Advantage Controls MegaTrom XSi User manual

1
Web Monitor
Product Manual
Important Safety Instructions
Read all warnings and instructions in
this manual. Save all instructions.
Advantage Controls
4700 Harold-Abitz Dr.
Muskogee, OK 74403
Phone: 800-743-7431
Fax: 888-686-6212
www.advantagecontrols.com
09/2021
C US

2
MegaTronXSi Web Monitor
Instruction & Maintenance Manual
Table of Contents
Contents Page
I. Introduction................................................................................. 3
Model Numbering ....................................................................... 3
Description of Unit / Control Functions....................................... 3
II. Installation .................................................................................. 4
Mounting Instructions ................................................................. 4
Electrical Wiring.......................................................................... 4
Wiring Diagrams......................................................................... 4
III. Front Panel Description.............................................................. 7
IV. System Operation Overview....................................................... 8
V. Menu Navigation......................................................................... 8
VI. Web Advantage Setup.............................................................. 17
VII. USB Functions.......................................................................... 20
VIII. Troubleshooting........................................................................ 23
IX. Warranty & 30 Day Billing Memo Policy ................................... 23
FCC Warning
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in
strict accordance with the manufacturer’s instruction, may cause interference to radio communications. It
has been type-tested and found to comply with the limits for a class A computing device pursuant to subpart J
of part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when
operated in a commercial or industrial environment. Operation of this equipment in a residential area is likely
to cause interference in which case the user, at his own expense, will be required to take whatever measures
necessary to correct the interference.

3
I. Introduction
The MegaTronXSi microprocessor based controllers are designed to provide a wide range of web monitoring
functions. The controller is programmed through a front panel keypad or via the internet through WebAdvantage
and can be congured to provide a customized web monitoring for your application. Your particular unit’s
functions can be determined by comparing the units model number to the Model Numbering table listed below.
Model Numbering
MegaTronXSi units have several base system control functions and unit optional features. Your unit may be
supplied with one or more of the features described in this manual. To determine what features apply to your
unit check the model number label located on the controller enclosure.
Options
A- Conduit connection
A3 - Liquid tights and 220-240 VAC relay card
A4 - Prewired USA power cord, dry contact only relay card
A9 - Prewired USA power cord; no relays
A24 - Prewired USA power cord; no relays with 24 VDC power supply in housing
H11 - Communications card with Modbus via ethernet instead of standard comm card
H21 - Communications card with BACnet via ethernet instead of standard comm card
L- (5) additional digital alarm inputs
N4 - (4) 4-20mA isolated inputs
N8 - (8) 4-20mA isolated inputs (O4 is not available with the N8 option)
O4 - (4) 4-20mA isolated outputs
W4 - (4) totalizing ow meter inputs with volume tracking and alarming
Y- ETL agency listing
Z- Black cover instead of clear
Model numbers start XSI followed by optional features. Example: XSI-N8W4.
Notice: Your unit may not have all features and functions described in this manual. This list represents our
most popular XSi options, additional option codes are available. Consult representative for more details.
Description of Unit
MegaTronXSi monitors provide WebAdvantage internet based remote monitoring, contolling and reporting
for a wide range of analog and digital appliations.
Control Functions
Each of these control functions are based on a 4-20mA analog input and will include user settable relay control
settings along with a High and Low Alarm setting and Limit Timer. Each control function can control relay
output. When the reading reaches (rises above or falls below) the Set Point the control relay is activated until
the reading changes by the Dierential amount.

