9/ 11
medical accident caused by the circuit breaker's difficulty in closing or the interruption in the operation
process.
5.4.4 Please read this manual carefully before use. When it comes to insulation monitor and insulation
fault locator products in-cabinet, refer to 076 Intelligent Insulation Monitoring Products of Medical IT
System (Five-piece) Installation and Operation Manual and 077 Insulation Monitoring and Fault
Location Products of Medical IT System (Seven-piece) Installation and Operation Manual.
6 Operation and Usage
After the product is installed, the following operations should be done:
If the GGF series isolation power cabinet is equipped with a dual power automatic transfer switch,
ensure the reliability of the dual power supply. The power cabinet should be able to quickly switch to
the standby power supply when the current working power supply is cut off. For example, if the
current working power supply is power A and the standby power supply is power B, cut off power
supply A and switch on power supply B quickly to ensure continuous power supply.
The GGF series isolation power cabinet is connected to the input line with the normal rated voltage,
and the load switch, residual current protector, circuit breaker and other components can be switched
off in turn. The circuit breaker should be correctly switched off.
After the GGF series isolation power cabinet is powered on, check whether the display data of the
instrument on the cabinet is normal. The total inlet line measurement can indicate the current voltage
and current value (GGF-O series cabinet); Insulation monitoring instrument should show the current
IT system insulation resistance value, and no alarm feature.
After the above confirmation, the GGF series isolation power cabinet can be put into use.
In the process of use, if the external alarm display instrument is found to emit abnormal alarm, you
can find the corresponding isolation power cabinet according to the alarm information, confirm the
alarm type, and then carry out load disconnection operation until the insulation monitor recovers
normal.
7 Typical Applications
The GGF series isolation power cabinet is mainly applied to the operating room and ICU power
distribution system. The typical system diagram is as follows: