ABB Zenith ZTS T Series Manual

QUICK START USER MANUAL
Zenith ZTS T-series
For ZTS(D) T-series automatic transfer
switches, 30-1200 A, 200-480 Vac
—
This document is not intended to completely replace document 1SCC303039M0201, ZTS(D) T-series
30-1200 A full-length O&M, which is called out in some cases for further details. This quick start
manual is intended to provide the basics of operation, maintenance, and installation for the installer
and users.

2Zenith ZTS(D) 30-1200A ATS, QUICK START USER MANUAL
—
Receiving, handling and storage
Read these safety instructions
carefully before using this product!
Receiving and handling
Upon receipt, carefully inspect the transfer
switch for damage that may have occurred
during transit. If damage is evident, or there
is visible indication of rough handling,
immediately file a damage claim with the
transportation company, and notify your
local ABB sales office.
Do not remove the shipping packaging until
ready to install the switch.
Storage
If the unit will not be placed into service
immediately, store the transfer switch in its
original package in a clean, dry location.
To prevent condensation, maintain a uni-
form temperature. Store the unit in a heated
building, allowing adequate air circulation
and protection from dirt and moisture.
Storing the unit outdoors could cause harm-
ful condensation inside the transfer switch
enclosure.
HAZARD OF EQUIPMENT
OVERTURNING
When moving with a fork lift, do not
remove the shipping packaging until the
device is in its final location.
Failure to follow this instruction may
result in personal injury or equipment
damage.
Warning
Indicates a hazardous situation that,
if not avoided, could result in death or
serious injury.
Danger
Indicates a hazardous situation that,
if not avoided, will result in death or
serious injury.
HAZARD OF ELECTRIC SHOCK,
EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective
equipment and follow safe electrical work
practices.
• This equipment must only be installed and
serviced by qualified electrical personnel.
• Before performing visual inspections,
tests, or maintenance on the equipment,
disconnect all sources of electric power.
Assume that all circuits are live unless they
are completely de-energized, tested,
grounded, and tagged. Pay particular at-
tention to the design of the power system.
Consider all sources of power, including
the possibility of backfeeding.
• Disconnect all sources of electric power
before removing or making source side or
load side connections to the transfer
switch.
• Always use a properly rated voltage
sensing device at all line and load connec-
tions to confirm transfer switch is discon-
nected from all live electrical sources.
• Turn off power supplying transfer switch
before doing any other work on or inside
switch.
Failure to follow these instructions could
result in death or serious injury.

3
—
Quick Start User Manual
Automatic transfer switches,
Zenith ZTS(D) T-series ATS
Introduction 4
Hazard Categories 4
Warranty 5
General overview 6
Zenith ZTS(D) T-series 30-1200 A features 8
Operation 10
Switching sequence / Automatic 10
Automatic configuration 11
Confirm Automatic Operation 11
Settings (Optional) 12
I/O Setting Instructions 14
Operating and locking 15
Manual handle operation 16
Return to Automatic mode, operating by HMI 17
LED functionality in HMI 18
Using Level 4 /touch) control Interface HMI 20
Electronic accessories 21
Troubleshooting 22
Alarms 22
Warnings 24
Technical data 26
Circuit diagrams 29
Maintenance 31
Panel installation 32
Basic Tools for Installation and Maintenance 33
Equipment Inspection and Storage 33
Lifting and Mounting the Panel 34
Mounting the automatic transfer switch 35
Mounting hole dimensions 35
Wire Connection 36
Final Equipment Inspection 36
Initial Energizing 37
Accessories 38
Auxiliary contact blocks 38
Auxiliary power supply and Ekip -modules 40
Replacement Parts 41

