RTBSB-001.xxx
Stand 6.2016 (16/034) 4 12 692 03
Raumtemperaturregler Bimetall „Wechsler“
Bimetal room temperature controller with changeover contact
Thermostat électronique à bilame avec contact de permutation pour la régulation de la température ambiante
Sicherheitshinweis! Safety information!
No persons other than expert electricians only must open this device in due compliance with the
related wiring diagram shown in the housing cover / on the housing / represented in the corre-
sponding operating instructions. All expert electricians committed to the execution of any such
works must comply with the relevant safety regulations currently operative and in force. The com-
pany charged with the installation of the device must, after the completion of the installation
works, instruct the user of the control system into its functions and in how to operate it correctly.
These operating instructions must be kept at a place that can be accessed freely by the operating
and/or servicing personnel in charge.
3. Montage/Anschluss
The controller is, in order to facilitate its installation, delivered in opened condition. It is recommended
to install the device on an UP box. The device can nevertheless be mounted on a non-conductible, plane
and solid surface. The opening and closing of the housing takes place as described in section 6. Remove
the turning knob first, then press the small hook inwards by means of a slot screwdriver and open the
controller cover by folding it down. The venting slots must not be covered. If otherwise, there is danger
that the control operations performed by the device become incorrect.
Caution: The device is able to resist to the types of dirt or dust that normally occur in offices and
living spaces. Excessive volumes of dust and/or dirt produced during the installation or during
renovation works may soil the contacts and can lead to a breakdown of the device. In any such
case, the contacts need to be cleaned by an expert electrician. This may for example be effected by
blowing the device down or by cleaning it with a dry brush.
3. Mounting / Installation
DGB
Dieses Gerät darf nur durch eine Elektrofachkraft geöffnet und gemäß dem entsprechenden Schaltbild
im Gehäusedeckel / auf dem Gehäuse / in der Bedienungsanleitung installiert werden. Dabei sind die
bestehenden Sicherheitsvorschriften zu beachten. Nach der Installation ist der Betreiber, durch die aus-
führende Installationsfirma, in die Funktion und Bedienung der Regelung einzuweisen.
Die Bedienungsanleitung muss für Bedien- und Wartungspersonal an frei zugänglicher Stelle aufbe-
wahrt werden.
Der einfacheren Montage wegen wird der Regler geöffnet ausgeliefert. Die Montage auf eine Unterputz-
dose wird empfohlen, kann aber auch auf ebenen, nichtleitfähigem Untergrund erfolgen. Das Öffnen
und Schließen des Reglers erfolgt wie unter Punkt 6. dargestellt. Zunächst Knopf abnehmen, Häkchen
mit einem Schlitzschraubendreher leicht nach innen drücken und Reglerkappe nach unten aufklappen.
Die Lüftungsschlitze dürfen nicht verschlossen werden, da dies zu einer fehlerhaften Regelung führt.
Achtung! Der Regler ist für übliche Verunreinigungen in Wohn- und Büroräumen geeignet. Unverhält-
nismäßiger Schmutz und Staub während der Installations- oder Renovierungsarbeiten kann die Kontakte
verschmutzen und zur Nichtfunktion des Reglers führen. In diesem Fall sind die Kontakte von einer
Elektrofachkraft zu reinigen. Dies kann zum Beispiel durch Ausblasen oder durch reinigen mittels eines
trockenen Pinsels geschehen.
1. Anwendung
Dieser Raumtemperaturregler wurde speziell für die Regelung oder Überwachung von Tempera-
turen in Büros, Wohnräumen und Hotels entwickelt und ist geeignet für alle Heizungsarten. Bei
elektrischen Fußbodenheizungen ist darauf zu achten, dass die Leistung der Heizung auch bei
Dauerbetrieb den Estrich nicht überhitzen kann. Bei Warmwasserheizungen sind auf den Heizaus-
gang max. 10 stromlos geschlossene, oder auf den Kühlausgang max. 5 stromlos offene Ventile
anzuschließen. Im Kühlfall sind max.5 stromlos geschlossenen Ventile auf den Kühlausgang oder
max. 10 stromlos offene Ventile auf den Heizausgang anzuschließen.
Achtung! Bei dem Reglertyp RTBSB-001.065 speziell für 2-Rohr-Klimasysteme, ist die
Bedruckung des Heiz-/Kühl-Umschalters auf stromlos geschlossene Ventile ausgelegt. Die übrigen
in dieser Anleitung beschriebenen Reglertypen sind speziell für 4-Rohr-Klimasysteme entwickelt.
Gegebenenfalls benötigte Temperaturbegrenzungen müssen zusätzlich installiert werden.
Für andere, vom Hersteller nicht vorherzusehende Einsatzgebiete, sind die dort gültigen Sicher-
heitsvorschriften zu beachten. Eignung hierfür siehe Punkt 9. Gewährleistung.
This bimetal room temperature controller has been specially devised for the control and super-
vision of temperatures in offices, living spaces and hotels. It serves for use with all types of heating
systems. With electric floor heating systems, care must be taken to ensure that the performance of the
controlled system cannot, even if the system is operated continuously, result in an overheating of the
pavement. With hot water heating systems, no more than 10 normally closed valves must be connected
to the cooling outlet and no more than 5 normally opened valves to the cooling outlet. If used for
cooling purposes, no more than 5 normally opened valves must be connected to the cooling outlet,
while no more than 10 normally closed valves must be connected to the heating outlet.
Caution: The imprint on the heating / cooling changeover switch installed on the controller model
RTBSB-001.065 (specially designed for use with two-pipe systems) relates to normally closed valves
only. All other controller models described herein have been devised for use with four-pipe climate
systems. Where applicable, temperature limiters need to be installed in addition.
Regarding other applications not to be foreseen by the manufacturer of this device, the safety standards
concerning these applications need to be followed and adhered to. Regarding the aptitude of the device
for any such other application, please refer to section 9 herein (Warranty).
1. Application
2. Funktionen
The room temperature controller described herein is equipped with an internal bimetal sensor that captures
the currently existing room temperature. The device controls the related heating or cooling system in accor-
dance with the adjusted set value. The individual controller models differ in their equipment, such as in an
ON/OFF switch and a fan outlet (.026), a “heating / cooling switch” (.065), a “temperature decrease mode /
comfort mode / automatic mode” selector switch (.073) or a green “temperature decrease mode active” indi-
cator lamp (.075).
Thermal recirculation
As, during the heating and/or cooling procedure, the controller usually captures the actually prevailing room
temperature at a rather late point, a thermal recirculation has been realised with the device that enables to
excite it early enough with the consequence that a very precise switching difference can be attained.
Range suppression
The mobile setting elements located underneath of the knob enable to delimit the setting range mechanically
(see section 6).
Night temperature decrease mode
With all controller models that enable to operate in night temperature decrease mode (indicated by the clock
symbol shown in the connection diagram), the room temperature is decreased by approx. 4K when connec-
ting the 230 V~ power supply to the terminal .
2. Functional description
4. Technische Daten
Fühlerelement: Bimetall „Wechsler“, Typ 1C
Versorgungsspannung und Schaltvermögen: siehe Punkt 7. Typenschild
Regelbereich: 5 … 30°C
Schaltdifferenz: ca. 0,5 K
Skala: °C Skala
max. zulässige Temperatur-
änderungsgeschwindigkeit der Regelstrecke: 4 K/h
Schutzart: IP30
Schutzklasse: II nach entsprechender Montage
Max. Luftfeuchtigkeit: 95%rH, nicht kondensierend
Gehäusematerial und -Farbe: Kunststoff ABS, reinweiß (ähnlich RAL 9010)
Energieeffizienzklasse: I (Beitrag zur jahreszeitbedingten
Raumheizungs-Energieeffizienz 1%)
4. Technical data
Sensing element: bimetal sensor, type 1C
Supply voltage and switching capacity: see section 7, type plate
Control range: 5 … 30°C
Switching difference: approx. 0.5 K
Scale: in °C
Max. admissible temperature
changing speed of the controlled system: 4 K/h
Degree of protection: IP30
Protection class: II (after according installation)
Max. admissible air moisture: 95% r.h., non condensing
Housing material and colour: plastic (ABS), pure white (similar to RAL 9010)
Energy efficiency class: I (contribution to seasonal space heating energy
efficiency 1%)
Der Raumtemperaturregler erfasst mit einem innenliegenden Bimetallfühler die Raumtemperatur und
regelt entsprechend dem eingestellten Sollwert. Die einzelnen Reglertypen unterscheiden sich durch die
Ausstattung, wie Schalter „Ein / Aus“ und „Lüfterausgang“ (.026), Schalter „Heizen / Kühlen“ (.065),
Schalter „Absenken / Komfort / Automatik“, (.075) Lampe grün „Absenkung“ (.075).
Thermische Rückführung
Da während des Heiz- oder Kühlvorgangs der Regler die Raumtemperatur erst relativ spät erfasst, wird
mittels einer thermischen Rückführung der Regler rechtzeitig zum Ausschalten angeregt und so eine
sehr genaue Schaltdifferenz erreicht.