4
II. Installation
Mounting Instructions
Select a mounting location that provides the operator easy access to the unit and a clear view of the controls
through the cover of the controller. The location should be convenient to grounded electrical connections, the
needed sample line plumbing, and should be on a stable vertical surface.
Electrical Wiring
The MegaTron XSi monitor has an internal regulated fused power supply that will operate o of 90 to 250
VAC at 47 to 63 Hz on the incoming wiring. Each output relay is individually protected with a replaceable fuse.
Relay outputs will equal incoming line voltage.
CAUTION
1. There are live circuits inside the controller even when the power switch on the front panel is in
the OFF position. Never open the front panel without rst disconnecting power from the outlet.
Prewired controllers are supplied with an 8 foot, 18 AWG power cord with USA style plug. A #1
Phillips driver is required to open the front panel.
2. Low voltage signal wires (mA, digital input, water meter, etc.) should never be run
in conduit with high voltage (like 115VAC) wires.
3. Never attempt to land connections to the controller without rst disconnecting power from the outlet.
4. Do not block access to disconnect power during mounting and installation.
5. The controller should be connected to its own isolated circuit breaker, and for best
results, the ground should be a true earth ground, not shared. Any attempt to bypass the grounding
will compromise the safety of users and property.
6. The electrical installation of the controller must be performed by trained personnel only and
conform to all applicable National, State and Local codes.
7. Operation of this product in a manner not specied by the manufacturer may result in damage
to equipment or persons.
8. Avoid mounting in locations that expose the controller to direct sunlight, vapors, vibration,
liquid spills or extreme temperatures; less than 0°F (-17.8°C) or greater than 120°F (50°C).
EMI(electromagnetic interference) from radio transmissions and electric motors can also cause
damage or interference and should be avoided.
! !
NOTES:
1. Liquid tight ttings and some labeled signal leads are provided for all signal (low voltage)
connections for both pre-wired and conduit units.
2. Units should be ordered with the appropriate option to provide powered relays designed for the
incoming/outgoing power.
Pre-Wired
Pre-wired units are supplied with a 16 AWG cable(s) with 3-wire grounded USA 115 volt plug for incoming
power and 3-wire grounded receptacle cords for all control relay outputs also 16 AWG.
Conduit
Conduit units are predrilled at the factory and supplied with conduit knockouts for easy hard wiring to supplied
detachable connectors on the relay card(s) located in the lower section of the controller. Remove the screws
of the lower panel for access.
NOTES:
1. Do not drill holes in upper section of enclosure.
2. All relays provide a N.O. and N.C. output.

5
3. The control function that activates each relay output is pre-congured at the factory
based on the options selected. To change relay activation, see on page 13.
4. Refer to label inside lower panel cover for specic relay board conguration supplied.
5. Relays congured as “dry contact” should only have D.C. voltage ran through them. The GND
connection point replaces the NEU when congured for dry contact. (Example: Use GND and N.O.
for a normally open dry contact relay output.)
!WARNING: If jumpers are not congured for dry contact, line voltage will be supplied.
Relay Card Wiring
Rev. I Relay Card Rev. N Relay Card
FUSE
NET
GRD
N.O.
N.C.
FUSE
NET
GRD
N.O.
N.C.
FUSE
NET
GRD
N.O.
N.C.
FUSE
NET
GRD
N.O.
N.C.
FUSE
POWER INPUT
HNG
Dry contact
115volt relay
NET
GRD
N.O.
N.C.
Ribbon Cable
2
1
10
9
Relay Card Rev.D
See note below
Jumpers above relay can change it
to a dry contact relay. Use GRD and
N.O. for a N.O. dry contact relay.
Powered relay Dry contact
* Relays 6-20 only on
multi-system controllers
INPUT
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
2
1
10
9
NEU
GND
N/O
N/C
NEU
GND
N/O
N/C
NEU
GND
N/O
N/C
NEU
GND
N/O
N/C
Relay
1
Relay
2
Relay
3
Relay
4
Relay
5
R1
R2
R3
R4
R5
Incoming
Power Fuse
15 amp
H N G
Incoming
Power
Relay Fuses
are 3 amp
Relays are shown configured for powered outputs.
[ Change jumpers to these configurations for dry contact. ]
Relays
1-3
Relays
4 & 5
Relay Card
Rev N
R1
R2
R3
R5
MegaTron relay card revision N adds a 15 amp fuse on the incoming power
to the board and small LED’s for each realy to indicate when the motherboard
has called for it to be activated.
Rev N Relay Board
NEU
GND
N/O
N/C
R4
LED
LED
LED
LED
LED
1
2
3
5
4
Motherboard Connections System Card Connections
XSi Megatron Main, Rev.
VDC Output
Connections
Gnd
Gnd
-12
-12
+12
+12
+5
+5
Flow Meter Inputs
+5
Gnd
Gnd
Input 1
Input 2
Input 3
Input 4
LED
Cable
Comm Card
Slot
4-20mA
Slot
Open
System
Slot
Battery
LED
Ground
Digital Input 5
Digital Input 4
Digital Input 3
Ground
Digital Input 2
Digital Input 1
Digital Input Card
Note: Use 22 AWG
(.76 mm) twisted
pair shielded wire
for all of these low
voltage signal
connections.

