ABB AWT210 User manual

—
ABB MEASUREMENT & ANALYTICS | COMMUNICATIONS SUPPLEMENT
AWT210
HART 2-wire transmitter
Measurement made easy
Introduction
This Communication Supplement provides
procedures specifically related to the AWT210
HART® 2-wire transmitter. Refer to the AWT210
Operating Instruction (OI/AWT210-EN) for general
information on installation, operation and
maintenance.
For more information
Further publications for the AWT210 transmitter are
available for free download from:
www.abb.com/measurement
or by scanning this code:
Search for or click on:
Data Sheet DS
Commissioning Instruction C
Operating Instruction
HART FDS Communications Supplement
HART/FDS-EN
—
AWT210
2-Wire transmitter

2AWT210 HART 2-WIRE TRANSMITTER | COM/AWT210/HART-EN REV. B
Contents
1 Health & Safety ..............................3
Document symbols .................................3
Safety precautions .................................3
Potential safety hazards ............................3
................3
Safety standards ...................................3
Waste Electrical and Electronic Equipment (WEEE) .. 4
Product recycling and disposal (Europe only) ....... 4
Information on ROHS Directive 2011/65/EU
(RoHS II) .......................................... 4
Product symbols .................................. 4
2 Overview....................................5
Abbreviations and Definitions ......................5
Reference documents ..............................5
HART Manufacturing ID and Device Type.............5
Engineering units and dynamic variables ............5
Dynamic variables ............................5
pH units......................................5
Conductivity units ............................5
3 Transmitter functionality and operator
interface controls............................6
Process interface.................................. 6
Sensor Input Channels ........................6
Host interface..................................... 6
Analog output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Local interfaces, jumpers and switches ............. 6
Local controls and displays....................6
Internal jumpers and switches.................6
4 Installation..................................6
Analog mode signal and power wiring ...............7
Multi-drop mode (digital) signal and power wiring .. 8
Sensor wiring and grounding ...................... 8
5 Appendix ...................................9
Introduction ...................................... 9
Supported HART commands ....................... 9
Universal HART commands ....................9
Common practice HART commands............9
Device-specific HART commands: general......9
Device--specific HART commands:
Two Electrode conductivity (TE) ..............10
Device-specific HART commands:
Toroidal Conductivity (TC) ...................10
Device-specific HART commands:
Four Electrode Conductivity (EC) ............. 11
Device-specific HART commands: pH ......... 11
Sales Service Software

AWT210 HART 2-WIRE TRANSMITTER | COM/AWT210/HART-EN REV. B 3
1 Health & Safety
Document symbols
Symbols that appear in this document are explained below:
DANGER – SERIOUS DAMAGE TO HEALTH
This symbol in conjunction with the signal word
‘DANGER’ indicates an imminent electrical hazard.
Failure to observe this safety information will result in
death or severe injury.
WARNING – BODILY INJURY
This symbol in conjunction with the signal word
‘WARNING’ indicates a potential electrical hazard.
Failure to observe this safety information will result in
death or severe injury.
CAUTION – MINOR INJURIES
This symbol in conjunction with the signal word
‘CAUTION’ indicates a potentially dangerous
situation. Failure to observe this safety information
may result in minor or moderate injury. The symbol
may also be used for property damage warnings.
IMPORTANT (NOTE)
This symbol indicates operator tips, particularly
useful information or important information about
the product or its further uses. The signal word
‘IMPORTANT (NOTE)’ does not indicate a dangerous
or harmful situation.
Safety precautions
Be sure to read, understand and follow the instructions
contained within this manual before and during use of the
equipment. Failure to do so could result in bodily harm or
damage to the equipment.
WARNING – BODILY INJURY
Installation, operation, maintenance and servicing
must be performed:
• by suitably trained personnel only
• in accordance with the information provided in this
manual
• in accordance with relevant national and local
regulations
Potential safety hazards
AWT210 transmitter – electrical
WARNING – BODILY INJURY
To ensure safe use when operating this equipment,
the following points must be observed:
• Up to 240 V AC may be present. Be sure to isolate
the supply before removing the terminal cover.
• Normal safety precautions must be taken to avoid
the possibility of an accident occurring when
operating in conditions of high pressure and/or
temperature.
Safety advice concerning the use of the equipment
described in this manual or any relevant Material
Safety Data Sheets (where applicable) can be
obtained from the Company, together with servicing
and spares information.
Safety standards
This product has been designed to satisfy the requirements of
IEC61010-1:2010 3rd edition ‘Safety Requirements for Electrical
Equipment for Measurement, Control and Laboratory Use’ and
complies with US NEC 500, NIST and OSHA.
This equipment complies with the requirements of CEI/IEC
61010-1:2010 ‘Safety Requirements for Electrical Equipment for
Measurement, Control and Laboratory Use’ and complies with
US NEC 500 and Occupational Safety & Health Administration.
If the equipment is used in a manner NOT specified by the
Company, the protection provided by the equipment may be
impaired.

