Qty Description Part Number Included with standalone device or kit*
1RSD2.0-1PN6-MC4 - single channel
RSD2.0-2PN6-MC4 - dual channel
3P029970000C - single
3P029950000C - dual Standalone device and kit
1 24Vdc power supply YPA.00238 Kit only
1 Mounting bracket - standard XER.P0500.0 Standalone device and kit
4 Mounting screws 816200010FA-G Standalone device and kit
2 Three-position terminal blocks ZEB.00273 Kit only
1Inverter power supply AC conductors
(Terminal 1, Terminal 2, GND) ZLH.P0504.0 Kit only
1Cover for three-position terminal block ZEB.00275 Kit only
1 Quick installation guide BCM.00372.3DG_AA Standalone device and kit
Table 2 *kit version required for PVI-3.0/3.6/3.8/4.2/5000/6000 and UNO-7.6/8.6 inverters
a. The mounting bracket (A) will come attached to the RSD device. The bracket has four screw holes (B). The RSD box may
be raised or lowered to match four bracket screw holes as needed for clearance from modules or roof. If needed, adjust the
bracket, reattach the bracket to the RSD box with the four screws provided with the device, and torque to 3.5 N.m (2.6 ft-lb).
b. When mounting the RSD device to the PV module frame, use the components supplied with the racking to secure the
mounting bracket (A) to the PV module frame in the area marked (C).
Label Description of RSD device components
AMounting bracket
BBracket mounting holes
CRSD mounting bracket attachment points
DInput conductor leads (coming from PV panels)
EOutput conductor leads (going to the inverter)
F24V supply cable
Table 3
D
F
E
Quick installation guide
Rapid shutdown device (RSD) for 600Vdc
Solar inverters
EN
IMPORTANT SAFETY INSTRUCTIONS – This QIG contains important safety instructions that must be
followed during installation and maintenance of the RSD system.
SAVE THESE INSTRUCTIONS – Keep this document in a safe place near the photovoltaic (PV) system
inverter for easy access during installation and maintenanc
e.
NOTE – This RSD has been tested and certified for use only with ABB single-phase inverters. If used with other inverters,
the RSD may not meet the rapid shutdown requirements of the NEC or perform as specified. Furthermore, use of the RSD
with any other inverters voids the RSD product warranty.
ELECTRICAL WARNINGS –
— An ABB RSD system is designed to comply with the 2014 NFPA 70 National Electric Code, section 690.12 and is tested
according to international safety requirements (UL1741); however, certain safety precautions must be observed when
installing and operating this product. Personal protective equipment (PPE) must be worn at all times when servicing this
equipment.
— Wiring methods used must be in accordance with the National Electric Code, ANSI/NFPA 70 and/or any prevailing local
codes and regulations.
— For suitable wire sizes (AWG), refer to National Electrical Code, Table 310.15(B)(16) for U.S. applications. Use only
copper (Cu) wire rated for 90oC, solid or with type B or type C stranding (19 strands minimum).
— This RSD operates only when properly connected to the power supply and PV strings.
— These connections must be made only by qualied technical personnel.
— The DC operating current and voltage MUST NOT exceed the absolute maximum limits (25A and 600Vdc).
— The RSD system is compatible with 208V and 240V grid connections; it is not compatible with 277V connections.
— The RSD must be tested before the system is commissioned.
2. List of components and spare parts
1. Label and warnings
a. Install the RSD on the roof, within ten feet of the PV array.
b. Note that the RSD may be installed at any angle from horizontal to vertical.
c. Note the temperature (-40oC to 75oC) and enclosure ratings (Type 4X) listed on product label attached to the RSD.
d. Choose a location where the maximum ambient air temperature will be less than the 75oC specifed maximum temperature.
While exposure to direct sunlight is permitted; installation under a module is preferred.
e. Ensure there is sufcient working area around the RSD to allow easy access for maintenance and/or service of the PV
system. If installing the RSD under a PV module, place it under the rst or last module in a row for access. Never install
the RSD in a location that would require the removal of multiple PV modules in order to gain access.
