manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. alfatronix
  6. •
  7. Power Supply
  8. •
  9. alfatronix PowerTector PT40 Manual

alfatronix PowerTector PT40 Manual

ASSEMBLY
PROGRAMMING
OPERATING & ASSEMBLY
INSTRUCTIONS
PowerTector PT40 & PT60
T E L: +44 (0) 1202 715 517 • [email protected]m
PACKING CONTENTS
 1 x PowerTector 3 x Screws
 5 x Crimp Connectors 1 x Programming Lead
FEATURES
 12V / 24V Automatic mode selection (12V mode 8<V≤17 , 24V mode
17<V≤35)
 10 Programmable voltage settings
 Supplied with FASTON crimp connectors for low current connections
 IP65 rated
 Switch connection for remote on/off
 Connection for remote alarm
OPERATION
The PowerTector will guard against excessive battery discharge by disconnecting the
load before the battery voltage drops too low. Ten seconds after the battery voltage
drops below the disconnect threshold the alarm output will activate. If the battery
voltage is still below the disconnect threshold after a total of 60s the PowerTector will
disconnect the load from the battery and deactivate the alarm.
The load will remain disconnected until the battery voltage rises above the reconnect
threshold.
The PowerTector will protect the load by disconnecting it if the battery voltage
exceeds 19V on a 12V system or 32V on a 24V system.
ASSEMBLY
1. Select a cool and ventilated position to install the device which is not exposed to
direct sunlight.
2. Mount as close to the battery as possible using a wire of sufficient diameter.
3. Isolate the power to the wiring before commencing installation.
4. Mount using the three mounting holes with screws or bolts.
5. Connect the ‘ground’ terminal.
6. Connect the ‘input positive’ terminal.
7. If required program the unit as described below.
8. Connect the ‘output positive’ once no further programming is required.
9. Connect the alarm and switch if required.
THE CONNECTIONS
Isolate the circuit before you connect or disconnect the device. Connect the unit as
detailed in the wiring diagram.
PROGRAMMING
There are 4 settings that can be defined by the user, each setting is in a Program
Family, as shown in the table below. Changing the setting within a Program Family
does not affect any other Program Family.
Program Family 1: Operating voltage range. P1-P10 (P7 is default).
Program Family 2: Alarm output mode.. P11 (default)—The alarm output will be
constantly active 10s after the voltage drops below the disconnect threshold. It will
deactivate if the voltage rises above the disconnect threshold or 60s after the voltage
drops below the disconnect threshold.
The alarm will activate in pulse mode if the battery voltage rises above 19V for a
12V system or 32V for a 24V system.
P12—The alarm output will be constantly active 10s after the voltage drops below the
disconnect threshold. It will deactivate if the voltage rises above the reconnect
threshold.
The alarm output will not activate if the voltage rises above the over-voltage protec-
tion level.
This mode can be used for enabling an external battery charger to replenish the
battery that the PowerTector is protecting.
Program Family 3: Switch terminal mode. P13 (default)—The PowerTector output is
disconnected when the switch terminal is connected to the negative terminal of the
battery.
P14—The PowerTector output is disconnected when the switch terminal is connected
to the positive terminal of the battery.
Program Family 4: Voltage range select. P15 (default)—The unit will automatically
select the voltage range (12V or 24V) each time power is applied.
P16—The unit will operate as a 12V unit only.
P17—The unit will operate as a 24V unit only.
To change a program:
1. Temporally connect together the ‘input positive’ and the ‘program’ terminal using
the programming lead supplied.
2. The LED will start to flash, each flash indicates the program to be selected.
3. Keep the connection until the LED has flashed the number of times for the desired
program then remove the connection.
4. The LED will then flash the number of times to confirm the selected program.
Alarm** - The use of a relay requires a free wheeling diode to prevent damage - see
application note AN-PT01.
29 Newtown Business Park, Poole, BH12 3LL, UK • www.alfatronix.com
This device complies with the EU directive 2004/108/EC.
The type plate is located on the top of the device.
SAFETY
SAFETY
 This PowerTector is for ancillary equipment only. It must not be used to
disconnect equipment that is critical to the safe operation of the vehicle.
 The device must not be exposed to severe mechanical shocks.
 The device must not be exposed to extreme temperature, direct sunlight or
vigorous vibration.
 The device may only be used within a dry environment, such as a vehicle.
 Do not install this device on hot vehicle parts and ensure there is sufficient
space around the device for air circulation and cooling.
 The wiring harness should be protected by fuses.
 Observe the magnitude and polarity of the input/output voltage when
installing, incorrect polarity of the output could damage the circuit.
 Isolate the circuit before you connect or remove the device.
 Ensure that the output of the device is not short-circuited.
 Never open the device casing and never repair it. The device must be
replaced if it is damaged.
ENGLISH
FUSING
The input and ground wiring must be fused appropriately.
For the ground, minimum 500mA to 1A maximum.
Part Number /
Référence
Current /
Courant
Rated Voltage/
Tension nominale
Dimensions/
Dimensions
Weight/
Poids
PT40 40A 12V/24V 76x78x33mm 155g
PT60 60A 12V/24V 76x78x33mm 155g
TECHNICAL DATA / CARACTÉRISTIQUES TECHNIQUES
PROGRAM MODES / MODES DE PROGRAMMATION
* Factory default settings / Réglages par défaut
 (1) - Input Positive (1) - Entrée positive
 (2) - Output Positive (2) - Sortie positive
 (3) - Program (3) - Programme
 (4) - Alarm** (4) - Alarme**
 (5) - Ground (5) - Terre
 (6) - Switch (6) - Commutateur
 (F)- Fuses (F)- Fusibles
ASSEMBLAGE
PROGRAMMATION
CONTENU
 1 x PowerTector 3 x Vis
 5 x Bornes Plates Encliquetables 1 x Fil de programmation
CARACTERISTIQUES
 Sélection automatique du mode 12 V / 24 V (mode 12 V, 8<V≤17, mode 24 V,
17<V≤35)
 10 réglages de tension programmables
 Fourni avec des bornes plates encliquetables FASTON
 Indice de protection IP65
 Connexion pour commutateur marche / arrêt à distance
 Connexion pour alarme à distance
FONCTIONNEMENT
Le PowerTector protège contre toute décharge excessive de la batterie en décon-
nectant la charge avant que la tension de la batterie n’atteigne un niveau trop faible.
Dix seconde après que la tension de la batterie chute en-deçà du seuil de déconnex-
ion, la sortie de l’alarme s’active. Si la tension de la batterie reste inférieure au seuil
de déconnexion après une période totale de 60 s,le PowerTector déconnecte la
charge de la batterie et désactive l’alarme.
La charge reste déconnectée jusqu’à ce que la tension de la batterie dépasse le seuil
de reconnexion.
Le PowerTector protège la charge en la déconnectant lorsque la tension de la batterie
excède 19 V sur un système 12 V ou 32 V sur un système 24 V.
ASSEMBLAGE
1. Sélectionner un endroit frais et aéré pour installer le dispositif. Ne pas exposer à
la lumière directe du soleil.
2. Monter aussi près que possible de la batterie en utilisant un fil de diamètre
suffisant.
3. Isoler l’alimentation du câblage avant de démarrer l’installation.
4. Monter via les trois orifices de fixation en utilisant des vis ou des boulons.
5. Connecter le terminal « terre »
6. Connecter le terminal « entrée positive ».
7. Si nécessaire, programmer l’unité en suivant les consignes ci-dessous.
8. Connecter la « sortie positive » une fois la programmation achevée.
9. Connecter l’alarme et le commutateur, si nécessaire.
LA CONNEXION
Isoler le circuit avant de connecter ou de déconnecter le dispositif. Raccorder l’unité
conformément au schéma de câblage.
PROGRAMMATION
Il y a quatre paramètres qui peuvent être définis par l’utilisateur, chaque paramètre
fait partie d’une famille de programmes, comme indiqué dans la table ci-dessous. Le
changement d’un paramètre à l’intérieur d’une famille de programmes n’affecte pas
les autres familles de programmes.
Famille de programmes 1: Gamme de tension de fonctionnement. P1-P10 (P7 est le
programme par défaut).
Famille de programmes 2: le mode de sortie Alarme. (P11 est le programme par
défaut). La sortie alarme sera active en continu, 10 secondes après que la tension
soit tombée en dessous du seuil de déconnexion. Elle sera desactivée si la tension
passe au-dessus du seuil de déconnexion ou 60 secondes après que la tension soit
tombée en dessous du seuil de déconnexion.
L’alarme sera activée en mode impulsion si la tension de la batterie passe au dessus
de 19V pour un système 12V ou 32V pour un système 24V.
P12 –La sortie alarme sera active en continu, 10 secondes après que la tension soit
tombée en dessous du seuil de déconnexion. Elle sera desactivée si la tension passe
au-dessus du seuil de reconnexion.
La sortie alarme ne sera pas activée si la tension passe au-dessus du niveau de
protection de surtension.
Ce mode peut être utilisé pour activer un chargeur de batterie externe pour remplir
de nouveau la batterie que le PowerTector protège.
Famille de programmes 3: Commuter mode terminal P13 (default)—La sortie du
PowerTector se déconnecte lorsque le terminal du commutateur est connecté au
terminal négatif de la batterie.
P14—La sortie du PowerTector se déconnecte lorsque le terminal du commutateur est
connecté au terminal positif de la batterie.
Famille de programmes 4: Sélection de la gamme de tension. P15 (programme par
défaut) –l’unité sélectionnera automatiquement la gamme de tension (12V ou 24V)
chaque fois que la tension sera appliquée.
P16 –L’unité fonctionnera comme une unité 12V uniquement.
P17 - L’unité fonctionnera comme une unité 24V uniquement.
Pour modifier un programme :
1. Connecter de manière provisoire le terminal « entrée positive » et le terminal de
« programmation » en utilisant le fil de programmation fourni.
2. La LED commence à clignoter, chaque clignotement indiquant le programme à
sélectionner.
3. Maintenir la connexion jusqu’à ce que le nombre de clignotements de la LED
corresponde à celui du programme souhaité, puis retirer la connexion.
4. La LED clignote un même nombre de fois pour confirmer la sélection du pro-
gramme.
Alarme** - L'utilisation d'un relais nécessite une diode de roue libre pour empêcher
tout dommage - cf. Note d'application AN-PT01.
L’appareil est conforme aux exigences de la Directive UE 2004/108/
CE. La plaquette d’identification se trouve sur le haut de l’appareil.
SÉCURITÉ
SECURITE
 Ce PowerTector est exclusivement pour des équipements accessoires. Il ne doit
absolument pas être utilisé pour déconnecter un équipement essentiel à la sécurité
du fonctionnement du véhicule.
 Tenir l’appareil éloigné de tout choc mécanique.
 Ne pas exposer l’appareil à des températures extrêmes, au soleil direct ou à
d’importantes vibrations.
 L’appareil ne doit être utilisé que dans un environnement sec, comme un véhicule.
 Ne pas installer l’appareil dans un véhicule à haute température et prenez garde
que l’espace entourant l’appareil soit assez large pour qu’il puisse être ventilé et
se refroidir.
 La sangle de connexion doit être protégée par des fusibles.
 Veillez à la puissance électrique et la polarité de la tension de sortie lors de
l’installation. Une polarité incorrecte de sortie pourrait entraîner des dommages
du circuit.
 Isoler le circuit avant de connecter ou de démonter l’appareil.
 Assurez-vous que la sortie de l’appareil n’est pas court-circuitée.
 Ne jamais ouvrir l’appareil ou tenter de le réparer. L’appareil doit être remplacé
en cas de dommage.
FRANÇAIS
FUSIBLE
Le fusible d’entrée et de sortie doit être connecté de façon appropriée.
Pour la terre, entre 500 mA minimum et 1 A maximum.
ENGLISH • FRANÇAIS • DEUTSCH • ESPAÑOL
vJ
INDUCTIVE LOADS
The inductive load rating of this PowerTector is 1mH.
Do not exceed the specified inductive rating.
Inductive equipment includes; motors, pumps, refrigeration, relays, long
cables etc.
Conducted voltage transients must not exceed those specified by ISO7637-
2:2004 Level III.
Program
Family /
Programme
famille
Program
Number /
Numéro de
programme
12V 24V
Disconnect /
Déconnecter
Reconnect /
Reconnecter
Disconnect /
Déconnecter
Reconnect /
Reconnecter
Family 1
Famille 1
P1 10.5V 12V 21V 24V
P2 10V 11.5V 20V 23V
P3 9.5V 11.5V 19V 23V
P4 11V 13.5V 22.5V 26.5V
P5 11.5V 13.5V 23V 27.5V
P6 10.5V 12.5V 21V 25V
P7* 11.5V 12.5V 23V 25.5V
P8 11V 12.5V 23.5V 25.5V
P9 12V 13V 24V 26V
P10 10V 13V 20V 26.5V
Family 2
Famille 2
P11*Alarm Mode = Normal / Mode alarme = Normal
P12 Alarm Mode = Battery Charger Enable
Mode alarme = Activation du chargement de la batterie
P13* Switch Mode = Low / Mode commutateur = Faible
Family 3
Famille 3 P14 Switch Mode = High / Mode commutateur = Élevé
Family 4
Famille 4
P15* Voltage Range = Auto / Gamme de tension= Auto
P16 Voltage Range = 12V Only / Gamme de tension= 12V
uniquement
P17 Voltage Range = 24V Only / Gamme de tension= 24V
uniquement
CHARGES INDUCTIVES
L’indice de charge inductive de ce PowerTector est 1mH.
Ne dépassez pas l’indice de charge inductive spécifié.
Les équipements inductifs incluent: les moteurs, pompes, systèmes de réfrigération,
relais, les longs cables, etc..
Les transitoires de tension conduits ne doivent pas dépasser celles qui sont spécifiées
par la norme ISO7637-2:2004 Level III
ASSEMBLY
PROGRAMMING
OPERATING & ASSEMBLY
INSTRUCTIONS
PowerTector PT40-T & PT60-T
T E L: +44 (0) 1202 715 517 • [email protected]m
PACKING CONTENTS
 1 x PowerTector 3 x Screws