4AWT210 HART 2-WIRE TRANSMITTER | COM/AWT210/HART-EN REV. B
…1 Health & Safety
Waste Electrical and Electronic Equipment
(WEEE)
WEEE EU Directive 2012/19/EU covers disposal and recycling
of electronic equipment at the end of life for reasons of
environmental protection.
For industrial installations, portable equipment is
included. This means that when the AquaMaster4
transmitter is used with a portable AquaProbe sensor,
it is included in directive’s scope and has the WEEE
symbol (left) on its data label. Therefore, at the end of
life, contact the supplier for specialist waste
recycling. It must not be disposed of as municipal
waste.
Permanent Industrial installations are not designated within
this directive for recycling. At the point of supply the intended
use is not always known, so the WEEE symbol is included on all
remote forms of the AquaMaster4 transmitter.
Product recycling and disposal (Europe only)
Electrical equipment marked with this symbol may
not be disposed of in European public disposal
systems after 12 August 2005. To conform to
European local and national regulations (EU Directive
2012/19/EU), European electrical equipment users
can now return old or end-of-life equipment to the
manufacturer for disposal at no charge to the user.
ABB is committed to ensuring that the risk of any
environmental damage or pollution caused by any of
its products is minimized as far as possible.
IMPORTANT (NOTE)
For return for recycling, please contact the equipment
manufacturer or supplier for instructions on how to
return end-of-life equipment for proper disposal.
Information on ROHS Directive 2011/65/EU
(RoHS II)
ABB, Industrial Automation, Measurement & Analytics, UK, fully
supports the objectives of the ROHS II directive. All in-scope
products placed on the market by IAMA UK on and following the
22nd of July 2017 and without any specific exemption, will be
compliant to the ROHS II directive, 2011/65/EU.
Product symbols
Symbols that may appear on this product are shown below:
Risk of electric shock.
This symbol, when noted on a product, indicates a
potential hazard which could cause serious personal
injury and/or death. The user should reference this
instruction manual for operation and/or safety
information.
Protective earth (ground) terminal.
Functional earth (ground) terminal.
Direct current supply only.
This symbol, when noted on a product enclosure or
barrier, indicates that a risk of electrical shock and/or
electrocution exists and indicates that only
individuals qualified to work with hazardous voltages
should open the enclosure or remove the barrier.
Recycle separately from general waste under the
WEEE directive.