f. Note that the RSD power supply may already be inside the photovoltaic inverter wiring box.
3. RSD installation location
4. Mounting the RSD
5. Wiring the RSD input (from PV array) and output (to inverter)
a. Ensure the inverter's external AC disconnect and its integrated DC disconnect are turned OFF (open). Use appropriate
PPE, and use insulated tools when working with this equipment.
b. Ensure the EGC from the array is indeed connected in the inverter: The equipment grounding conductor (EGC) must
connect the inverter and array in order for the inverter’s ground fault protection to operate as required. (The RSD
enclosure itself is polycarbonate and does not require bonding.)
c. Refer to local codes for appropriate wire size on all conductors.
d. Locate the input wires (D) on the side of the RSD device marked "Input". This marking is present near the edge of the
RSD device on the front and back side. Connect the RSD input wires (D) to the PV array. The positive end of the PV
array must be connected to the RSD input wire labeled (+). The negative end of the PV array must be connected to the
RSD input wire labeled (-). (Note that there will be voltage on the PV array at this point.)
e. Locate the output wires (E) on the side of the RSD device marked "Output". This marking is present near the edge of the
RSD device on the front and back side. Connect the RSD output wires (D) to the inverter inputs. The RSD output wire
labeled Inverter (+) must be connected to the positive DC input terminal of the inverter. The RSD output wire labeled
Inverter (-) must be connected to the negative DC input terminal of the inverter.
WARNING: Swapping the input and output connections of the RSD device may make the system non-compliant
and/or create a hazardous situation. Therefore extra care must be taken to ensure proper connections of the input
and output wiring of the RSD device.
Safety and Hazard Symbols
Risk of electrical shock. Hazardous voltage
will cause severe injury or death. No user-
serviceable parts inside. Only trained service
personnel are allowed access.
Verify the correct connection of the strings to the input
terminals. Polarity reversal may cause serious damage.
Refer to the appropriate product instruction manuals for
more details.
Risk of electrical shock. Multiple voltage
sources may be terminated inside this
equipment. Each circuit must be disconnected
before servicing.
When the photovoltaic array is exposed to light, it
supplies DC voltage to this equipment.
Table 1
Figure 1
D
E
F
6. Prepare to install the 24Vdc power supply
a. Conrm the inverter output (grid connection) is three-wire 240V line-to-line or two-wire 208V line-to-line inverter output.
The RSD unit is NOT compatible with a 277V grid connection. It must only be used with a 208V or 240V grid
connection.
b. Conrm all items in the RSD kit are accounted for; two 3-position terminal blocks and one terminal block cover (Figure
4), 24Vdc power supply and three short conductors to connect the power supply to the inverter AC terminals and to
ground. The 24Vdc power supply, terminal blocks, terminal cover and AC conductor cable will be be installed inside the
ABB string inverter's wiring box.
c. Before installing the 24Vdc power supply, open (turn OFF) the PV system AC disconnect switch AND the PV breaker
to ensure the inverter is disconnected from the grid and from the PV modules.
d. Follow the instructions starting in section 7 to install the 24Vdc power supply. Note that the power supply pigtail coming
out of the RSD box (FIgure 5) will house both the 24V and return wires.
e. The new UNO-DM+ inverter will already have a 24Vdc power supply inside the inverter wiring box and you can skip
sections 7 & 8. Only the older PVI-3.0/3.6/ 3.8/4.2/5000/6000-TL inverters and the UNO 7.6/8.6 inverters will require
you to add the 24Vdc power supply as described in sections 7 & 8.
Note that an uncovered terminal blocks' interior metal will carry the AC voltage. Therefore, the terminal block
cover is required to ensure there is no exposed AC voltage.
RSD - Single Channel Version F
Figure 4
Figure 2
AC
B
D
F
E
RSD - Dual Channel Version
Figure 3: UNO DM+ with 24Vdc power supply
