
0540569-J0 Rev F
18
4.4.3 Mechanical
A locking clip automatically secures the rectifier into the shelf.
4.4.4 True Module Fail Alarm
The power modules have a “true” fail alarm. This provides a true indication of the power module’s ability to source
current. When the module’s output current drops below 2.5% of the rated output a low output current condition is
detected and the Module Fail detection circuit is activated. This circuit momentarily ramps up the output voltage to
determine if the module will source current. If no increase in current is detected, the Module Fail alarm is activated.
The module will test once every 60 seconds for the condition until current is detected. Output voltage ramping will
cease upon detection of current1.
A minimum 2.5% load is required to avoid the Ramp Test Fail alarm; this can typically be provided with the parallel
system battery. Activation of this alarm could indicate a failed module or a failed load.
4.4.5
NOTE:
For Cordex rectier systems without batteries (or with a very light load; below 2.5%
of rated output) it is recommended that the ramp test be disabled to avoid nuisance
alarms. The Ramp Test feature is enabled/disabled via the controller. Refer to the soft-
ware manual for detailed information.
Heat Dissipation
Cooling of the module is front-to-rear with the exhaust air exiting at the back. The fan is variable speed; which is
determined by heatsink temperature and load.
4.4.6 Over Temperature Protection
Each rectifier module is protected in the event of an excessive increase in temperature due to component failure
or cooling airflow blockage. During over temperature conditions, the rectifier limits the output power as well as the
output current. If temperature continues to increase, a shutdown of the rectifier is initiated. The rectifier shall restart
automatically if the temperature has returned to a safe level.
4.4.7 Wide AC Range
A minor alarm is generated when the AC input voltage drops below specification.
• Output power is reduced linearly between 176Vac and 132Vac to 60% of the rated output power.
• Input current is limited to less than 6A for operation from 132Vac to 90Vac. Power is derated linearly between
132Vac (~700W) to 90Vac (~475W).
• At a lower voltage the module will shut down and will not restart until the AC is greater than 90Vac.
• For voltages above 277Vac, power factor and total harmonic distortion may be derated. Up to 320Vac, the recti-
fier may not be operational but shall not suffer any damage.
4.4.8 AC Inrush/Transient Suppression
An external surge suppressor is not required at the AC input, modules are protected from input lightning and transient
surges in accordance with IEEE/ANSI C62.41 Category B3.
4.4.9 Soft Start
To eliminate an instantaneous demand on the AC source, a soft start feature is employed. Soft Start, sometimes
referred to as “current walk-in”, works by gradually (up to five seconds) ramping the current limit up from zero to the
actual or defined customer setting. The rectifier output voltage is ramped up from the minimum voltage to the float
voltage.
1 Under normal conditions, a battery connected to the output of the rectifier will draw current when the voltage ramp
occurs. Therefore the rectifier fail alarm will not be generated with a battery connected.