AWT210 HART 2-WIRE TRANSMITTER | COM/AWT210/HART-EN REV. B 5
2 Overview
The AWT210 HART® transmitter provides either a 4 to 20mA
analog signal (conventional analog), a 4 to 20mA analog signal
with superimposed digital signal (HART point to point analog),
or a polled digital signal (HART multi-drop). Using HART
communications, many functions normally requiring the use of
the local user-interface can be accessed remotely using HART
communication devices.
Four variants of AWT210 are available for use with pH, ORP,
pIon, and conductivity sensors.
The device has four dynamic variables. The device does not
have any device variables.
The analogue output of this device corresponds to the primary
variable (pH, ORP, pIon, Ion concentration, conductivity, or
concentration), outputting 4 mA at the lower range value and
20 mA at the upper range value.
Supported Sensors:
• pH
• 2-electrode conductivity
• 4-electrode conductivity
• toroidal conductivity
The ABB AWT210 analyzer complies with HART Protocol
Revision 7.0.
Abbreviations and Definitions
Module Description
TE Module
EC Module
TC Module Toroidal conductivity module
ORP Oxidation-reduction potential
DDL Device description language
HART Highway addressable remote transducer
HHT Hand held terminal
Reference documents
Document ID Title
HART-FDS-EN
Field Device Specification
HART manufacturing ID and device type
All HART products contain unique identifiers that specify the
product manufacturer and device type. In accordance with this
requirement, the ABB Manufacture ID is 26 (1A hexadecimal)
and the device type code for AWT210 is 34 (22 hexadecimal).
Engineering units and dynamic variables
Dynamic variables
pH (pH) Conductivity (TE, EC, TC)
Measurement Units Measurement Units
PV
pH
ORP
pION
Ion Conc.
pH
mV
%, ppb, ppm, µg/l
mg/l
Conductivity
concentration
µS/cm,
mS/cm
%
ppb
ppm
µg/l
mg/l
SV Temperature °C, °F Temperature °C
°F
TV Reference
impedance Compensated
conductivity µS/cm
QV Input voltage mV Uncompensated
conductivity µS/cm
Unit codes
Unit Unit
code
Unit type/dynamic variable
classification
Unit type
code
Deg C Temperature
Deg F Temperature
uS/Cm Conductivity/Volumetric conductance
mS/Cm Conductivity/Volumetric conductance
mV EMF
pH Analytical
Kilo Ohm Electric resistance
% Concentration
ppm Concentration
ppb Concentration
ug/l Concentration
mg/l Concentration

6AWT210 HART 2-WIRE TRANSMITTER | COM/AWT210/HART-EN REV. B
3 Transmitter functionality and
operator interface controls
Process interface
Sensor Input Channels
The sensor module provides 8 terminals marked 1 to 8, 1 to 4 for
Process Variable (detailed in commissioning instructions) and 5
to 8 for temperature sensor (up to 3 wire RTD + shield).
Operating ranges correspond to the capabilities of each sensor
type.
Host interface
The 2-wire 4 to 20 mA current loop is connected via terminals 1
and 2 on the HART communications module and can be tested
via terminals 4 and 5.
Output from the transmitter representing the PV measurement
linearized and scaled according to the engineering range set on
the instrument. PV% is displayed on the Signals View page.
Analog output
Value
Below Lower Range
Above Upper Range
Device malfunction indication
Maximum current
Multi-drop current draw
Lift-off voltage
Local interfaces, jumpers and switches
Local controls and displays
• The Device has a 75 x 65 mm (3.00 x 2.55 in.) monochromatic
dot matrix LCD display and 4 push buttons
Internal jumpers and switches
• The device has 2 internal switches, situated on the top
see Figure 1.
• SW1: Reset to Defaults
If the device is powered up with SW1 in the ON position it
returns device setup to default factory settings. If powered
up with SW1 in the OFF position the device retains
previously saved user settings*.
• SW2: Write Protection
If SW2 is in the ON position HW write protect shows as
enabled and the user is unable to make changes to setup or
send Write commands via HART. With SW2 in OFF position
the user is able to make changes/send commands providing
they are in a sufficient access level and Software Write
Protect has not been enabled.
*Reset to defaults is not performed if
SW2 Write Protection is ON.
4 Installation
This section provides installation instructions specific to the
AWT210 HART functionality.
WARNING – BODILY INJURY
• For general mechanical, electrical and hazardous
location installation requirements refer to the
AWT210 Operating Instructions (OI/AWT210-EN).
• The signal/power terminals accept wire sizes
0.14 mm² (26 AWG) to 1.5 mm²(14 AWG).
• Wiring should not be run in conduit or open trays
where power or heavy electrical equipment could
physically or electrically interfere with the signal
wiring. Twisted, shielded pairs should be used for
cabling to ensure best performance. Reverse
polarity protection, built into the transmitter,
protects it against accidental reversal of the
field wiring connections.
Figure 1 HART communication module connection overview
Sensor module connections
Communication module
connections
HART modules
Power Ammeter
123456 87
12 435
+– +–
Non IS installations
14 to 42 V DC
IS installations
14 to 30 V DC
Functional earth
Ammeter connection
for loop current test
SW1:
Reset to
defaults
ON
OFF
SW2:
Write
protection