attachment points inside wire box.
FOLD
BCM.00372.3DG Rev AA
© Copyright 2017 ABB. All Rights Reserved.
Specications subject to change without notice.
Contact us
www.abb.com/solarinverters
9. Connecting the control wires between RSD(s) and power supply
Step 6: The installer may connect the 24Vdc supply cable (F) to a UL approved “I” or “T” splice connector depending on the number
of SRD boxes or into a UL approved junction box on the roof. Installer is allowed to clip off connectors in order to use the junction box.
Run the 24Vdc wire pair from the splice connector or junction box to the inverter and attach to the 24Vdc power supply. (Note the
power supply terminals accept wire sizes 18 AWG to 16 AWG). Connect the conductors as follows:
Strip 0.3" of insulation from the ends of the wires.
Use a small Philips screwdriver to attach wires to the (+) and (-) outputs of the power supply. Torque all power supply terminal screws
between 4.43 lb.-in (0.5 N•m) and 5.31 lb.-in (0.6 N•m).
The 24Vdc power supply conductors may be routed through the DC conduits to the location where the RSD device is installed near
the PV array or the installer may run these conductors through a separate DC conduit.
Note: 1. The power supply installed in the inverter wiring box is a Class 2 power source. Class 2 circuits are permitted to be reclassified
as Class 1 circuits per NEC 725.130 (A) exception 2. By reclassifying this circuit at Class 1, the 24Vdc conductors may be installed
in the same raceway as the PV conductors as specified in section 725.48(B) (1) of the NEC. Be sure to follow all Class 1 wiring
methods as stated in section 725.49 to ensure compliance. The installer should mark out any reference to 'Class 2.'
2. Placing the 24Vdc power supply conductors in the same EMT conduit as the PV conductors will require use of 18AWG 600Vdc wire.
Table 4: Expected resistance measurements
Number of RSD
channels in parallel Expected resistance value
136kΩ ±5%
218kΩ ±5%
312kΩ ±5%
49kΩ ±5%
+24V RSD power PV system
disconnect
Utility
grid
~
Rooftop 1
Rooftop 2
PV String 1
PV String 2
PV String 3
ABB rapid
shutdown
PV output MPPT1
PV output MPPT2
ABB rapid
shutdown
6. Once the inverter is connected to the grid and producing power, remove the grid voltage from the inverter by opening AC
circuit breaker or circuit disconnect and monitor the inverter DC input voltage.
7. Confirm the inverter DC input voltage is below 30Vdc within 30 seconds of grid disconnect by measuring the voltage across
the DC input terminals inside the wiring box.
Testing the PV System only, without Rapidshutdown or to Perform Anti-Islanding Test:
If it is necessary to test the PV system without the rapid shutdown being operational, bypass the rooftop RSD by directly
connecting the PV strings to the corresponding PV array output conductors.
Prior to commissioning the PV system, the PV strings and PV output circuits must be properly reconnected through the RSD,
and the system must be tested as described above.
Testing Rapid Shutdown within the PV system:
Once the PV system has been installed, test the RSD system. The intention of the test is to confirm inverter DC input drops
to less than 30 Vdc in less than 30 seconds after AC is removed. A multimeter will be required to measure the DC voltage.
PPE must be used in all steps while working with this equipment.
1. Before connecting the inverter to the grid, measure the output resistance of the RSD at the inverter input terminals (see
Table 4 for correct values.)
12. System testing - required before system commissioning
The inputs of both rapid shutdown boxes
are rated for 25A which allows for single
or paralleled string to be connected to
one input. On a 2 rooftop system either
version of the Rapid Shutdown box, or
both, may be used.
7c. Installing the power supply
Step 3: Snap the orange cover on one terminal block from the kit, prior to mounting it on the DIN rail. Install both terminal
blocks from the kit on the DIN rail to the right of the power supply. The terminal cover must be on the right-side end. Push
the two new terminal blocks, the terminal cover, terminal block 3 and end caps to the left, up against the 24V power supply.
Figures 10 and 11 show the two new terminal blocks in place.
