ControlLogix Programmable Limit Switch Module 5
Publication 1756-IN594A-EN-P - November 2003
North American Hazardous Location Approval
The following information applies when
operating this equipment in hazardous
locations:
Informations sur l’utilisation de cet équipement
en environnements dangereux:
Products marked “CL I, DIV 2, GP A, B, C, D” are
suitable for use in Class I Division 2 Groups A, B, C,
D, Hazardous Locations and nonhazardous locations
only. Each product is supplied with markings on the
rating nameplate indicating the hazardous location
temperature code. When combining products within
a system, the most adverse temperature code
(lowest “T” number) may be used to help determine
the overall temperature code of the system.
Combinations of equipment in your system are
subject to investigation by the local Authority Having
Jurisdiction at the time of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu’à une utilisation en environnements de
Classe I Division 2 Groupes A, B, C, D dangereux et non
dangereux. Chaque produit est livré avec des
marquages sur sa plaque d’identification qui indiquent
le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés
dans un système, le code de température le plus
défavorable (code de température le plus faible) peut
être utilisé pour déterminer le code de température
global du système. Les combinaisons d’équipements
dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de
l’installation.
WARNING EXPLOSION HAZARD
•Do not disconnect
equipment unless power
has been removed or the
area is known to be
nonhazardous.
•Do not disconnect
connections to this
equipment unless power
has been removed or the
area is known to be
nonhazardous. Secure
any external connections
that mate to this
equipment by using
screws, sliding latches,
threaded connectors, or
other means provided
with this product.
•Substitution of
components may impair
suitability for Class I,
Division 2.
•If this product contains
batteries, they must only
be changed in an area
known to be
nonhazardous.
AVERTISSEMENT RISQUE D’EXPLOSION
•Couper le courant ou
s’assurer que
l’environnement est
classé non dangereux
avant de débrancher
l'équipement.
•Couper le courant ou
s'assurer que
l’environnement est
classé non dangereux
avant de débrancher les
connecteurs. Fixer tous
les connecteurs externes
reliés à cet équipement à
l'aide de vis, loquets
coulissants, connecteurs
filetés ou autres moyens
fournis avec ce produit.
•La substitution de
composants peut rendre
cet équipement inadapté
à une utilisation en
environnement de Classe
I, Division 2.
•S’assurer que
l’environnement est
classé non dangereux
avant de changer les
piles.
Allen-Bradley Automation