4Zenith ZTS(D) 30-1200A ATS, QUICK START USER MANUAL
—
Introduction
This manual describes the installation,
basic operation, and maintenance of
the Zenith ZTS(D) T-series (30-1200 A,
200-480 Vac) automatic transfer
switches, manufactured by ABB.
Installation instructions for the transfer
switch and available accessories
can be found in the O&M Manual
1SCC303039M0201 on pages 9 and 10.
—
Hazard Categories
The following important highlighted
information appears throughout this
document to warn of potential hazards
or to call attention to information that
clarifies a procedure.
Carefully read all instructions and become
familiar with the devices before trying to
install, operate, service or maintain
this equipment.
Danger
Indicates a hazardous situation that, if not
avoided, will result in death or serious injury.
Warning
Indicates a hazardous situation that, if not
avoided, could result in death or serious
injury.
Caution
Indicates a hazardous situation that, if not
avoided, could result in minor or moderate in-
jury. Failure to comply with these instructions
may result in product damage.
Notice
It is used to notify of practices not related to
personal injury. Failure to comply with these
instructions may result in product damage.

5
—
Warranty
This document is based on information
available at the time of its publication.
While efforts have been made to ensure
accuracy, the information contained
herein does not cover all details or
variations in hardware and software,
nor does it provide for every possible
contingency in connection with
installation, operation, and maintenance.
Features may be described herein that are
not present in all hardware and software
systems.
ABB Zenith assumes no obligation of
notice to holders of this document with
respect to changes subsequently made.
ABB Zenith makes no representation or
warranty, expressed, implied, or
statutory, and assumes no responsibility
for the accuracy, completeness,
sufficiency, or usefulness of the
information contained herein. No
warrantees of merchantability or fitness
for purpose shall apply.
Contact your local sales office if further
information is required concerning any
aspect of the automatic transfer switch
operation or maintenance.
Warranty Period
The Warranty Period for ZTS(D) T-series
transfer switch products is twenty-four
(24) months from the date of
shipment.
Notes: This warranty is valid only in the
United States and for products sold and
installed within seller-specified countries.
Replacement parts are warranted for a
period of 90 days when installed by a
factory or an authorized service station.
Contact Service team at: +1 800 637 1738
or epis.pqservice@abb.com for 24-hour
support.
Fig. 1 Sample nameplate
Product Rating / Applicable Standards
For UL 1008 ‘withstand’ and ‘close on
short circuit’ ratings, refer to ABB
publication number 1SCC303020C0201.

6Zenith ZTS(D) 30-1200A ATS, QUICK START USER MANUAL
1 Automatic transfer switch
2 Embedded ATS control unit and mechanism
3 Level 4 HMI unit, ZTS T-series color touchscreen LCD
4 Slide switch (Hand - Locking - AUTO) for selection of the operation mode
5 Padlocking the automatic transfer switch to prevent automatic and
manual operation
6 Handle for manual operation
7 Position indication
8 Terminals for control circuit connections (behind the cover)
9 Place for connectivity modules (aux power supply, com and signaling)
10 Place for auxiliary contact block
11 Location of product identification label
12 Programming port, only for Ekip Programming module and Ekip Connect software
—
Fig. 2 Automatic transfer switch, Zenith ZTS powered by TrueONE™
—
General overview
289 4 6 1 10
12
11
3
5 7

7
l
ON
ll
ON
AUTO
!
S1 S2
LOAD
lll
O
O
OFF
Operation types, ZTS T-series ATS Ekip-modules suitable
Delayed transition, ZTSD Open transition, ZTS
IS1 S2
Load
OII IIS1 S2
Load
OI
IS1 S2
Load
II
ZTS T-series HMI (with touch screen) and connections of control circuit
Suitable
12 3
CNO NC
65
O1
CI3
14 15
10 11 12 13
I1 I2C
G+-
FIRE
24V I2
O1C CC NO NC I1
12 13 1 41 2 3 65
G
—
Table 1 The differences of level types / operation types and the suitability of Ekip-modules
l
ON
ll
ON
AUTO
!
S1 S2
LOAD
lll
O
O
OFF
l
ON
ll
ON
AUTO
!
S1 S2
LOAD
lll
Operational types
In this table you can find the differences
of the automatic transfer switch open
and delayed transition operation types.
Due to the different transition types, there
are variances with HMI and on wiring of I/O
contacts.
HMI
The HMI is the control interface
(Human Machine Interface) of the ATS.
Zenith ZTS T-series has a color touch
screen LCD HMI with push buttons.
The HMI is used for configuring
parameters for automatic operation.