6
4-20mA Output Card Wiring
A. Isolated Conguration
For isolated 4-20mA outputs an external power source for the loop must be supplied. JP4 and JP5 on the
board must be jumpered for isolated with an external power source supplied to the external VDC input. The
external power source must not exceed 24 volts DC.
B. Non-isolated Conguration
For non-isolated 4-20mA outputs the controller will supply the power for the loop. JP4 and JP5 must be
jumpered for non-isolated and no connections are made to the external VDC points.
NOTES:
1. If multiple outputs are being connected to a single energy management system, the negatives or
commons MUST remain isolated from each other.
2. The power for the mA output loop is always provided by the controller with either isolated or non-
isolated conguration.
4-20mA Input Card Wiring
The 4-20mA input card requires that the external device sending the 4-20mA input signal(s) supply the power
for the loop. The external power source must not exceed 24 volts DC.
IN1+
V+
V+
V+
V-
V-
V-
VEXT+
VEXT-
01+
01-
02+
02-
03+
03-
04+
04-
ISO
LED
ISO ISO ISO
IN1-
IN2+
IN2-
IN3+
IN3-
IN4+
IN4-
J5
J4
mA Outputs are supplied
as non-isolated as shown.
For isolated outputs
J4 and J5 jumpers
as shown to here.
ISO
External
VDC Input
J8
J6
If J4 and J5 are set for isolated an
external DC voltage must be
connected to power the mA
outputs.
If J8 & J6 and set for isolated as
shown instead of the standard non-
isolated the external VDC will be
applied to the other V- and V+
connection points instead of
the controller’s internal 12 VDC
on the V+ and ground on the
V- connections.
ISO
mA
Inputs
1-4
mA
Outputs
1-4
DC
Voltage
Connections
4-20mA Input/Output Card
IN1+
V+
V+
V+
V-
V-
V-
VEXT+
VEXT-
+
-
+
-
+
-
+
-
LED
IN1-
IN2+
IN2-
IN3+
IN3-
IN4+
IN4-
IN8
IN5
IN5
IN6
IN6
IN7
IN7
IN8
4-20mA 8 Input Card

7
III. Front Panel Description
3
4
5
2
1
8
9
0
7
6
SET UP
RUN
CANCEL HELP BACK
ENTER HOME
ACI MEGATRON
SYS1: PROCESS 1
COND 1,400 uS/cm
pH 7.2
PSI 125
SYSTEM OK <HOT KEY>
STATUS
SYS OK
TEMP: 72.1F
Thursday, August 29, 2013 02:24:10 PM (Wk1)
NUMBER Keys- Used to enter new values in the SET UP mode and to access desired sub menus.
UP/DOWN - Used to cycle through text options to nd desired setting.
LEFT/RIGHT - Used to cycle through text or setting options to nd desired setting.
SET UP/RUN - System initializes into RUN mode. Press this key to put the controller in SET UP
Mode and see HOME menu page.
ENTER - Used to log a changed value into program.
HOME - Used to go back to the HOME menu page.
CANCEL - Used to cancel a pop-up screen if no change is desired.
HELP - Used to access help screens.
BACK - Used to go back to last menu screen viewed or clear values keyed in that are not
wanted.
The bottom right box in the RUN screen mode is a hot key that will take you directly to a particular menu
screen. The default is the RELAY status menu, but this can be changed by navigating to the desired
screen and pressing the HELP button. Follow the on-screen instructions to set the new hot key location.

8
IV. System Operation Overview
Operation
MegaTron XSi controllers have two modes of operation, RUN and SET-UP.
RUN - This mode is for normal operation. In the RUN mode the display will show each system’s parameters.
If an alarm is present, the ALARM box will ash how many alarms are activated. No settings may be entered
or changed in the RUN mode. Readings are updated every 6 seconds on the screen while in the RUN mode.
SET-UP - This mode is used to adjust settings and readings on the controller. To access the SET UP mode
from the RUN screen, press the SETUP/RUN key.
V. Menu Navigation
To access the menus press the Set Up / Run key on the front panel. This takes you to the Home menu.
MegaTron XSi controller’s menus are easily navigated by pressing the associated number key next to a
menu box on the screen. Once you have stepped through the sub menus to reach a point at which a value
or selection is made a Pop-up window will appear prompting you to enter a desired value or selection.
NOTE: When entering new numeric values, enter all available digits (characters).
1. Home Menu
From the HOME menu select the desired menu.
The menu name explains what parameters can be
programmed in the menu.
SET POINTS - Setting control set points for mA inputs and digital input alarming.
CALIBRATION - Calibrating mA signals if present.
CUSTOMIZE - Giving the controller, system, mA iputs and all relays a user dened name.
ALARMS - View current alarms.
DAY/TIME - Menu for setting date and time.
CONFIGURE - Menus for conguring passwords, relay activations, setting history interval, contrast.
HISTORY - Allows for view history on board in a graph form.
TOTALIZERS - Menu for conguring ow meter totalizing if present.
RELAYS - Menu for resetting accumulated “ON” times and manual relay activation.
>HOME SETUP<
SETPOINTS DATE/TIME
CALIBRATION CONFIGURE
HISTORY
CUSTOMIZE TOTALIZERS
ALARMS RELAYS

