ADTRAN DDM+ H2TU-C User manual

JOBAID
61222003L2-22A
0104
DDM+ H2TU-C
CLEI: T1L3X5BA_ _
STATUS LEDs
STATUS ●RED Alarm on the H2TU-C loop, H2R loop, DSX or DS1 interface.
✷FLASHING Signal Quality of 0 or No Sync on the loop.
●AMBER Loopbacks active.
✷FLASHING In-band loopbacks armed.
●GREEN Functioning properly.
✷FLASHING ES, SES, or BPV detected at either DSX or DS1 interface.
RS-232 DB-9 CONNECTOR
■Used to access the HDSL2 utilities menu tree via VT100 emulation software such as
Terminal, Hyper Terminal – Private Edition, and ProComm Plus.
■There are two types of terminal emulation modes, Manual and Real-Time. To toggle
between the two modes, type “CTRL” and “T.” To update the screens while in Manual
Mode, press the space bar 3 times. Real-Time Update Mode is the default.
■Provision terminal port as follows:
Data Rate — 1.2 kbps to 19.2 kbps
Asynchronous Data Format — eight data bits, no parity (none), one stop bit, and no
flow control.
■Hardware Flow Control – disabled.
■When using a PC with terminal software, be sure to disable any power saving programs.
COMPLIANCE CODES
This product is intended to be installed in an enclosure with an Installation Code (IC)
of “B” or “E” and in Restricted Access Locations only.
WARRANTY
Warranty for Carrier Networks products manufactured by ADTRAN and supplied under
Buyer’s order for use in the U.S. is ten (10) years. For a complete faxback copy of
ADTRAN’s U.S. and Canada Carrier Networks Equipment Warranty: (877) 457-5007,
Document #414.
CIRCUIT BOARD 6-POSITION DIP SWITCH – SW1
Provisions the unit. (Default settings are in bold.)
SW1-1
■Selects line coding to AMI or B8ZS
SW1-2
■Selects T1-framing to FRAMED or UNFRAMED1
SW1-3
■Selects T1-framing to SF or ESF
SW1-4
■ENABLES or DISABLES the NIU loopback
SW1-5
■ENABLES or DISABLES the loopback timeout2
SW1-6
■ENABLES or DISABLES the shelf alarm
1UNFRAMED operation ignores the setting of SW1-3
2Default timeout setting is 20 minutes when loopback timeout is ENABLED
CIRCUIT BOARD 5-POSITION ROTARY SWITCH – SW2
Sets the DSX-1 Line Build Out (LBO). (Default settings are in bold.)
■0 — 0-133 feet of LBO
■133 — 133-266 feet of LBO
■266 — 266-399 feet of LBO
■399 — 399-533 feet of LBO
■533 — 533-655 feet of LBO
DDM+ H2TU-C
Code Input Output
Installation Code (IC) A —
Telecommunication Code (TC) — X
Power Code (PC) F C
C A U T I O N
C A U T I O N
!
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
For a complete Installation and Maintenance faxback document: (877) 457-5007, Document #695. Please have your fax number available.
SW2
0
0
133
DSX-1 LBO
533 399
266
2
7
1
4
6
3
5
INDICATIONS AND PROBABLE CAUSES
Front Panel or Circuit Parameters Indicate Abnormal Operation
Connect a terminal or PC to the RS-232 (DB-9) craft interface located on the faceplate. The
terminal must be VT100 or compatible and set for 1.2 to 19.2 kbps, 8 data bits, no parity, 1
stop bit, and no flow control. Select “3” from the ADTRAN HDSL2 Main Menu Screen and “2”
from the Span Status Screen:
■Is signal quality fluctuating (this would occur when real-time mode is active)?
■Is ATTEN (pulse attenuation) > 30 dB?
■Are there any errors counting on the ES, SES, or UAS registers?
If the above conditions do not exist, the circuit should provide quality service; however, if any
of the above conditions exist, a cable problem or excessive loss situation is probable and
more detailed cable testing should be done to verify all HDSL2 Loop Specifications are met.
These conditions may also reflect intermittent cable faults or excessive noise impairments. If
intermittent faults or noise impairments are suspected, select “5” from the HDSL2 Main
Menu and review the Performance History Screen.
Front Panel Indications Under Normal Operation
STATUS ●Green
Circuit Parameters Under Normal Operation
■LOSS < 30 dB
■Good signal quality with no fluctuation
■All HDSL2 Deployment Guidelines are met
HDSL2 DEPLOYMENT GUIDELINES
■Cable pairs must be non-loaded
■Total bridged tap < 2.5 kft
■No single bridged tap >2 kft
■196 kHz insertion loss ≤35 dB
■Pulse attenuation (loss on HDSL2 Span Status Screen) ≤30 dB
■Maximum loop resistance is 900 Ω
■Impulse noises < 50 dBrn as measured using a 50 kb filter
■Wideband noise ≤31 dBrn as measured using a 50 kb filter
For further information regarding deployment guidelines and applications, reference
ADTRAN’s Supplemental Deployment Information for HDSL/HDSL2 document,
P/N 61221HDSLL1-10.
HDSL2 TROUBLESHOOTING GUIDE
PRICING AND AVAILABILITY 800.827.0807
TECH SUPPORT 800.726.8663
RETURN FOR REPAIR 256.963.8722
www.adtran.com
61222003L2-22A
HDSL2 Loopback Control Codes
Name Code Comments
Arming (In-band) 11000 Signal sent in-band or over ESF data link. HDSL2 elements in disarmed
Arming (ESF) 0001 0010 1111 1111 state make transition to armed state. Detection of either code results in
(12 FF Hex) Smartjack loop up, if NIU loopback is enabled.
Activation 1101 0011 1101 0011 Signal sent in-band. HDSL2 elements in armed state make transition to
(H2TU-C) (D3D3 Hex) loop up state. Loop up state timeout is programmable from the H2TU-C.
Activation 1100 0111 0100 0010
(H2TU-R) (C742 Hex)
Deactivation 1001 0011 1001 0011 Signal sent in-band. HDSL2 element loop-up state makes transition to
(9393 Hex) armed state.
Disarming (In-band) 11100 Signal sent in-band or over ESF data link. HDSL2 elements in any state
Disarming (ESF) 0010 0100 1111 1111 make transition to disarmed state.
(24FF Hex)
Arming Timeout N/A 2 Hours
Loop-up Timeout N/A HDSL2 element in loop up makes transition to armed state.
Programmable from H2TU-C: None, 20, 60, or 120 minutes.
Loopback Timeout 1101 0101 1101 0110 Signal sent in-band. Sets Loopback Timeout to NONE. Timeout will
Override (D5D6 Hex) return to previous value when pattern is removed. Arming pattern
(11000) must precede this pattern.
Span Power 0110 0111 0110 0111 Signal sent in-band. Disables span powering of remotes. Span power
Disable (6767 Hex) will return when pattern is removed. Arming pattern (11000) must
precede this pattern.