8Zenith ZTS(D) 30-1200A ATS, QUICK START USER MANUAL
Feature comparison ZTS(D) controls (Touch screen)
Ampere sizes available
Rated voltage
Rated frequency
Phase system Single and Three
Number of poles
Neutral configuration
Switched Yes
Product type
Open transition (I-II) Yes
Delayed transition (I - O - II or II - O - I) Yes
Voltage and frequency settings
Time delay settings
Generator stop delay, min
Center-OFF delay, sec
Load shed delay, sec
Source failure detections
No voltage Yes
Undervoltage Yes
Overvoltage Yes
Phase missing Yes
Voltage unbalance Yes
—
Zenith ZTS(D) T-series 30-1200A features

9
Feature comparison ZTS(D) controls (Touch screen)
Invalid frequency Yes
Incorrect phase sequence Yes
Features
Controls Touch + keys
Yes
Open transition - Standard digital inputs/outputs
Delayed transition - Standard digital inputs/
outputs
Programmable digital inputs/outputs Yes
Auto config (voltage, frequency, phase system) Yes
Auto config (voltage frequency, phase system) Yes
Source priority
Manual re-transfer Yes
In-phase monitor Yes
Genset exercising: on-load, off-load Yes
In-built power meter module Yes
Load shedding Yes
Real time clock Yes
Event log Yes
Predictive maintenance Yes
Harmonics measuring Voltage, current
Field-mount accessories
Auxiliary contacts for position indication Yes
Digital input/output modules Yes
Yes
Communication modules Yes
Connectivity
Yes
Modbus/TCP Yes
Profibus DP Yes
ProfiNet Yes
DeviceNet Yes
Ethernet IP Yes
Ekip Com Hub (monitoring via ABB Ability™: EDCS) Yes
Enclosures
Yes
For applications
Mains - Mains Yes
Mains - Generator Yes
Contact ABB for applications with smaller than 20 KVA gensets.
—
Table 2 ATS features not limited to what is in the table above

10 Zenith ZTS(D) 30-1200A ATS, QUICK START USER MANUAL
—
Operation
Switching sequence / Automatic
SOURCE1 Priority (SOURCE2 = Generator)
The switching sequence can be summarized
in the following steps:
1. An anomaly occurs on SOURCE 1
2. Override momentary S1 outage delay
3. Generator start
4. SOURCE 2 OK
5. Transfer from S1 to S2 delay
6. Pre-transfer signal on
7. Load shed signal on
8. Pre-transfer S1 to S2 delay
9. Load shed delay
10. Transfer switch (SOURCE 1) to position O
11. Center-off delay (only with Delayed
transition I - O - II type)
12. Transfer switch (SOURCE 2) to
position II
13. Post-transfer S1 to S2 delay
14. Pre-transfer signal off
The re-transfer sequency can be
summarized in the following steps:
1. SOURCE 1 is restored
2. Transfer from S2 to S1 delay
3. Pre-transfer signal on
4. Pre-transfer S2 to S1 delay
5. Transfer switch (SOURCE 2) to
position O
6. Center-off delay (only with Delayed
transition I - O - II type)
7. Transfer switch (SOURCE 1) to position I
8. Load shed signal off
9. Generator stop delay
10. Post-transfer S2 to S1 delay
11. Pre-transfer signal off
12. Generator stop
13. SOURCE 2 off
SOURCE2 Priority (No generator)
The switching sequence can be
summarized in the following steps:
1. An anomaly occurs on SOURCE 2
2. Override momentary S2 outage delay
3. Transfer from S2 to S1 delay
4. Pre-transfer signal on
5. Load shed signal on
6. Pre-transfer S2 to S1 delay
7. Load shed delay
8. Transfer switch (SOURCE 2) to
position O
9. Center-off delay (only with Delayed
transition I - O - II type)
10. Transfer switch (SOURCE 1) to
position I
11. Post-transfer S2 to S1 delay
12. Pre-transfer signal off
The re-transfer sequence can be
summarized in the following steps:
1. SOURCE 2 is restored
2. Transfer from S1 to S2 delay
3. Pre-transfer signal on
4. Pre-transfer S1 to S2 delay
5. Transfer switch (SOURCE 1) to
position O
6. Center-off delay (only with Delayed
transition I - O - II type)
7. Transfer switch (SOURCE 2) to
position I
8. Load shed signal off
9. Post-transfer S1 to S2 delay
10. Pre-transfer signal off