9
2. Set Points
The same basic format is used for dening each available analog mA control parameters.
SET POINTS - For setting the relay set points for the
available analog readings.
NOTE: In the Setpoint pop-up screen the direction (Rising or Falling) of the setpoint can also be set.
Rising setpoints will activate the control relay when the particular reading rises above the setpoint and will
stay activated until the reading comes down by the amount of the dierential. If set for Falling the relay is
activated when the probe reading falls below the setpoint and stays on until the probe reading comes back
up by the amount of the dierential.
2.1 Set Point Options
SET POINT - What reading turns the relay on
DIFFERENTIAL - Amount reading changes by before
the relay is turned o
HIGH ALARM - What reading generates a High alarm.
LOW ALARM - What reading generates a Low alarm.
LIMIT TIMER - What amount of continuous control will
generate a time alarm notice. The relay is locked-out
by this alarm.
DISABLER - One of the digital inputs can be selected
to prevent alarming.
Note: Each alarm value can also be set-up to be displayed or not on the front screen as well as remotely
notied or not if connected to the Web Advantage server.
2.2 Aux Inputs
Auxiliary inputs are the generic digital input status indicators from external dry contacts. From these menus
the user can set if they want each of the status alarms Displayed, Remote Notication, both or none.
Note: Digital inputs can have the direction selected
between OPEN or CLOSED as the alarm polarity. If
set for CLOSED, the input will be in alarm when it
sees a closed contact.
>SYSTEM 1 SET POINTS<
mA OUT
mA IN
AUX INPUTS
>mA INPUT 1 SETPOINT<
SET POINT DISABLER
DIFFERENTIAL
HIGH ALARM
LOW ALARM
LIMIT TIME
>SYSTEM 1 DIGITAL INPUTS ALARM<
ALARM NOTIFICATION DIGITAL 1
DIGITAL 2
DIGITAL 1 = DISPLAY DIGITAL 3
DIGITAL 4
DIGITAL 5

10
2.3 4-20mA Out
Units with a 4-20mA output option will have a menu for setting up the 4-20mA output. The 4mA and 20mA
values can be dened by giving the output proportioning capability. i.e. 4mA = a pH of 6.0 and 20mA = a pH
of 8.0.
SIGNAL SOURCE - Select which mA reading the mA
will use as its reading source.
4 mA VALUE - What the 4mA signal equals
20mA VALUE - What the 20mA signal equals on the
assigned signal sources scale.
3. 4-20mA Output Calibration
4-20mA outputs can be calibrated to ensure that the
output generated by the controller and received by the
external device match. With a volt meter connected
across the out and return wires (see page 7) of the
4-20mA output channel to be calibrated go into the
output’s Low or High calibration.
The number displayed in the Calibration dialog box can
range from 0-4095 with 800 equal to 0 mA output and
4030 equal to 20 mA. This number range of 0-4095 is
the raw digital to analog (D/A) values and is strictly used
for a reference. The D/A numbers you get will vary based
on your installation conditions.
While in the High or Low calibration pop-up screen use
the up and down arrows to change the output value
being read with the volt meter. Adjust the High value
for the 20-mA reading and the Low value for the 4 mA
value.
3.1 4-20mA Input Calibration
4-20mA inputs can be calibrated to ensure that the input seen by the controller from the external device
match. It also allows for setting the 4-20mA input into a number range that relates to the value being read.
Select the Input to be calibrated
>OUT 1 SETUP<
SIGNAL SOURCE
4mA VALUE
20mA VALUE
>CURRENT LOOP CALIBRATION<
OUTPUT 1
OUTPUT 2
>mA OUTPUT 1 CALIBRATION<
HIGH 4030
LOW 800
>mA OUTPUT 1 CALIBRATION<
OUTPUT 1 CAL HIGH
4000
Use Up/Down arrows to change
Use Enter to save value
>CURRENT LOOP CALIBRATION<
INPUT 1
INPUT 2