AWT210 HART 2-WIRE TRANSMITTER | COM/AWT210/HART-EN REV. B 7
HART point-to-point analog signal and power wiring (loop current mode enabled)
Make connections to the HART communication module as
shown in Figure 2.
Do not connect secondary communication device directly
across the power supply.
Figure 2 Analog mode wiring diagram
The signal wiring supplies all power to the transmitter.
The power supply limits are 14.0 to 42.0 V DC
(14 to 30 V DC for agency certified installation).
The minimum supply voltage is determined by the loop
resistance (R) as follows:
• minimum supply = 14.0 (volt) + 0.022 (amps) x R (ohms)
Load resistance must include any meters external to the
AWT210 transmitter, the wiring and the system input.
IMPORTANT (NOTE)
The equation for minimum supply voltage is based on
a maximum output current of 20 mA. In some cases
such as fail high or process variable over range
condition, the output current limits to 21.5 mA. To
support these cases, use 0.0215 instead of 0.020.
A secondary communication device can be connected anywhere
there is access to the signal wires as long as it is not connected
directly across the power supply.
IMPORTANT (NOTE)
Only one secondary device can communicate on the
loop at any given time.
+
+
+
–
–
–
+–
System power
supply
High impedance
controller,
recorder
or control
system
HART compatible
hand-held terminal
(secondary
communication device) 250 W

8AWT210 HART 2-WIRE TRANSMITTER | COM/AWT210/HART-EN REV. B
… 4 Installation
Multi-drop mode (digital) signal and power wiring (loop current mode enabled)
Refer to Figure 3 for a typical wiring configuration for multi-
drop installations. In the multi-drop mode of operation, the
analog 4 to 20 mA is not used. Instead the transmitter draws a
constant 3.6 mA of current to maintain operation.
• Do not connect secondary communication device directly
across the power supply.
• Add 1 V DC to all minimum supply voltage values if using the
TEST connections.
• The maximum number of transmitters is 63.
+
+
–
–
+–+–
+–+–
System power supply
High impedance
controller, recorder
or control system
HART compatible hand-
held terminal (secondary
communication device) 250
ohms
Transmitter 1Transmitter n
Figure 3 Digital mode wiring diagram
In the multi-drop mode, the process variable signal of each
transmitter on the signal bus is digitally polled. The primary
communication device sequentially polls each transmitter
output on the bus. Each transmitter has its own unique
address that is assigned during configuration. The address
(1..15) allows the primary communication device to distinguish
between transmitters on the bus.
Each transmitter on the bus is wired from the primary
POWER (SIGNAL) terminals of the AWT210. Connect all
transmitters on the bus in parallel.
The minimum power supply voltage required for the loop is
typically determined by:
• minimum voltage supply = 14 V + (0.004 A x R)
• minimum current supply = 0.004 A x T
Where:
• R is the Load Resistance in ohms, and
• T is the number of transmitters on the bus
IMPORTANT (NOTE)
The equation for minimum supply voltage is based on
a maximum output current of 4 mA. In some cases
other transmitters may use a multi-drop minimum
current of greater than 4 mA. Consult the vendor
product instruction for multi-drop current values for
other equipment on the bus..
The load resistance must include the system input resistance
and the resistance of the wire. Analog meters or measurement
devices should not be connected to the bus since the
transmitters on the bus are not delivering an analog process
variable.
A secondary communication device can be connected anywhere
there is access to the signal wires, as long as it is not connected
directly across the power supply.
IMPORTANT (NOTE)
Only one secondary device can communicate on the
loop at any given time.
Sensor wiring and grounding
Refer to the AWT210 Operating Instructions (OI/AWT210-EN)
for sensor wiring and grounding instructions.