11
—
Automatic configuration
Auto configure is the first step to take
after the panel is initially energized. This
function recognizes the electrical system,
then automatically sets all the system
parameters: system voltage, frequency,
and phase sequence.
Follow the steps in the figure on the HMI
to run auto configure. The ATS must have
at least one source available to complete
this step.
To put your ATS into Auto mode, confirm
the slide switch is in “AUTO” before the
enclosure door is closed. This slide switch
overrides the Auto/Manual mode set from
the HMI. To place the ATS controller in
AUTO mode through HMI screen, set
"Automatic mode" to "ON" in the
operations menu.
Confirm the ATS is in Auto mode by
validating that the “AUTO” LED above and
to the right of the LCD screen is solid
green.
—
Confirm Automatic Operation
—
Fig. 4
—
Fig. 3
S1 Connected to Load
Load Current
393 A
11:06
60sG
Override S1 Fail TruONE ATS
S
ystem Overview
S
1 OkNot Ok S2
Operation ParametersMeasurements
AboutTestSettings
TruONE AT
S
1. 2.

12 Zenith ZTS(D) 30-1200A ATS, QUICK START USER MANUAL
—
Settings (Optional)
Time delays Default Value Possible range
Center-off delay
Generator stop
Set points
Voltage and frequency drop-out
Voltage and frequency pick-up
In-phase Monitor On Off, On
Manual Retransfer Off Off, On
Commit Transfer Off Off, On
Application
See manual
—
Table 3
Settings can be changed via the HMI as shown in Figure 5 and 6. See section 4 of the
ZTG(D) O&M for further detail. A password is required to change parameters; the default
password is 00001. Alternatively, settings can be changed with Ekip Connect 3 software
using Ekip Programming module.
—
Fig. 5

13
If the standard I/O or any com modules such as Ekip 2k Signaling I/O must be pro-
grammed, these can be set in the same manner, by following the appropriate path below
from the main menu.
Settings>Standard I/O Settings or Settings>Modules
—
Fig. 6

14 Zenith ZTS(D) 30-1200A ATS, QUICK START USER MANUAL
—
I/O Setting Instructions

15
—
Operating and locking
Locking mode
Manual mode Automatic mode
Ø 5-6 mm
0.20- 0.24 in
—
Fig. 7 Above the selection of the operation modes
(Manual or Automatic) by the slide switch. Below
padlocking the automatic transfer switch; The handle
has to set standby slot (not in use), after that the slide
switch will move to the Locking mode automatically
and the switch is allowed to be padlocked.
The operation mode is selected by using
the slide switch (Hand - Locking - AUTO)
located on the front of the automatic
transfer switch (ATS).
• Hand-position = Manual mode, enabling
emergency manual operation using the
handle. ATS functionality is disabled
when in Hand position.
• Lock-position = Locking mode, padlock-
ing the automatic transfer switch in a
specific position to prevent automatic
and manual operation.
Notice
The handle has to be in its stored position
(not in use), after which the slide switch will
move to the Locking mode automatically and
the switch is allowed to be padlocked. To set
the operating handle back to its place, refer to
the left most picture in Fig. 3.6.
• AUTO-position = Automatic control
mode enabled, ATS is operable in Auto-
matic mode or from the HMI manual
control keys. When the slide switch is
moved to the AUTO position, the ATS is
functioning immediately in the auto-
matic control mode.

16 Zenith ZTS(D) 30-1200A ATS, QUICK START USER MANUAL
—
Fig. 8 Mounting of the handle in the operating position
To mount the handle in the operating
position, turn the slide switch to the
Manual mode (Hand), lift the handle
from its place inside and place it to the
operating position.
More information, see animation:
Manual and automatic operation
- TruONE™ATS (https://youtu.be/
bosvSPVi2sM).
—
Manual handle operation
Warning
Verify the condition of power source
prior to manually transferring. Manual
operation may result in out-of-phase
transfer when both sources are
energized.
—
Fig. 9 Manual mode, operating by handle, delayed
transition I - O - II. You have to stop and release
(= take the hand off) the handle in O-position when
moving from position I to II (or from position II to I)
Manual
mode
3
2
1
I-position
O-position
ZTSD: I - O - II
O-position
II-position

17
2
1
3Automatic
mode
—
Fig. 10 Manual mode, operating by
handle, open transition I - II
—
Fig. 11 The operating handle must set back to standby
slot before moving to the automatic mode
—
Return to Automatic mode,
operating by HMI
When operating the automatic transfer
switch by HMI, turn the slide switch to
Automatic mode (AUTO). Remark! The
handle has to be standby slot (not in use)
before turning to automatic mode.
Notice
When the slide switch is moved to the AUTO
position, the ATS will enter auto mode after a
3 second delay.
I-position II-position
ZTS: I - II

18 Zenith ZTS(D) 30-1200A ATS, QUICK START USER MANUAL
—
LED functionality in HMI
—
Fig. 12 On left: LEDs in ZTSD, delayed transition, I - O - II. On right: LEDs in ZTS, open transition I - II.
I - O - II I - II
Manual
retransfer
Auto
config
Priority
In-phase
monitor
AUTO
!
S1 S2
LOAD
lll
O
Lamp
test
l
ON
Off
load
test
ll
ON
Auto
Alarm reset
On
load
test
Bypass
time
delay
Generator
stop delay
4 min
30 s
ΔU 20% / Δf 10%
0
1
2
3
4
5
10
15
20
30
S1 Failure
delay [s] S1 Return
delay [min]
O Position
delay
4 s
0 s
O
OFF
Manual
retransfer
Auto
config
Priority
In-phase
monitor
AUTO
!
S1 S2
LOAD
lll
LED Indication Description
Power led
Lamp
test
l
Off
load
test
ll
Auto
Alarm reset
On
load
test
Bypass
time
delay
Generator
stop delay
4 min
30 s
ΔU 10% / Δf 5%
ΔU 15% / Δf 10%
ΔU 20% / Δf 10%
0
1
2
3
4
5
10
15
20
30
S1 Failure
delay [s] S1 Return
delay [min]
Manual
retransfer
On
Priority
No priority
In-phase
monitor
On
AUTO
!
S1 S2
LOAD
lll
O
ON, fixed light Power supply and communication present
Power supply present, communication
absent between switch and the HMI
OFF No power available for HMI.
S1 and S2 leds
Off
load
test
ll
ON
Auto
Alarm reset
On
load
test
Bypass
time
delay
4 min
30 s
4
5
10
15
20
30
S1 Return
delay [min]
4 s
0 s
O
OFF
Manual
retransfer
Auto
config
Priority
In-phase
monitor
AUTO
!
LOAD
lll
O
S1 S2
ON, fixed light
defined limits
Undervoltage
Invalid frequency
Unbalance
Overvoltage
Incorrect phase sequence
Phase missing
Generator stop delay ongoing
OFF No voltage
At the top of ZTS 30-1200 A, 200-480 Vac ATS, there is a set of LEDs intended to
model the state of the transfer switch sources, position, alarms, and mode.
A considerable amount of information can be deciphered from the LED states.
See the tables below for more information.