11
>mA INPUT 1 CALIBRATION<
20mA 5500
4mA 1100
MAX 200
LOW 0
OFFSET FACTORY DEF.
The 20mA and 4mA values are where the controller’s raw analog to digital value is adjusted to match a
20mA (full scale) and 4mA (bottom of scale) signal from the external device inputting the 4-20mA input. The
external device must be connected to the controller and showing either full scale or bottom of scale when
calibrating each. The number shown along with either the 20mA or 4mA while calibrating is the raw A/D value
and is only a reference. A 20mA input should be around 5500 and 4mA around 1100. If the A/D numbers are
not in this range check input device.
The MAX and LOW calibration inputs are for telling the controller what to display for a 20mA input and a 4mA
input. For example, if the input is a drum level sensor monitoring a 55-gallon drum the value for MAX should
be 55 and LOW should be 0. The controller then displays a number automatically ranging between 55 and
0 based on the input value. The units of measure (gallons for example) is set in the Customize menu from
the Home page.
OFFSET - Changes the current displayed value of the 4-20mA input reading to allow for a manual 1pt
calibration of the displayed value.
FACTORY DEFAULT - If the 20mA or 4mA calibration has been incorrectly set (not at 4 or 20) this will reset
the settings back to a factory value for 4 and 20.
4. Customize
This menu allows the user to dene the on-screen name of the unit plus the name of each system and relay.
The user can also setup the Notepad for each system and 4-20mA Input’s name and unit of measurement.
RUN SCREEN - Allows user to select which mA inputs
and/or ow meter inputs are shown on the screen in
RUN mode.
NOTE: When entering values for custom names use
the numerical keys for numbers and the up / down
arrows to scroll through all the characters of a key
board. Press the right arrow to advance the curser after setting a desired value. Press the Help button to
place the last entered character into the new cursor space to speed up the process. The Help button will also
jump advance through the characters.
4.1 Notepad
The Notepad function allows the user to set up a customized manually entered data eld for each system
with ten notepad items. The NOTEPAD is ideal for setting up and storing into the controller’s history the items
typically tested for reporting a service call. The Notepad items come with no names but when an individual
note is selected a menu for setting it appears.
>CUSTOMIZE<
UNIT NAMES
RELAY NAMES NOTEPAD
SYSTEM 1 NAME
mA IN
RUN SCREEN

12
NAME - Pick from a list of dened names or customize
your own.
NUMBER - Set the number range.
UNITS - Set the units of measurement.
ALARMS - Set Hi/Low alarm points and how frequently
a new value is expected to be manually enter via the
History menu.
4.2 mA Inputs
NAME - Name the input.
UNITS - Set the units of measurement.
NUMBER - Set the number range.
4.3 Run Screen
This lets you customize various aspects of the RUN screen.
MAIN SCREEN - Customize what is displayed on the
RUN screen.
SCREENS SHOWN - Pick if the mA input & Aux Flow
screens are scrolled.
CYCLE TIME - The amount of time between screen
scrolls.
5. Alarms
ALARMS - Shows any current alarms.
6. Date and Time Set Up
DATE AND TIME - For setting the date, time, day and
week on the controller.
7. Congure
Provides access to menus to set-up passwords, relay activation, temp scale, display contrast, ow switch,
inputs, history time stamps, factory set-up and system information.
>NOTEPAD SYS 1 NOTE 1<
NAME
NUMBER
UNITS
ALARMS
>mA INPUT 1 CUSTOMIZE<
NAME
UNITS
NUMBER
>RUN SCREEN<
MAIN SCREEN
SCREENS SHOWN
CYCLE TIME
>ALARMS<
SYS 1 ALARMS
>SET DATE AND TIMES<
SET DATE
SET TIME
SET DAY
SET WEEK
Friday May 14, 2005 03:04:56

13
CONTRAST - This screen allows for adjusting the
display contrast.
FACTORY - A factory only menu
TEMP SCALE - Set Celsius or Fahrenheit
HISTORY - Sets the history time stamp interval.
SYS INFO - Tells unit software specics.
7.1 Password
ADMIN PASSWORD - The administrator password
gives access to all menus except factory set up.
USER PASSWORD - The user password allows the
user to access HOME menus that are made available
in USER SET UP.
7.2 Relays
CONFIGURE RELAYS - This menu lets you choose a
Main Action or function (mA input setpoint, etc...) to
activates a relay.
A pop-up screen appears with a list of all available
activation functions to arrow through.
Additional relay logic is available with up to 3 additional Activators and up to 4 Disablers allowing multiple
functions to activate the same relay and multiple functions to prevent the relay from coming on. There is
also a Daily Max amount of time that a relay can be on. If a relay is on for the max amount, it does not
let the relay come on anymore that day. (A 24-hour clock is used for the day with midnight being the start
of the day). The Delay setting is the amount of time a control function must come on before the relay will
react and activate. This is to prevent a relay from chattering on/o if a reading is bouncing around the set
point or alarm.
7.3 History
This menu is used to set the history “time stamp” interval, the water meter daily history starting hour, the
alarm delay period and the USB history save format.
INTERVAL - The amount of time between each history
time stamp for probe readings.
W/M HOUR - The time of day that the daily water
meter history cycle is to start.
ALARM DELAY - The amount of time an alarm has to
be on before it is recognized as an alarm.
SAVE FORMAT - The USB history save format.
>CONFIGURE<
PASSWORD CONTRAST
RELAYS
NETWORK
HISTORY SYS INFO
FACTORY
>CONFIGURE PASSWORDS<
ADMIN PASSWORD
USER PASSWORD
USER SET UP
>RELAY 1 SETUP<
MAIN ACTION DISABLE 1
ACTIVATOR 2 DISABLE 2
ACTIVATOR 3 DISABLE 3
ACTIVATOR 4 DISABLE 4
DELAY DAILY MAX
>CONFIGURE HISTORY<
INTERVAL
W/M HOUR
ALARM DELAY
SAVE FORMAT