AWT210 HART 2-WIRE TRANSMITTER | COM/AWT210/HART-EN REV. B 9
5 Appendix
Introduction
This appendix contains descriptions of the HART commands
available through the HART universal, common practice and
device specific command sets.
Device-specific command details such as data bytes and
response codes are described in the AWT210 HART field device
specification (COM/AWT210/HART-FDS-EN)
Supported HART commands
The following HART Commands are supported on the AWT210.
Universal HART commands
Command Description
Read Dynamic Variables And Loop Current PV,SV,TV
Read Primary Variable Transducer Information
Table 1 Universal HART commands
Common practice HART commands
Command Description
Write PV Damping Value *
Write PV Range Values *
Set PV Upper Range Value *
Set PV Lower Range Value *
Enter/Exit Fixed Current Mode *
Perform Self-Test *
Perform Device Reset *
Write PV Units *
Trim Loop Current Zero *
Trim Loop Current Gain *
Read Additional Device Status
Write Number of Response Preambles *
Lock Device *
Read Lock Device State
*Requires HART login (Command 168) to Advanced level or higher if HART login is enabled
via Configuration -> Advanced-> Device Setup -> Security -> HART Login -> Enabled
Table 2 Common practice HART commands
1AWT does not support device variables, only dynamic variables. Hence,
Command 9 returns a response code of 14 (Dynamic Variables returned for
Device Variables) as required by the HART specification. However, this return
value is seen as an error by Simatic PDC software. This response code may
be turned off in the device by enabling PDM compatibility at the following
menu: Device Setup > PDM Compatibility > Enable.
Device-specific HART commands: general
Command Description
Login to Service Level
Read Board Object *
Write Object *
Read Memory *
Write Memory *
Reset Software Write Protection
Read Revision
Write Current Alarm Selection
Read Write Protection
Write Software Write Protection
Recognize Temperature Compensation Type
Reset to Factory Default
Write Temperature Compensation Type
Read Front End Board Data
Write Manual Temperature Setpoint
Write Reference Temperature
Read PV and Temperature Calibration Slope and Offset
Write PV Calibration Slope and Offset
Write Temperature Calibration Slope and Offset
Log Out HART Service Code
HART Login with Password
Read Diagnosis Masking
Write Diagnosis Masking
Read Diagnosis Simulation
Write Diagnosis Simulation
Write HART Version
Write Sensor Diagnostic Option
Write Temperature Unit
Read Conductivity Units Mode
Write Conductivity Units Mode
Read Condensed Status Mapping Array
*Requires HART Login to Service Level (Command 122)
Table 3 Device-specific HART commands: general
2HART commands that write to the device can be protected with access
control. This is similar to the access control within the device that has
Read Only, Calibrate, Advanced and Service levels.
Access control for HART can be enabled at the following menu:
Device Setup > Security Setup > HART Logging > Password Protected.
If this option is enabled, the user will have to log in with the appropriate
access level password before sending write commands to the device. Please
see details of command 168 in the HART Field Device Specification
document for AWT210.

10 AWT210 HART 2-WIRE TRANSMITTER | COM/AWT210/HART-EN REV. B
… 5 Appendix
…Supported HART commands
Device--specific HART commands:
Two Electrode conductivity (TE)
Command Description
Write Measurement Type
Write Cell Constant
Read Concentration Configuration
Write Concentration Display Text
Read Temperature Sensor and Compensation
Configuration
Write Automatic Temperature Compensation Option
Write Temperature Compensation Coefficient
Read Temperature Compensation Curve
Write Temperature Compensation Curve
Read Concentration Curve
Write Concentration Curve
Reset PV and Temperature Calibration
Calibration
Read Calibration Mode and Status
Write Calibration Mode and Status
Write Calibration Value
Read Calibration Progress and Error Status
Read Factory Calibration Parameters
Write Factory Calibration Parameters
Read Factory Calibration Slope and Offset
Read PV Sensor Config
Table 4 Device--specific HART commands:
Two Electrode conductivity (TE)
Device-specific HART commands:
Toroidal Conductivity (TC)
Command Description
Read PV Sensor Configuration
Write Measurement Type
Read Concentration Configuration
Write Concentration Display Text
Read Temperature Sensor and Compensation
Configuration
Write Automatic Temperature Compensation Option
Write Temperature Compensation Coefficient
Reset PV and Temperature Calibration
Read Calibration Mode and Status
Write Calibration Mode and Status
Write Calibration Value
Read Calibration Progress and Error
Read Factory Calibration Parameters
Write Factory Calibration Parameters
Read Factory Calibration Slope and Offset
Write Concentration Solution
Table 5 Device-specific HART commands:
Toroidal Conductivity (TC)