19
I, II and 0 leds
Lamp
test
l
ON
Off
load
test
ll
ON
Auto
Alarm reset
On
load
test
Bypass
time
delay
O
OFF
Manual
retransfer
Auto
config
Priority
In-phase
monitor
AUTO
!
S1 S2
LOAD
ll
O
l
Lamp
test
l
ON
Off
load
test
ll
ON
Auto
Alarm reset
On
load
test
Bypass
time
delay
Generator
stop delay
4 min
30 s
0
1
2
3
4
5
10
15
20
30
S1 Failure
delay [s] S1 Return
delay [min]
O Position
delay
4 s
0 s
O
OFF
Manual
retransfer
Auto
config
Priority
In-phase
monitor
AUTO
!
S1 S2
LOAD
ll
O
l
Lamp
test
l
ON
Off
load
test
ll
ON
Auto
Alarm reset
On
load
test
Bypass
time
delay
4 min
30 s
0
1
2
3
4
5
10
15
20
30
S1 Failure
delay [s] S1 Return
delay [min]
4 s
0 s
O
OFF
Manual
retransfer
On
Priority
No priority
In-phase
monitor
On
AUTO
!
S1 S2
LOAD
ll
O
l
ON, fixed light Switch position is indicated with fixed
light in I, O or II led. Only one can be on
simultaneously
Delay ongoing. Going to move away from
the blinking status
Load led
ON
Off
load
test
ll
ON
Auto
Alarm reset
On
load
test
Bypass
time
delay
Generator
stop delay
4 min
30 s
4
5
10
15
20
30
S1 Return
delay [min]
O Position
delay
4 s
0 s
O
OFF
Dropout ΔU / Δf
Manual
retransfer
ΔU 5% / Δf 5%
On
Off
Priority
No priority
Source 1
In-phase
monitor
Off
On
AUTO
!
S1 S2
lll
O
LOAD
ON Supply ok and connected to load
OFF Not connected to load
Auto led
ON, fixed light Switch is in automatic mode
Test on load
Test off load
If blinks simultaneously with Alarm led
'Inhibit transfer' digital input is activated.
Autoconfig completed
Alarm led
ON
Off
load
test
ll
ON
Auto
Alarm reset
On
load
test
Bypass
time
delay
4 min
515 30 4 s
O
OFF
Manual
retransfer
On
Off
Priority
No priority
Source 1
AUTO
S2
!
OFF No alarms
ON, fixed light Handle attached, locked, other alarm
Control Alarm
Auto configuration ongoing
Control Retry
Auto mode off
If blinks simultaneously with Alarm led
'Inhibit transfer' digital input is activated.
If Auto led is fixed light then manual
retransfer is required.
ll
ON
Auto
Alarm reset
Bypass
time
delay
!
S2
AUTO
Table 4 LED functionality

20 Zenith ZTS(D) 30-1200A ATS, QUICK START USER MANUAL
—
Using Level 4 (touch) control interface HMI
Keypad
1 Home Button: Opens up the root
menu or brings user to the homepage
if defined. While viewing a specific
page, it can be defined as the home
page by pressing the home button for
3 seconds. All pages, except for the
menus, can be set as home page.
Home page is automatically shown
after inactivity.
2 I ON: Operate switch to I position.
3 II ON: Operate switch to II position.
4 O OFF: Operate switch to O position
and disable automatic control mode
(only in delayed transition I-O-II type).
Navigating menu
Menus and parameters- Refer detailed
catalog.
—
Fig.13 Keypad in Level 4 HMI with touch screen
l
ON ll
ON
O
OFF
2
1
4 3
l
ON ll
ON
AUTO
!
S1 S2
LOAD
lll
2
1
3
1SCC303039M0201
Other manuals for Zenith ZTS T Series
2
Table of contents
Other ABB Switch manuals
Popular Switch manuals by other brands

Marshall Amplification
Marshall Amplification VMV-402-SH user manual

Black Box
Black Box LB9020A-R2 manual

Advantech
Advantech EKI-7428G Series user manual

Asante
Asante FriendlyNET GX5-2400W Specification sheet

Pittway
Pittway System Sensor EPS10EXP Installation and maintenance instructions

Siemens
Siemens SENTRON 3NJ621 operating instructions