14
7.4 Contrast
This menu is used to adjust the contrast of the display.
7.5 Network
The Network menu is used when a controller is being remotely communicated with either a local network
connection or over the internet on the Web Advantage server.
NETWORK - This menu is used for setting up the
remote WebAdvantage communications and is
covered in a separate manual.
http://www.advantagecontrols.com/downloads/pdf/M-WebAdvantage.pdf
Note: The Network card must be RESET after making any
changes to Network setting in order to save changes and
reset communications.
WIFI / DHCP - Enable or disable if available.
SETTINGS - This menu is used to congure a variety
of extended network options.
WIFI NETWORK - This menu is used for choosing the
local wi network and setting the password. This is
covered more in a separate manual.
https://www.advantagecontrols.com/downloads/quicksteps/QS-
MegaTronXS-MT_H_WiFi.pdf
Note: Some choices may not be available if DHCP or WIFI
are disabled in previous NETWORK menu.
7.8 System Information
System information will identify the version of rmware installed in the controller along with the controller’s
serial number.
8. History
The onboard history allows for viewing the history of the mA readings, relay activations, key-pad activity,
calibrations, ow meter hourly and daily logs and alarms for each system present. It is also where Notepad
data is entered and reviewed. An initial overview page is displayed showing your current sample interval, the
calculated number of days the unit can keep probe history for before losing the oldest. The number of sensor
samples and relay/alarm events and Notepad entries currently stored is also displayed.
>NETWORK<
IP Addr: 192.168.001.006
Subnet: 255.255.255.000
Gateway: 192.168.001.253
DNS: 192.168.1.238
ACI Srvr: connect.webadvantage.online:443
MAC: E4.38.F2.00.01.3C
DHCP: ENABLE
WIFI
DIAGNOSTICS DHCP
SETTINGS RESET
>CONFIGURE NETWORK<
IP ADDRESS WIFI NETWORK
IP MASK HTTP REMOTE
GATEWAY FTP
SERVER
HTTP LOCAL

15
NOTE: The history can be reset by going to the
congure menu and entering a dierent sample
interval. After the new sample interval has been set
the onboard history is reset.
8.1 Viewing History
RELAY LOGS - Relay activations displayed in a log
form. Arrow up to advance through the log.
ALARM LOG - Alarm activations in log form.
SENSOR HISTORY - For selecting the parameters
and viewing of a given probe reading’s history in log or
graph form.
EVENT LOG - Displays various activities.
8.2 Notepad Entries
The Notepad section under History is where the user
goes to enter new values for the customized notepad
items. Each individual notepad item’s manually
entered entries are stored in the unit’s history and
can be reviewed in log or graph form after 4 or more
values have been entered.
9. Option W Totalizers
MegaTron XSi controllers with “W” option may have 1 to 4 auxiliary owmeter inputs. These additional
inputs are for tracking various ow meter devices (additional water meters or owmeters in a metering
pump’s discharge tubing). They can also be linked to a system’s water meter input for additional tracking
and alarm capabilities including: bleed ow/no ow, exceeding too much ow in a 12- or 24-hour period.
Units with Auxiliary Flow meter inputs have a Home menu selection for Totalizers. The Totalizer menu has
selections for each of the System Water Meters plus one named Aux Meters.
Select the system water meter to set-up
or go to Aux Meters to set-up the auxiliary ow meters.
>HOME REVIEW<
SYSTEM 1 Sample Time: 5 MIN
(Length 164.62 days)
Sensor Samples
882
Relay/Alarm Events
323
Notepad Entries
>HISTORY<
RELAY LOGS WATER METER
ALARM LOGS
SENSOR HISTORY
EVENT LOG
NOTEPAD
>NOTEPAD: SYS 1 NOTE 1<
ENTER VALUE Total Hardness
LOG 8 Entries
GRAPH
517.2 Hrs to Alarm
>TOTALIZERS<
SYS 1 WATER METER 1
SYS 1 WATER METER 2
AUX METERS