7d. Installing the power supply
Step 4: Replace the inverter AC conductors in the top positions of the two, new left-hand terminal blocks by inserting a ¼”
flat screwdriver into the square holes. Insert the wire labeled '1' into terminal 1 and wire labeled '2' into terminal 2. The wires
are shown in Figures 12 and 13. Be sure the wires are completely seated. Give each wire a pull test to confirm the wire is
snugly held in place.
11. Operation of the RSD
Note: To comply with NEC 690.12 rapid shutdown requirements, within the ten-foot perimeter of the PV array, DC voltage
must be reduced to no more than 30Vdc, and power to <240VA, within 30 seconds. The RSD system is activated through a
loss of AC voltage to the inverter. When the loss of AC occurs, the RSD power supply shuts off. This results in opening the
relay contacts of the RSD device and de-energize the system per NEC 690.12 requirements.
Figure 10
Wiring box for PVI-3.0/3.6/3.8/4.2 and PVI-5000/6000
Figure 11
Wiring box for UNO-7.6/8.6
Figure 12 Figure 13
10. Multiple-RSD installation
Each 24Vdc power supply has terminals for connecting four RS1-1PN6-MC4 devices or two RS2-2PN6-MC4 devices. Repeat
the wiring directions above to connect a second RSD control circuit to the second output positions on the power supply.
However, each 24Vdc power supply in the kit can power up to six single-output RSDs (ABB P/N: RS1-1PN6-MC4) or three
dual-input RSDs (ABB P/N: RS2-2PN6-MC4). For more than two RSDs, you must use an UL approved "I" or "T" splice or a
UL approved junction box, or equivalent.
Without the approved splices an additional power supply would be required to power more than two RSDs in a single-inverter
system. UNO-7.6/8.6 inverters have sufficient space for additional power supplies. If using PVI-series ABB in-verter, there may
be space for only one power supply on the inverter DIN rail.
7a. Installing the power supply
Step 1: Open the inverter wiring box. Disconnect the inverter output conductors from top-side of terminals 1 and 2 by inserting
a ¼” flat screwdriver into the square holes. (The square holes are indicated in Figures 6 and 7.) Lightly press the screwdriver
toward the wire slot until the clamp opens.
7b. Installing the power supply
Step 2: Push the end caps on the DIN rail to the right. Pop the terminal block 1, 2 and GND off the DIN rail by pulling upwards
from the bottom. Install the 24V power supply on the DIN rail, by using a small screwdriver to pull down on the tab on the
bottom of the power supply. See Figures 8a-8d and 9.
Figure 6
Wiring box for PVI-3.0/3.6/3.8/4.2 and PVI-5000/6000
Figure 7
Wiring box for UNO-7.6/8.6
Figure 8a
Figure 13Figure 8c
Figure 8b
Figure 8d
Note: Once the Grid Connections are done to the power supply, measure the output voltage of the power supply to be 24V. If
not, adjust the screw off the power supply until it reads 24V.
8. Wiring the Power Supply inputs from the Grid
Step 5: Connect the ground (green) wire from the kit to the ground terminal of the power supply and to the green terminal block.
Connect one black wire between the center position of the first terminal block and terminal "L" on the power supply. Connect
the 2nd black wire between the center position of the 2nd DIN rail terminal block and terminal "N" on the power supply. Confirm
all wires are completely seated. Torque all power supply screws to 4.43 in-lb (0.5 N.m) - 5.31 in-lb (0.6 N.m). Figures 14 and
15 show the two terminal blocks in place and correctly wired. Give all wires a pull test to confirm the connections are solid.
Figure 14 Figure15
PVI-3.0/3.6/3.8/4.2/5000/6000-TL UNO-7.6/8.6
Do NOT energize the system until proper resistance values are
measured.
2. Connect a voltmeter to the inverter DC input voltage at a
convenient location.
3. Reinstall the inverter switchbox cover.
4. Connect the system to the grid by closing a circuit breaker or
circuit disconnect.
5. Begin monitoring the DC input voltage at the input terminals.
Ensure that the proper input voltage is present based on the
PV plant design documentation.
A system with two or more RSD boxes
will require either a UL approved "T"
connector (available from ABB) or a UL
approved junction box.
FOLD

