3.When both Zone Status LEDs are out, do the following,and observe the appropriate LED light in each case:
a. Open the fast response loop momentarily. The Basic Zone LED should light while the loop is open.
b. Open the normal response loop momentarily. The Basic Zone LED should lightagain.
c. Open the entry/exit loop momentarily. The Entry/Exit Zone LED should light.
d. Short the fast and nonal loops momentarily. The Basic Zone LED should light momentarily.
e. Short the normal and entry/exit loops momentarily/The Entry/Exit LED should light momentarily.
4.fast the Bell(s) and Standby Battery
by depressing the BELL TEST switch momentarily. The bell(s) should ring
while the switch is depressed. Any devices connected to the dry contacts
will
not be activated.
Note:
The battery may not be fully charged. Ifthis test is tried with a low battery, there will not be enough power to
ring the bell. Let the unit charge (transformer plugged in) for
at
least one half hour if the battery is low.
5.Test the Emergency (Panic) Circuit
by momentarily shorting terminals 7 and 8 or tripping an emergency switch.
The bell(s) should ring only as long as the short remains and any devices connected to the dry contacts
will be activated.
6. Turn the system ONand simulate leaving the premises
by following the procedure given in the OPERATION
section.
.Note:
If an alarm is tripped during testing, the bell(s) can be silenced by turning the keyswitch to OFF.
7. Simulate entering the premises and turn the system OFF
by following the procedure given in the OPERATION
section.
OPERATION:
Note:
The Zone Status LEDs on the panel will go on and off as the protective loops open and close during normal operation
of doors, windows, etc., while the system is OFF.
WhenTurning System ON:
1. A.C. power LED should be lit at all times.
If out, AC. failure to unit is indicated.
2.Zone Status LEDs should
be off. If lit, protective loop is not set properly.
CAUTION:
If either Zone Status LED is lit, turning the keyswitch
ONwill cause an alarm
immediately in the case of
the Basic Protective Zone or after 90 seconds (exit plus entry delay time) for the Entry/Exit Zone (60 seconds if the
4B
WHfTE jumper has been cut). In the latter case, the No. 706 Mini-Howler (if installed) will sound a warning immedi-
ately that an alarm can be avoided if the keyswitch is returned to OFF before 90 (60) seconds have expired.
3. Depress BELL TESTSwitch
to test bell, standby battery and power supply.
IMPORTANT:
For continual assurance that bell, battery and power supply are in proper working order,
regular
performance of BELL TEST is advised.
This is particularly important when remote arm/disarm
keyswitches without LEDs.are,used.
4. Turn Keyswitch ONto arm system.
Leave via entry/exit door within 45 (30) seconds.
WhenTurning System OFF:
1. Entar only through entry/exit door.
If a No. 706 Mini-Howler has been installed, it will sound during the entry
delay period.
2. Note if ALARM MEMORYLEDon panel is lit
(it will be if an alarm has taken place).
3.Turn keyswitch
Off before end of entry delay period.
ACCESSORIES:
IMPORTANT: Accessories may be used, provided they do not result in a total 6V. DC continuous auxiliary load of more
than 220 ma (except as noted below) being drawn from the panel.
Total current on ALARM (including
alarm sounding device) should not exceed 2amperes.
Instaad of using a keyswftch
to control the panel, up to 4 remote stations (e.g.: No. 214.246,246R or 5248) may be
usedviaa No. 244 Remote Station Adapter
(each remote station shows system status via a single LED).
Current
Draw, No. 244with 1remote station: 11.5ma (each add’1remote station :9.5ma).
Alternatively, the following are available for coded pushbutton control
of the No. 1025:
No.2l6 Two Wire Digital Station with Panic Circuitry
(up to
4
can be used via a
No. 216Adapter). Current Draw,
No.216with 1No. 215: 11.1ma (each add’1No. 215:9.1ma).
No.227 Single Button Digital Remote Station
(up
to 5
can
be
used, via a
No.228Adapter). Current Draw, No. 226
with 1No. 227: 14ma (each add’1No. 227: 6 ma).
No.5241‘Self-contained Digital Remote Station with Panic Circuitry
(single unit only
can
be
used).Current Draw:
12ma. 509
500