16
9.1 Aux Meters
A unit may have 1 to 4 Aux Meters. These additional inputs are for tracking various ow meter devices
like Advantage Controls’ FloTracker in a metering pump’s discharge tubing. They can also be linked to a
system’s water meter input for additional tracking and alarm capabilities.
Select the Aux Flow Meter to set-up or review.
9.2 Aux Meter Review
A review screen of the current settings is provided with a selection for the Tracking method and the
Settings.
SETTINGS - Access the various settings for the ow
meter.
TRACKING - Provides a pop-up screen to select
either FloTracker or Rate and Volume tracking.
NOTE: Select FloTracker if the aux meter is a
FloTracker. Select Rate and Volume if tracking a
water meter or other batch ow device.
9.3 Aux Meter Settings
PULSE VALUE - Denes the numerical value for a
contact, i.e. 225.
UNITS - Denes the units of measure for a contact,
i.e. Pulses / Ounce.
RESET TOTAL - Resets the totalized count of the
meter.
VERIFY ALARM - If a ow meter is linked to a control
relay the controller will give an alarm if it does not receive a contact or pulse from the aux meter within the
amount of time dened or if it gets a contact when the relay is not on.
RELAY LINK - The relay link informs the particular aux meter input is relevant to the control function that the
selected relay is being driven by. For example, if the aux ow meter is a metering pump’s FloTracker then it
should be linked to the relay that is driven by the feed timer that pump will be controlled by. If the aux meter
is going to be linked to a water meter in a bleed of line, then it should be linked to the relay that is controlling
the bleed o valve.
VOLUME ALARM - If FloTracker has been selected as the Tracking method, an alarm will occur when the
dened VOLUME USED has passed through the ow device.
>FLOW METER<
FM01: AUX METER A
FM02: AUX METER B
FM03: AUX METER C
FM04: AUX METER D
>FLOW METER 1<
TOTAL VALUE: 9966.0 ML
FLOW RATE: 0.0 ML/MIN
CONTACT VALUE: 0.33 ML/CONTACT
LAST RESET ON: 08/25/2006
VOLUME ALARM: 1000 LITERS (24 HOURS)
ALARM NOTIFY: (DISPLAY)
VOLUME: 0.0 LITERS
VERIFY ALARM: 100 SEC (DISPLAY)
RELAY LINK: SYS1 TIMER3
SETTINGS TRACKING
>FLOW METER 1 SETUP<
PULSE VALUE VOLUME ALARM
UNITS RESET VOLUME
RESET TOTAL
VERIFY ALARM
RELAY LINK METER LINK

17
Note: If Rate and Volume tracking has been selected an alarm will occur if the dened MAX VOLUME
amount is measured within the dened TIME CYCLE which can be a 12-or-24 hour period.
RESET VOLUME - Resets the Volume Alarm totalizer.
METER LINK – This selection only shows if the tracking method is Rate and Volume and tells the auxiliary
owmeter input to get its signals from one of the system water meters already wired to the controller’s water
meter inputs. If this is selected no wiring to the auxiliary input is required and the PULSE VALUE and UNITS
settings are auto populated from the particular water meter’s settings.
10. Relays
STATUS - Allows for viewing accumulated relay ON
times, temporary forcing relays ON or OFF or seeing
which relay is on.
RESET - Allows the accumulated run time of a
particular relay to be reset to zero.
FORCE - Allows a relay to be manually forced ON
for a single event from 0-99 minutes. When the event
is over the relay goes back to its normal automatic
control.
In the STATUS view the accumulated ON time is
shown along with the main activator, custom name and
current status:
ON = Relay on by relay activators
OFF = Relay o by normal logic
OFF-T = Relay o for daily max
OFF-D = Relay o for relay disabler
ON-A = Relay activated by activator other than main
action
H-ON = Relay manually forced on
H-OFF = Relay manually forced o
VI. WebAdvantage Setup
WebAdvantage Connection - SETUP CHECKLIST
• Do you have a WebAdv3 USER ID and password? _____ Yes, if ‘No’ proceed to page 18.
• Has your account admin added the device and linked it to your USER ID? _____ Yes, if ‘No’
proceed to page 19.
Congratulations! You are now ready to go online
with WebAdvantage. https://webadvantage.online/
>RELAYS<
STATUS
RESET
FORCE
>RELAY STATUS<
R01: ON 006:30:30
SYS1 COND BLEED
R02: OFF 008:56:35
SYS1 pH
R03: OFF-T 011:00:10
SYS1 TIMER1 INH
R04: OFF 007:00:00
SYS1 TIMER2 BIO1
R05: OFF 008:10:30
SYS1 TIMER3 BIO2
Complete
WebAdvantage
Manual