AWT210 HART 2-WIRE TRANSMITTER | COM/AWT210/HART-EN REV. B 11
Device-specific HART commands:
Four Electrode Conductivity (EC)
Command Description
Read PV Sensor Configuration
Write Measurement Type
Write Sensor Group
Read Concentration Configuration
Write Concentration Solution
Write Concentration Text Display
Read Temperature Sensor and Compensation
Configuration
Write Automatic Temperature Compensation Option
Write Temperature Compensation Coefficient
Reset PV and Temperature Calibration
Read Calibration Mode and Status
Write Calibration Mode and Status
Write Calibration Value
Read Calibration Progress and Error
Read Factory Calibration Parameters
Write Factory Calibration Parameters
Read Factory Calibration Slope and Offset
Table 6 Device-specific HART commands:
Four Electrode Conductivity (EC)
Device-specific HART commands:
pH
Command Description
Read PV Sensor Configuration
Write Measurement Type
Write pH Sensor Type
Write Reference Impedance Limit
Write Isopotential pH and Asymmetric Potential
Read ION Concentration Configuration
Write ION Concentration Configuration
Read Temperature Sensor and Compensation
Configuration
Write pH Solution Coefficient Value
Write millivolt Solution Coefficient Value
Read Two Point Manual Calibration Parameters
Write Two Point Manual Calibration Parameters
Reset PV and Temperature Calibration
Calibration
Read PV Calibration Slope and Offset Alarm Limits
Write PV Calibration Slope and Offset Alarm Limits
Read Auto-Buffer Calibration Parameters
Write Standard Buffer Type
Read Calibration Mode and Status
Write Calibration Mode and Status
Read Temperature Compensated Buffer Value
Write Calibration Value
Read Calibration Progress and Error
Read Factory Calibration Parameters
Write Factory Calibration Parameters
Read Factory Calibration Slope and Offset
Write Linearity/Function Generator
Read Linearity/Function Generator
Table 7 Device-specific HART commands: pH
Acknowledgements
• Fieldbus is a registered trademark of the Fieldbus Foundation
• HART is a registered trademark of the FieldComm Group
• Modbus is a registered trademark of Schneider Electric USA Inc.
• PROFIBUS is a registered trademark of PROFIBUS organization.

COM/AWT210/HART-EN Rev. B 05.2019
—
ABB Limited
Measurement & Analytics
Oldends Lane, Stonehouse
Gloucestershire, GL10 3TA
UK
Tel: +44 (0)1453 826 661
Fax: +44 (0)1453 829 671
Email: instrumenta[email protected]
ABB Inc.
Measurement & Analytics
125 E. County Line Road
Warminster, PA 18974
USA
Tel: +1 215 674 6000
Fax: +1 215 674 7183
abb.com/measurement
—
We reserve the right to make technical changes or modify the contents of this document
without prior notice. With regard to purchase orders, the agreed particulars shall prevail.
ABB AG does not accept any responsibility whatsoever for potential errors or possible lack
of information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained
therein. Any reproduction, disclosure to third parties or utilization of its contents – in
whole or in parts – is forbidden without prior written consent of ABB.
© ABB 2019 3KXA877202R4001
Other manuals for AWT210
3
Table of contents
Other ABB Transmitter manuals
Popular Transmitter manuals by other brands

Pfeiffer Vacuum
Pfeiffer Vacuum RPT 100 operating instructions

Cooper
Cooper Scantronic 735rEUR-50 installation guide

JTS
JTS IN-64TH instruction manual

Digi
Digi Connect WS Hardware reference manual

Auto Mate
Auto Mate 7142A quick start guide

Ameri-King
Ameri-King AK-451 Series Installation and operation manual