 5 x Crimp Connectors 1 x Programming Lead
FEATURES
 12V / 24V Automatic mode selection (12V mode 8<V≤17 , 24V mode 17<V≤35)
 10 Programmable disconnection times
 Supplied with FASTON crimp connectors for low current connections
 IP65 rated
 Ignition switch connection
 Connection for remote alarm
OPERATION
The PowerTector-T will guard against excessive battery discharge by disconnecting the load at a user selectable time after the ignition has been
turned off.
The PowerTector-T will also monitor the battery once the ignition has been turned off and disconnect the load when the voltage drops below a user
selectable level after one minute.
The PowerTector will protect the load by disconnecting it if the battery voltage exceeds 19V on a 12V system or 32V on a 24V system.
ASSEMBLY
1. Select a cool and ventilated position to install the device which is not exposed to direct sunlight.
2. Mount as close to the battery as possible using a wire of sufficient diameter.
3. Isolate the power to the wiring before commencing installation.
4. Mount using the three mounting holes with screws or bolts.
5. Connect the ‘ground’ terminal.
6. Connect the ‘input positive’ terminal.
7. Connect the ‘ignition’ terminal to the vehicle ignition switched output.
8. If required program the unit as described below.
9. Connect the ‘output positive’ once no further programming is required.
10.Connect the alarm if required.
For the alarm, (4) maximum current is 500mA.
THE CONNECTIONS
Isolate the circuit before you connect or disconnect the device. Connect the unit as detailed in the wiring diagram.
PROGRAMMING
The table shows the factory default and user defined settings.
To change a program:
1. Remove the ‘input positive’ crimp connector just enough to reveal the ’input positive’ terminal.
2. Temporally connect together the ‘input positive’ and the ‘program’ terminal using the programming lead supplied.
3. The LED will start to flash, each flash indicates the program to be selected.
4. Keep the connection until the LED has flashed the number of times for the desired program then remove the connection.
5. The LED will then flash the number of times to confirm the selected program.
6. Programming of P1 to P10 and P11 to P15 are carried out separately.
PROGRAM MODES
P1-P10—Disconnect time range. (P1 is default)
P11—15 Disconnection Voltage. (P13 is default)
ALARM
The alarm output will be constantly active 10s after the voltage drops below the disconnect threshold. It will deactivate if the voltage rises above the
disconnect threshold or 60s after the voltage drops below the disconnect threshold.
The alarm will activate in pulse mode if the battery voltage rises above 19V for a 12V system or 32V for a 24V system.
Alarm** - The use of a relay requires a free wheeling diode to prevent damage - see application note AN-PT01.
29 Newtown Business Park, Poole, BH12 3LL, UK • www.alfatronix.com
This device complies with the EU directive 2004/108/EC.
The type plate is located on the top of the device.
SAFETY
SAFETY
 This PowerTector is for ancillary equipment only. It must not be used to disconnect equipment that is critical to the safe operation of the vehicle.
 The device must not be exposed to severe mechanical shocks.
 The device must not be exposed to extreme temperature, direct sunlight or vigorous vibration.
 The device may only be used within a dry environment, such as a vehicle.
 Do not install this device on hot vehicle parts and ensure there is sufficient space around the device for air circulation and cooling.
 The wiring harness should be protected by fuses.
 Observe the magnitude and polarity of the input/output voltage when installing, incorrect polarity of the output could damage the circuit.
 Isolate the circuit before you connect or remove the device.
 Ensure that the output of the device is not short-circuited.
 Never open the device casing and never repair it. The device must be replaced if it is damaged.
ENGLISH
FUSING
The input and ground wiring must be fused appropriately.
For the ground, minimum 500mA to 1A maximum.
Part Number Current Rated Voltage Dimensions Weight
PT40-T 40A 12V/24V 76x78x33mm 155g
PT60-T 60A 12V/24V 76x78x33mm 155g
TECHNICAL DATA
PROGRAM MODES / MODES DE PROGRAMMATION
* Factory default settings
 (1) - Input Positive
 (2) - Output Positive
 (3) - Program
 (4) - Alarm**
 (5) - Ground
 (6) - Vehicle ignition switch
 (F)- Fuses
 (X) - Vehicle Ignition Switch
ENGLISH
Program Number Time
P1* 30 mins
P2 1 hour
P3 3 hours
P4 6 hours
P5 12 hours
P6 18 hours
P7 24 hours
P8 36 hours
P9 48 hours