18
Step 4: Important! Contact our WebAdv3 dept with
your USER ID (email), the device’s serial number and
your phone number.
USER ID (email)
Device Serial #
Phone:
Fax: 918-686-6212
Phone: 918-686-6211
Email: [email protected]
Note: Please allow 24 hours for processing.
Setting Up a USER ID
Before you can view a device, a USER ID
must be setup. Note: If you already have a
USER ID and are just adding a new device,
skip to step 4.
Step 1: Visit https://webadvantage.online
or access the registration form with the QR
code below.
Step 2: Choose Create Account? at the
bottom of the login screen.
Step 3: After completing form click SAVE to
create ID.
Note: The email address you add will be your
USER ID.
USER ID Setup

19
Note: USER ID and Company Access Permissions
are required before you can access a device. For
creating a USER ID see the Setting Up a USER ID
steps on page 17.
Company Access Permissions: If you are not
a part of a company already registered with
WebAdvantage, please contact your company’s
WebAdv account manager for device access.
Step 1: Access the WebAdvantage page at
https://webadvantage.online.
Note: Only company administrators can add, edit,
remove or modify devices, user accounts, history
reports. User account permissions only allow for
viewing of devices.
Step 2: Choose Administration at top of page.
Step 3: Then choose Manage Devices.
Step 4: Enter the device’s Name and Serial
Number. The remaining elds are optional.
Click SAVE to submit.
Admins Only: Add Device and Assign USER ID
Setting Up / Accessing a Device
Note: Please allow up to 24 hrs for processing before
controller shows in device list.
WebAdvantage support can be reached at
918-686-6211 or via email at

20
MegaTron Quick Steps
The XS is capable of transferring information
using a FAT formatted USB drive. The XS has
three main USB functions as detailed in the
following sections:
1. Exporting log data
2.Upgradingrmware
3. Cloning user settings for other XS units
Getting Started
With the controller powered up, plug the USB
drive into the XS USB port. The USB DRIVE
DETECTED pop-up window will appear.
Notes:
• You may be required to enter a password.
• USB drives must be FAT formatted.
• Not all customized names will be saved.
Exporting Log Data
History from an XS controller can be saved to a
USBdriveinoneoftwoleformats:WebAdvan-
tage or generic comma separated (default).
WebAdvantage Format
without header row
Comma Separated Format
with header row
SampleLogData“log.txt”les
To change formats, see Step 2.
Step 1:
To transfer the contents of the XS history logs to the
USB drive, select → History → USB
by using the Arrow
buttons. Then press ENTER.
XS Controller
3 ALARMS! RELAYS
Friday, February 6, 2015 15:50:47 Wk1
SYS1: Towers 1-4
COND: 0 uS/cm
pH: 3.2
ORP: 548 mV
TEMP1: 68°F
WM1: 0.0
WM2: 0.0
FLOW: ON
DR
USB DRIVE DETECTED
--> History --> USB
PRESS UP/DOWN KEYS TO CHANGE
PRESS ENTER TO ACCEPT
Note: Status will be displayed on the screen to show the
percent completed of each log record type. Once the
log is completely stored, the pop-up window will close. If
only a small amount of data is available the screen may
disappearquickly.TheUSBdrivewillnowcontainale
name: example “LOG_AB-1234.TXT”. The AB-1234 will
be the unit’s serial number.
Step 2: Changing the File Format
This is the RUN Screen.
XS Controller
3 ALARMS! RELAYS
Friday, February 6, 2015 15:50:47 Wk1
SYS1: Towers 1-4
COND: 0 uS/cm
pH: 3.2
ORP: 548 mV
TEMP1: 68°F
WM1: 0.0
WM2: 0.0
FLOW: ON
DR
Step 3:
Push the SET UP RUN
button to get this screen. From
here push CONFIGURE
(Button 7) to go to the next
screen.
>HOME SETUP<
SETPOINTS DATE/TIME
CALIBRATION CONFIGURE
TIMERS HISTORY
CUSTOMIZE WATER METER
ALARMS RELAYS
XS Controller - USB Functions
Table of contents
Other Advantage Controls Controllers manuals

Advantage Controls
Advantage Controls MegaTron Operating instructions

Advantage Controls
Advantage Controls MegatronXS Quick start guide

Advantage Controls
Advantage Controls 75 Series User manual

Advantage Controls
Advantage Controls MINI-TROL IF User manual

Advantage Controls
Advantage Controls MICROtron MICRO-C User manual

Advantage Controls
Advantage Controls NanoTron Nano-P Series Operating instructions

Advantage Controls
Advantage Controls MegaTronMT User manual

Advantage Controls
Advantage Controls MicroTron User manual

Advantage Controls
Advantage Controls MegatronXS Operating instructions

Advantage Controls
Advantage Controls MegatronXS User manual