Other manuals for DDM+ H2TU-C

3

This manual suits for next models

1

Other ADTRAN Switch manuals

ADTRAN 1xN Instruction Manual

ADTRAN

ADTRAN 1xN Instruction Manual

ADTRAN NetVanta 900 Series User manual

ADTRAN

ADTRAN NetVanta 900 Series User manual

ADTRAN HTU-C M User manual

ADTRAN

ADTRAN HTU-C M User manual

ADTRAN NetVanta 1224 User manual

ADTRAN

ADTRAN NetVanta 1224 User manual

ADTRAN NetVanta 1560-24-740W User manual

ADTRAN

ADTRAN NetVanta 1560-24-740W User manual

ADTRAN NetVanta 1560-48 User manual

ADTRAN

ADTRAN NetVanta 1560-48 User manual

ADTRAN NETVANTA 1224 POWER OVER ETHERNET Series User manual

ADTRAN

ADTRAN NETVANTA 1224 POWER OVER ETHERNET Series User manual

ADTRAN NetVanta 1224STR PWR User manual

ADTRAN

ADTRAN NetVanta 1224STR PWR User manual

ADTRAN OC-3c/STM 1 User manual

ADTRAN

ADTRAN OC-3c/STM 1 User manual

ADTRAN NetVanta 1224R User manual

ADTRAN

ADTRAN NetVanta 1224R User manual

ADTRAN 1200655L1 User manual

ADTRAN

ADTRAN 1200655L1 User manual

ADTRAN D4 OCU DP (ETR) D4-OCU Instruction Manual

ADTRAN

ADTRAN D4 OCU DP (ETR) D4-OCU Instruction Manual

ADTRAN NetVanta 1638 Manual

ADTRAN

ADTRAN NetVanta 1638 Manual

ADTRAN NetVanta Series User manual

ADTRAN

ADTRAN NetVanta Series User manual

ADTRAN HDSL HTU-C/DDM+ User manual

ADTRAN

ADTRAN HDSL HTU-C/DDM+ User manual

ADTRAN NetVanta 1524ST User manual

ADTRAN

ADTRAN NetVanta 1524ST User manual

ADTRAN NetVanta 1748F Series Manual

ADTRAN

ADTRAN NetVanta 1748F Series Manual

ADTRAN ATLAS 550 User manual

ADTRAN

ADTRAN ATLAS 550 User manual

ADTRAN NetVanta 1235P User manual

ADTRAN

ADTRAN NetVanta 1235P User manual

ADTRAN D4 TRDDB User manual

ADTRAN

ADTRAN D4 TRDDB User manual

ADTRAN 1534/1544 User manual

ADTRAN

ADTRAN 1534/1544 User manual

ADTRAN /FXS/FXO 850 Quad User manual

ADTRAN

ADTRAN /FXS/FXO 850 Quad User manual

ADTRAN NetVanta 1560-08-65W User manual

ADTRAN

ADTRAN NetVanta 1560-08-65W User manual

ADTRAN SDX 8110-24-740W User manual

ADTRAN

ADTRAN SDX 8110-24-740W User manual

Popular Switch manuals by other brands

ATEN Master View ACS-1208A user manual

ATEN

ATEN Master View ACS-1208A user manual

Avaya ERS 3500 Quick setup guide

Avaya

Avaya ERS 3500 Quick setup guide

SICK MLP1 operating instructions

SICK

SICK MLP1 operating instructions

Kramer VS-81H user manual

Kramer

Kramer VS-81H user manual

Ubiquiti UniFi USW-16-POE quick start guide

Ubiquiti

Ubiquiti UniFi USW-16-POE quick start guide

socomec STATYS XS 16A Installation and operating manual

socomec

socomec STATYS XS 16A Installation and operating manual

Korenix JetNet 3808G Series user manual

Korenix

Korenix JetNet 3808G Series user manual

Danfoss KP 34 installation guide

Danfoss

Danfoss KP 34 installation guide

Freedom9 freeStor 4P user manual

Freedom9

Freedom9 freeStor 4P user manual

Dell S4048-ON Configuration guide

Dell

Dell S4048-ON Configuration guide

CYBEX AUTOVIEW COMMANDER - Installer/user guide

CYBEX

CYBEX AUTOVIEW COMMANDER - Installer/user guide

Econ 21440 Installation & operation manual

Econ

Econ 21440 Installation & operation manual

Sams HDS-4 User manual for use and maintenance

Sams

Sams HDS-4 User manual for use and maintenance

Dolphin ESRPZ installation guide

Dolphin

Dolphin ESRPZ installation guide

Kohler RSB Series Operation

Kohler

Kohler RSB Series Operation

Southern States ES-1 Installation instructions manual

Southern States

Southern States ES-1 Installation instructions manual

HDanywhere MHUB 100A Product guide

HDanywhere

HDanywhere MHUB 100A Product guide

Ruijie RG-S6000C-48GT4XS-E-AC DCN Hardware  installation and reference guide

Ruijie

Ruijie RG-S6000C-48GT4XS-E-AC DCN Hardware installation and reference guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.