operating performance
Maximum Efciency (ηmax) 96.8%
Weighted Efciency (EURO/CEC) 96.5% / -
Power Input Treshold 24.0 W
Stand-by Consumption < 8.0 W
Communication
Wired Local Monitoring PVI-USB-RS232_485 (opz.), PVI-DESKTOP (opz.)
Remote Monitoring PVI-AEC-EVO (opz.), VSN700 Data Logger (opz.)
Wireless Local Monitoring PVI-DESKTOP (opz.) with PVI-RADIOMODULE (opz.)
User Interface LCD Display with 16 characters x 2 line
Environmental
Ambient Temperature Range -25...+60°C /-13...140°F -25...+60°C /-13...140°F
with derating above 50°C/122°F
Storage Temperature -40...80°C (-40...+176°F)
Relative Humidity 0...100% condensing
Environmental pollution classication for external environment 3
Noise Emission < 50 dB(A) @ 1 m
Maximum Operating Altitude without Derating 2000 m / 6560 ft
Environmental Category External
Physical
Environmental Protection Rating IP 65
Cooling Natural
Dimension (H x W x D) 712 x 325 x 222 mm / 28.0 x 12.8 x 8.7 inch
Weight < 24.0 kg / 53.0 lb
Mounting System Wall bracket
Overvoltage Category in accordance with IEC 62109-1 II (DC input) III (AC output)
Safety
Isolation Level HF transformer
Safety Class I
Marking CE (50Hz only)
1. Limited to 3800 W for Germany
2. Limited to 4600 W for Germany
3. Limited to 16 A for UK G83/1 standard
4. The AC voltage range may vary depending on specic country grid standard
5. The Frequency range may vary depending on specic country grid standard
6. Independent MPPT only available with negative input grounded.
Remark. Features not specically listed in the present data sheet are not included in the product

Other ABB Inverter manuals

ABB PVS-120-TL User manual

ABB

ABB PVS-120-TL User manual

ABB ACS880-107 User manual

ABB

ABB ACS880-107 User manual

ABB PVS980-MWS User manual

ABB

ABB PVS980-MWS User manual

ABB PVS980-58 Use and care manual

ABB

ABB PVS980-58 Use and care manual

ABB TRIO-TM-60.0-US-480 User manual

ABB

ABB TRIO-TM-60.0-US-480 User manual

ABB TRIO-50.0-TL-OUTD User manual

ABB

ABB TRIO-50.0-TL-OUTD User manual

ABB PVI-3.0-OUTD-US User manual

ABB

ABB PVI-3.0-OUTD-US User manual

ABB PVS980-58 Guide

ABB

ABB PVS980-58 Guide

ABB GMS600 User manual

ABB

ABB GMS600 User manual

ABB UNO-DM-6.0-TL-PLUS-US-Q User manual

ABB

ABB UNO-DM-6.0-TL-PLUS-US-Q User manual

ABB PVI-3.0-TL-OUTD User manual

ABB

ABB PVI-3.0-TL-OUTD User manual

ABB UNO-DM-6.0-TL-PLUS-US User manual

ABB

ABB UNO-DM-6.0-TL-PLUS-US User manual

ABB LMIU1500 User manual

ABB

ABB LMIU1500 User manual

ABB UNO-DM-3.3-TL-PLUS-US-Q User manual

ABB

ABB UNO-DM-3.3-TL-PLUS-US-Q User manual

ABB Fimer PVI-10.0/12.5-TL-OUTD User manual

ABB

ABB Fimer PVI-10.0/12.5-TL-OUTD User manual

ABB TRIO-20.0-TL-OUTD-US User manual

ABB

ABB TRIO-20.0-TL-OUTD-US User manual

ABB ACS880-104 User manual

ABB

ABB ACS880-104 User manual

ABB ACS350 Series User manual

ABB

ABB ACS350 Series User manual

ABB ACS880-104 User manual

ABB

ABB ACS880-104 User manual

ABB ESI-S General instructions

ABB

ABB ESI-S General instructions

ABB ACS880-07CLC User manual

ABB

ABB ACS880-07CLC User manual

ABB UNO-DM-1.2-TL-PLUS User manual

ABB

ABB UNO-DM-1.2-TL-PLUS User manual

ABB UNO-7.6-TL-OUTD-S-US-A User manual

ABB

ABB UNO-7.6-TL-OUTD-S-US-A User manual

ABB PVI-3.0-TL-OUTD-W User manual

ABB

ABB PVI-3.0-TL-OUTD-W User manual

Popular Inverter manuals by other brands

Hayward ECLI15MA Installation instructions manual

Hayward

Hayward ECLI15MA Installation instructions manual

FSP Technology LightUp L11K user manual

FSP Technology

FSP Technology LightUp L11K user manual

Ampair AQUAIR 100 Operation installation and maintenance

Ampair

Ampair AQUAIR 100 Operation installation and maintenance

Epever UP2000-HM6022 user manual

Epever

Epever UP2000-HM6022 user manual

Deye SUN-20K-G02-LV user manual

Deye

Deye SUN-20K-G02-LV user manual

EGO Power+ Nexus Escape PAD1500E Operator's manual

EGO

EGO Power+ Nexus Escape PAD1500E Operator's manual

Yingli Solar YLM 144CELL 182PERC Installation and user manual

Yingli Solar

Yingli Solar YLM 144CELL 182PERC Installation and user manual

Hoymiles HM-600P user manual

Hoymiles

Hoymiles HM-600P user manual

Endress ESE 406 HG-GT ES DUPLEX operating instructions

Endress

Endress ESE 406 HG-GT ES DUPLEX operating instructions

Sunforce Pro Series 11240 user manual

Sunforce

Sunforce Pro Series 11240 user manual

Huawei SUN2000-125KTL-JPH0 quick guide

Huawei

Huawei SUN2000-125KTL-JPH0 quick guide

Sealey MW80 instructions

Sealey

Sealey MW80 instructions

Growatt 4000UE Installation & operation manual

Growatt

Growatt 4000UE Installation & operation manual

Hyundai HiRun N50 Series manual

Hyundai

Hyundai HiRun N50 Series manual

AE Conversion INV315-50EU manual

AE Conversion

AE Conversion INV315-50EU manual

Sensata dimensions 12NP18 owner's manual

Sensata

Sensata dimensions 12NP18 owner's manual

Hitachi WJ200 Series Software Quick reference guide

Hitachi

Hitachi WJ200 Series Software Quick reference guide

North Star M165610B.3 owner's manual

North Star

North Star M165610B.3 owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.