This manual suits for next models

3

Other ABB Inverter manuals

ABB PVS980-58 Guide

ABB

ABB PVS980-58 Guide

ABB PVI-3.8/4.6-I-OUTD User manual

ABB

ABB PVI-3.8/4.6-I-OUTD User manual

ABB UNO-2.5-I-OUTD User manual

ABB

ABB UNO-2.5-I-OUTD User manual

ABB PVI-5000-TL-OUTD-US User manual

ABB

ABB PVI-5000-TL-OUTD-US User manual

ABB REACT-BATT-AP1 User manual

ABB

ABB REACT-BATT-AP1 User manual

ABB PVI-3.0-TL-OUTD User manual

ABB

ABB PVI-3.0-TL-OUTD User manual

ABB GMS600 User manual

ABB

ABB GMS600 User manual

ABB PVI-3.0-OUTD-US User manual

ABB

ABB PVI-3.0-OUTD-US User manual

ABB PVI-5000-OUTD-US User manual

ABB

ABB PVI-5000-OUTD-US User manual

ABB UNO-2.0-I-OUTD-US User manual

ABB

ABB UNO-2.0-I-OUTD-US User manual

ABB ACS355 series User manual

ABB

ABB ACS355 series User manual

ABB PVS980-MWS User manual

ABB

ABB PVS980-MWS User manual

ABB UNO-2.0-I-OUTD User manual

ABB

ABB UNO-2.0-I-OUTD User manual

ABB PVI-3.0-TL-OUTD-S-US User manual

ABB

ABB PVI-3.0-TL-OUTD-S-US User manual

ABB UNO-DM-6.0-TL-PLUS User manual

ABB

ABB UNO-DM-6.0-TL-PLUS User manual

ABB PVS980-58 Use and care manual

ABB

ABB PVS980-58 Use and care manual

ABB TRIO-20.0-TL-OUTD-US User manual

ABB

ABB TRIO-20.0-TL-OUTD-US User manual

ABB TRIO-20.0-TL-OUTD-S-US-480 User manual

ABB

ABB TRIO-20.0-TL-OUTD-S-US-480 User manual

ABB UNO-DM-3.3-TL-PLUS-US-Q User manual

ABB

ABB UNO-DM-3.3-TL-PLUS-US-Q User manual

ABB PVS-175-TL Series User manual

ABB

ABB PVS-175-TL Series User manual

ABB TRIO-50.0-TL-OUTD User manual

ABB

ABB TRIO-50.0-TL-OUTD User manual

ABB UNO-DM-6.0-TL-PLUS-US-Q User manual

ABB

ABB UNO-DM-6.0-TL-PLUS-US-Q User manual

ABB PVI-3.0/3.6/4.2-TL-OUTD User manual

ABB

ABB PVI-3.0/3.6/4.2-TL-OUTD User manual

ABB REACT-3.6-TL Installation and operating instructions

ABB

ABB REACT-3.6-TL Installation and operating instructions

Popular Inverter manuals by other brands

TECO-Westinghouse Motor EV INVERTER Series operating manual

TECO-Westinghouse Motor

TECO-Westinghouse Motor EV INVERTER Series operating manual

SMA SUNNY BOY STORAGE 2.5 Quick reference guide

SMA

SMA SUNNY BOY STORAGE 2.5 Quick reference guide

Voltacon LV 6KVA-48V user manual

Voltacon

Voltacon LV 6KVA-48V user manual

Scientific Aviation SOOFIE installation guide

Scientific Aviation

Scientific Aviation SOOFIE installation guide

SMA SHP 100-20 operating manual

SMA

SMA SHP 100-20 operating manual

Solahart SunCell SOLAHART450H2 installation manual

Solahart

Solahart SunCell SOLAHART450H2 installation manual

Goodwe SDT G2 Series user manual

Goodwe

Goodwe SDT G2 Series user manual

Autarco XLX20000S Installation and operation manual

Autarco

Autarco XLX20000S Installation and operation manual

Whistler 1200 WATT SERIES owner's manual

Whistler

Whistler 1200 WATT SERIES owner's manual

Winco WL22000VE/A Installation and operator's manual

Winco

Winco WL22000VE/A Installation and operator's manual

Mastervolt WHISPER 9.5 ULTRA installation manual

Mastervolt

Mastervolt WHISPER 9.5 ULTRA installation manual

V-TAC VT-6607136 instruction manual

V-TAC

V-TAC VT-6607136 instruction manual

TOYODenki VF66B operating manual

TOYODenki

TOYODenki VF66B operating manual

AirMan SG Series instruction manual

AirMan

AirMan SG Series instruction manual

Lux Power Technology LXP 3600ACS user manual

Lux Power Technology

Lux Power Technology LXP 3600ACS user manual

Mitsubishi Electric Freqrol-A100 instruction manual

Mitsubishi Electric

Mitsubishi Electric Freqrol-A100 instruction manual

Afore HNS1000TL-1 Installation and operation manual

Afore

Afore HNS1000TL-1 Installation and operation manual

RCT Power Storage DC 4.0 Setup & installation

RCT

RCT Power Storage DC 4.0 Setup & installation

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.