the two wires. The output is connected with the 2×1.5mm2 wire to the No.8, 9 terminals of
AIM-M100, which is not allowed for grounding.
(5) In order to reliably monitor the grounding insulation of the isolation power system, the No.4, 5
terminals of AIM-M100 insulation monitor should be reliably connected to IT system (which can be
connected in parallel to the output terminal of the isolation transformer) with 2×1.5mm2multicore
copper wires, and the No.13, 14 terminals should be respectively connected to the on-site
equipotential terminals (or the grounding terminals in the isolation power cabinet) with two
independent 4mm2yellow-green grounding wires.
(6) When AID150 centralized alarm and display instrument monitors multiple sets of AIM-M100 at
the same time, the communication line should be connected by hand (that is, after the communication
line of the previous meter is connected to the communication terminal of this meter, it is led out from
the terminal of this meter and connected to the communication terminal of the following table). One
matching resistance shall be connected between the two communication terminals at the head and end
of RS485 bus, and the resistance recommended and attached with the goods. The resistance is 120Ω.
The 15 and 16 terminals of AIM-M100 are also RS485 communication terminals, which are used to
communicate with the upper computer. If there is no upper computer, there is no wiring.
5.5 Considerations
(1) Medical IT system insulation monitoring and fault locating seven pieces of products should be
centrally installed in the isolation power cabinet except for AID150. If the field space is too limited to
apply the isolation power cabinet, the isolation transformer can be installed separately, but should not
be too far away from the insulation monitor and the field load.
(2) The installation of wiring should strictly follow the wiring diagrams, which should preferably
use the pressure connection with the needle-type fittings, and then insert into the corresponding
terminal of the instrument and tighten the screws to avoid the abnormal work conditions of instrument
caused by loose connection.
(3) The grounding wire of the instrument and the transformer shall be reliably connected with the
equipotential terminals in the field. When applying the isolation power cabinet, it should be connected
to the grounding terminals in the isolation power supply cabinet, and then to the equipotential
terminals in the field.
(4) The current input of AIM-M100 medical intelligent insulation monitoring instrument should use
a matching AKH-0.66P26 type current transformer. It is recommended to use pressure connection
with U-type indenters during wiring operation, and then connect to the CT terminal. Do not directly
use the bare head connection, for the considerations of reliable connection and easy disassembly.
Before removing the wiring, the CT primary circuits must be cut off or the secondary circuits must be
short connection.