P10 72 hours
12V System 24V System
P11 10.5V 21V
P12 11V 22V
P13* 11.5V 23V
P14 12V 24V
P15 8.5V 8.5V
vD
INDUCTIVE LOADS
The inductive load rating of this PowerTector is 1mH.
Do not exceed the specified inductive rating.
Inductive equipment includes; motors, pumps, refrigeration, relays, long cables etc.
Conducted voltage transients must not exceed those specified by ISO7637-2:2004 Level III.
ASSEMBLY
PROGRAMMING
OPERATING & ASSEMBLY
INSTRUCTIONS
PowerTector PT60-B
T E L: +44 (0) 1202 715 517 • [email protected]m
PACKING CONTENTS
 1 x PowerTector 3 x Screws
 5 x Crimp Connectors 1 x Programming Lead
FEATURES
 12V / 24V Automatic mode selection (12V mode 8<V≤17 , 24V mode
17<V≤35)
 10 Programmable voltage settings
 Supplied with FASTON crimp connectors for low current connections
 IP65 rated
 Switch connection for remote on/off
 Connection for remote alarm
OPERATION
The PowerTector will guard against excessive battery discharge by disconnecting the
load before the battery voltage drops too low. Ten seconds after the battery voltage
drops below the disconnect threshold the alarm output will activate. If the battery
voltage is still below the disconnect threshold after a total of 60s the PowerTector will
disconnect the load from the battery and deactivate the alarm.
The load will remain disconnected until the battery voltage rises above the reconnect
threshold.
The PowerTector will protect the load by disconnecting it if the battery voltage
exceeds 19V on a 12V system or 32V on a 24V system.
ASSEMBLY
1. Select a cool and ventilated position to install the device which is not exposed to
direct sunlight.
2. Mount as close to the battery as possible using a wire of sufficient diameter.
3. Isolate the power to the wiring before commencing installation.
4. Mount using the three mounting holes with screws or bolts.
5. Connect the ‘ground’ terminal.
6. Connect the ‘input positive’ terminal.
7. If required program the unit as described below.
8. Connect the ‘output positive’ once no further programming is required.
9. Connect the alarm and switch if required.
THE CONNECTIONS
Isolate the circuit before you connect or disconnect the device. Connect the unit as
detailed in the wiring diagram.
PROGRAMMING
There are 4 settings that can be defined by the user, each setting is in a Program
Family, as shown in the table below. Changing the setting within a Program Family
does not affect any other Program Family.
Program Family 1: Operating voltage range. P1-P10 (P7 is default).
Program Family 2: Alarm output mode.. P11 (default)—The alarm output will be
constantly active 10s after the voltage drops below the disconnect threshold. It will
deactivate if the voltage rises above the disconnect threshold or 60s after the voltage
drops below the disconnect threshold.
The alarm will activate in pulse mode if the battery voltage rises above 19V for a
12V system or 32V for a 24V system.
P12—The alarm output will be constantly active 10s after the voltage drops below the
disconnect threshold. It will deactivate if the voltage rises above the reconnect
threshold.
The alarm output will not activate if the voltage rises above the over-voltage protec-
tion level.
This mode can be used for enabling an external battery charger to replenish the
battery that the PowerTector is protecting.
Program Family 3: Switch terminal mode. P13 (default)—The PowerTector output is
disconnected when the switch terminal is connected to the negative terminal of the
battery.
P14—The PowerTector output is disconnected when the switch terminal is connected
to the positive terminal of the battery.
Program Family 4: Voltage range select. P15 (default)—The unit will automatically
select the voltage range (12V or 24V) each time power is applied.
P16—The unit will operate as a 12V unit only.
P17—The unit will operate as a 24V unit only.
To change a program:
1. Temporally connect together the ‘input positive’ and the ‘program’ terminal using
the programming lead supplied.
2. The LED will start to flash, each flash indicates the program to be selected.
3. Keep the connection until the LED has flashed the number of times for the desired
program then remove the connection.
4. The LED will then flash the number of times to confirm the selected program.
Alarm** - The use of a relay requires a free wheeling diode to prevent damage - see
application note AN-PT01.
29 Newtown Business Park, Poole, BH12 3LL, UK • www.alfatronix.com
This device complies with the EU directive 2004/108/EC.
The type plate is located on the top of the device.
SAFETY
SAFETY
 This PowerTector is for ancillary equipment only. It must not be used to
disconnect equipment that is critical to the safe operation of the vehicle.
 The device must not be exposed to severe mechanical shocks.
 The device must not be exposed to extreme temperature, direct sunlight or
vigorous vibration.
 The device may only be used within a dry environment, such as a vehicle.
 Do not install this device on hot vehicle parts and ensure there is sufficient
space around the device for air circulation and cooling.
 The wiring harness should be protected by fuses.
 Observe the magnitude and polarity of the input/output voltage when
installing, incorrect polarity of the output could damage the circuit.
 Isolate the circuit before you connect or remove the device.
 Ensure that the output of the device is not short-circuited.
 Never open the device casing and never repair it. The device must be
replaced if it is damaged.
ENGLISH
FUSING
The input and ground wiring must be fused appropriately.
For the ground, minimum 500mA to 1A maximum.
Part Number /
Référence
Current /
Courant
Rated Voltage/
Tension nominale
Dimensions/
Dimensions
Weight/
Poids
PT60-B 60A 12V/24V 76x78x33mm 155g
TECHNICAL DATA / CARACTÉRISTIQUES TECHNIQUES
PROGRAM MODES / MODES DE PROGRAMMATION
* Factory default settings / Réglages par défaut
 (1) - Input Positive (1) - Entrée positive
 (2) - Output Positive (2) - Sortie positive
 (3) - Program (3) - Programme
 (4) - Alarm** (4) - Alarme**
 (5) - Ground (5) - Terre
 (6) - Switch (6) - Commutateur
 (F)- Fuses (F)- Fusibles
ASSEMBLAGE
PROGRAMMATION
CONTENU
 1 x PowerTector 3 x Vis
 5 x Bornes Plates Encliquetables 1 x Fil de programmation
CARACTERISTIQUES
 Sélection automatique du mode 12 V / 24 V (mode 12 V, 8<V≤17, mode 24 V,
17<V≤35)
 10 réglages de tension programmables
 Fourni avec des bornes plates encliquetables FASTON
 Indice de protection IP65
 Connexion pour commutateur marche / arrêt à distance
 Connexion pour alarme à distance
FONCTIONNEMENT
Le PowerTector protège contre toute décharge excessive de la batterie en décon-
nectant la charge avant que la tension de la batterie n’atteigne un niveau trop faible.
Dix seconde après que la tension de la batterie chute en-deçà du seuil de déconnex-
ion, la sortie de l’alarme s’active. Si la tension de la batterie reste inférieure au seuil
de déconnexion après une période totale de 60 s,le PowerTector déconnecte la
charge de la batterie et désactive l’alarme.
La charge reste déconnectée jusqu’à ce que la tension de la batterie dépasse le seuil
de reconnexion.
Le PowerTector protège la charge en la déconnectant lorsque la tension de la batterie
excède 19 V sur un système 12 V ou 32 V sur un système 24 V.
ASSEMBLAGE
1. Sélectionner un endroit frais et aéré pour installer le dispositif. Ne pas exposer à
la lumière directe du soleil.
2. Monter aussi près que possible de la batterie en utilisant un fil de diamètre
suffisant.
3. Isoler l’alimentation du câblage avant de démarrer l’installation.
4. Monter via les trois orifices de fixation en utilisant des vis ou des boulons.
5. Connecter le terminal « terre »
6. Connecter le terminal « entrée positive ».
7. Si nécessaire, programmer l’unité en suivant les consignes ci-dessous.
8. Connecter la « sortie positive » une fois la programmation achevée.
9. Connecter l’alarme et le commutateur, si nécessaire.
LA CONNEXION
Isoler le circuit avant de connecter ou de déconnecter le dispositif. Raccorder l’unité
conformément au schéma de câblage.
PROGRAMMATION
Il y a quatre paramètres qui peuvent être définis par l’utilisateur, chaque paramètre
fait partie d’une famille de programmes, comme indiqué dans la table ci-dessous. Le
changement d’un paramètre à l’intérieur d’une famille de programmes n’affecte pas
les autres familles de programmes.
Famille de programmes 1: Gamme de tension de fonctionnement. P1-P10 (P7 est le
programme par défaut).
Famille de programmes 2: le mode de sortie Alarme. (P11 est le programme par
défaut). La sortie alarme sera active en continu, 10 secondes après que la tension
soit tombée en dessous du seuil de déconnexion. Elle sera desactivée si la tension
passe au-dessus du seuil de déconnexion ou 60 secondes après que la tension soit
tombée en dessous du seuil de déconnexion.
L’alarme sera activée en mode impulsion si la tension de la batterie passe au dessus
de 19V pour un système 12V ou 32V pour un système 24V.
P12 –La sortie alarme sera active en continu, 10 secondes après que la tension soit
tombée en dessous du seuil de déconnexion. Elle sera desactivée si la tension passe
au-dessus du seuil de reconnexion.
La sortie alarme ne sera pas activée si la tension passe au-dessus du niveau de
protection de surtension.
Ce mode peut être utilisé pour activer un chargeur de batterie externe pour remplir
de nouveau la batterie que le PowerTector protège.
Famille de programmes 3: Commuter mode terminal P13 (default)—La sortie du
PowerTector se déconnecte lorsque le terminal du commutateur est connecté au
terminal négatif de la batterie.
P14—La sortie du PowerTector se déconnecte lorsque le terminal du commutateur est
connecté au terminal positif de la batterie.
Famille de programmes 4: Sélection de la gamme de tension. P15 (programme par
défaut) –l’unité sélectionnera automatiquement la gamme de tension (12V ou 24V)
chaque fois que la tension sera appliquée.
P16 –L’unité fonctionnera comme une unité 12V uniquement.
P17 - L’unité fonctionnera comme une unité 24V uniquement.
Pour modifier un programme :
1. Connecter de manière provisoire le terminal « entrée positive » et le terminal de
« programmation » en utilisant le fil de programmation fourni.
2. La LED commence à clignoter, chaque clignotement indiquant le programme à
sélectionner.
3. Maintenir la connexion jusqu’à ce que le nombre de clignotements de la LED
corresponde à celui du programme souhaité, puis retirer la connexion.
4. La LED clignote un même nombre de fois pour confirmer la sélection du pro-
gramme.
Alarme** - L'utilisation d'un relais nécessite une diode de roue libre pour empêcher
tout dommage - cf. Note d'application AN-PT01.
L’appareil est conforme aux exigences de la Directive UE 2004/108/
CE. La plaquette d’identification se trouve sur le haut de l’appareil.
SÉCURITÉ
SECURITE
 Ce PowerTector est exclusivement pour des équipements accessoires. Il ne doit
absolument pas être utilisé pour déconnecter un équipement essentiel à la sécurité
du fonctionnement du véhicule.
 Tenir l’appareil éloigné de tout choc mécanique.
 Ne pas exposer l’appareil à des températures extrêmes, au soleil direct ou à
d’importantes vibrations.
 L’appareil ne doit être utilisé que dans un environnement sec, comme un véhicule.
 Ne pas installer l’appareil dans un véhicule à haute température et prenez garde
que l’espace entourant l’appareil soit assez large pour qu’il puisse être ventilé et
se refroidir.
 La sangle de connexion doit être protégée par des fusibles.
 Veillez à la puissance électrique et la polarité de la tension de sortie lors de
l’installation. Une polarité incorrecte de sortie pourrait entraîner des dommages
du circuit.
 Isoler le circuit avant de connecter ou de démonter l’appareil.
 Assurez-vous que la sortie de l’appareil n’est pas court-circuitée.
 Ne jamais ouvrir l’appareil ou tenter de le réparer. L’appareil doit être remplacé
en cas de dommage.
FRANÇAIS
FUSIBLE
Le fusible d’entrée et de sortie doit être connecté de façon appropriée.
Pour la terre, entre 500 mA minimum et 1 A maximum.
ENGLISH • FRANÇAIS • DEUTSCH • ESPAÑOL
vJ
INDUCTIVE LOADS
The inductive load rating of this PowerTector is 1mH.
Do not exceed the specified inductive rating.
Inductive equipment includes; motors, pumps, refrigeration, relays, long
cables etc.
Conducted voltage transients must not exceed those specified by ISO7637-
2:2004 Level III.
Program
Family /
Programme
famille
Program
Number /
Numéro de
programme
12V 24V
Disconnect /
Déconnecter
Reconnect /
Reconnecter
Disconnect /
Déconnecter
Reconnect /
Reconnecter
Family 1
Famille 1
P1 10.5V 12V 21V 24V
P2 10V 11.5V 20V 23V
P3 9.5V 11.5V 19V 23V
P4 11V 13.5V 22.5V 26.5V
P5 11.5V 13.5V 23V 27.5V
P6 10.5V 12.5V 21V 25V
P7* 11.8V 12.8V 23V 25.5V
P8 11V 12.5V 23.5V 25.5V
P9 12V 13V 24V 26V
P10 10V 13V 20V 26.5V
Family 2
Famille 2
P11*Alarm Mode = Normal / Mode alarme = Normal
P12 Alarm Mode = Battery Charger Enable
Mode alarme = Activation du chargement de la batterie
P13* Switch Mode = Low / Mode commutateur = Faible
Family 3
Famille 3 P14 Switch Mode = High / Mode commutateur = Élevé
Family 4
Famille 4
P15* Voltage Range = Auto / Gamme de tension= Auto
P16 Voltage Range = 12V Only / Gamme de tension= 12V
uniquement
P17 Voltage Range = 24V Only / Gamme de tension= 24V
uniquement
CHARGES INDUCTIVES
L’indice de charge inductive de ce PowerTector est 1mH.
Ne dépassez pas l’indice de charge inductive spécifié.
Les équipements inductifs incluent: les moteurs, pompes, systèmes de réfrigération,
relais, les longs cables, etc..
Les transitoires de tension conduits ne doivent pas dépasser celles qui sont spécifiées
par la norme ISO7637-2:2004 Level III

This manual suits for next models

1

Other alfatronix Power Supply manuals

alfatronix PVPro-S/A Manual

alfatronix

alfatronix PVPro-S/A Manual

alfatronix PR65R Manual

alfatronix

alfatronix PR65R Manual

alfatronix PowerTector PT10 Manual

alfatronix

alfatronix PowerTector PT10 Manual

alfatronix AD Series Manual

alfatronix

alfatronix AD Series Manual

alfatronix PV USB-1 Manual

alfatronix

alfatronix PV USB-1 Manual

alfatronix PV-USB1 Manual

alfatronix

alfatronix PV-USB1 Manual

alfatronix A/C.PVPro-S Manual

alfatronix

alfatronix A/C.PVPro-S Manual

Popular Power Supply manuals by other brands

Weinzierl KNX IP LineMaster 762 Operation and installation manual

Weinzierl

Weinzierl KNX IP LineMaster 762 Operation and installation manual

environmental potentials EP-2800 Series Installation and application manual

environmental potentials

environmental potentials EP-2800 Series Installation and application manual

Communications Specialties 6010A user manual

Communications Specialties

Communications Specialties 6010A user manual

RND 320-KA3005D user manual

RND

RND 320-KA3005D user manual

Sennheiser ADN PS - Specifications

Sennheiser

Sennheiser ADN PS - Specifications

Akyga AK-ND-53 user manual

Akyga

Akyga AK-ND-53 user manual

Omron S8VK-G Series manual

Omron

Omron S8VK-G Series manual

2E DIYA user guide

2E

2E DIYA user guide

Pulsar HPSB 3524C quick start guide

Pulsar

Pulsar HPSB 3524C quick start guide

US drives AC REGEN RGB-0200-0030-N1 instruction manual

US drives

US drives AC REGEN RGB-0200-0030-N1 instruction manual

Liebert PowerSure PSA350MT-120 quick start guide

Liebert

Liebert PowerSure PSA350MT-120 quick start guide

Global Specialties 1412 user manual

Global Specialties

Global Specialties 1412 user manual

IBM System/370 145 Reference Summary

IBM

IBM System/370 145 Reference Summary

Hyundai HYPS-400 user manual

Hyundai

Hyundai HYPS-400 user manual

GMI D6014S instruction manual

GMI

GMI D6014S instruction manual

Televes T.0X Series manual

Televes

Televes T.0X Series manual

Elektro-Automatik ELR Rack 38U installation guide

Elektro-Automatik

Elektro-Automatik ELR Rack 38U installation guide

ferrum OOR user manual

ferrum

ferrum OOR user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.