Bereichseinengung
Mittels der sich unter dem Knopf befindlichen Einstellfahnen kann der Einstellbereich mechanisch
begrenzt werden (vgl. Punkt 6.).
Nachtabsenkung
Bei Reglern mit Absenkbetrieb (Uhrensymbol im Anschluss-Schaltbild) wird bei Beschalten der
Klemme mit 230 V~ die Raumtemperatur um ca. 4K abgesenkt.
5. Klemmen- und Bediensymbole
Symbol Bedeutung
L Phase Versorgungsspannung
N Neutralleiter
Ausgang Heizen
Temperatur-Absenkeingang (ECO-Eingang)
Zusatzheizung
Ventilatorausgang
(als Klemmensymbol) Ausgang Kühlen
(als Bediensymbol) Frostschutz ca. 5°C
I Ein
OAus
Temperatur-Absenkbetrieb (ECO-Betrieb)
Temperatur-Wohlfühlpunkt
5. Terminals and operating symbols
Symbol Explanation
L Supply voltage phase
N Neutral conductor
Heating output
Temperature decrease input (ECO input)
Additional heating
Fan output
(terminal symbol) Cooling output
(operating symbol) Fros protection (approx 5°C)
ION
O OFF
Temperature decrease mode (ECO mode)
Thermal well-being point
Die von uns genannten technischen Daten wurden unter Laborbedingungen nach allgemein gültigen Prüfvorschriften, insbesondere DIN-Vorschriften, ermittelt. Nur insoweit werden Eigenschaften
zugesichert. Die Prüfung der Eignung für den vom Auftraggeber vorgesehenen Verwendungszweck bzw. den Einsatz unter Gebrauchsbedingungen obliegt dem Auftraggeber; hierfür übernehmen wir
keine Gewährleistung. Änderungen vorbehalten.
The technical data specified herein have been determined under laboratory conditions and in compliance with generally approved test regulations, in particular DIN standards. Technical characteristics can
only be warranted to this extent. The testing with regard to the qualification and suitability for the client’s intended application or the use under service conditions shall be the client’s own duty. We refuse
to grant any warranty with regard thereto. Subject to change without notice.
I dati tecnici indicati in queste avvertenze di montaggio sono stati rilevati in laboratorio in conformità con le norme di controllo correnti, soprattutto con le norme DIN. La caratteristiche tecniche vengono
garantire solo in tale misura. Il controllo del dispositivo in relazione all’idoneità per lo scopo di destinazione previsto dal committente e all’impiego in condizioni di servizio è a carico del cliente. Non as-
sumiamo alcuna garanzia al riguardo. Salvo modifiche di ordine tecnico.
ALRE-IT Regeltechnik GmbH · Richard-Tauber-Damm 10 · D-12277 Berlin
Tel.: +49(0)30/399 84-0 · Fax: +49(0)30/ 391 70 05 · mail@alre.de · www.alre.de
Avvertimento di sicurezza!
Questo apparecchio può essere aperto esclusivamente da un elettricista ed installato in base allo
schema elettrico, riportato nel coperchio della scatola / sulla scatola / nelle istruzioni per l’uso.
Le istruzioni per l’uso dovranno essere custodite per il personale di servizio e di manutenzione in
un punto accessibile. Dopo l’installazione l’operatore dovrà essere istruito dall’installatore sul fun-
zionamento e sul comando della regolazione.
I
Per facilitare l’installazione del dispositivo il regolatore viene fornito aperto. Si raccomanda di effettuare
l’installazione su una presa incassata. Il dispositivo serve può essere tuttavia anche installato su un sot-
tofondo piano non conduttore. L’apertura e la chiusura del dispositivo avvengono come descritto nel
3. Installazione
Questo termostato elettronico a bimetallo è stato concepito specialmente per il controllo ed il monitor-
aggio di temperature negli uffici, nelle abitazioni e negli alberghi. Esso é idoneo soprattutto per il
controllo di tutti i tipi di sistemi di riscaldamento. Con i sistemi di riscaldamento per il pavimento assi-
curarsi che la potenza di riscaldamento non surriscaldi il pavimento anche a regime continuato. Per
riscaldamenti ad acqua calda utilizzare al massimo 10 valvole chiuse diseccitate all’uscita del riscalda-
mento o al massimo 5 valvole aperte diseccitate all’uscita del raffreddamento. Nel tratto di raffredda-
mento collegare al massimo 5 valvole chiuse diseccitate all’uscita del raffreddamento o al massimo 10
valvole aperte diseccitate all’uscita del riscaldamento.
Attenzione! Per il tipo di regolatore RTBSB-001.065, idoneo per sistemi di climatizzazione a doppio
tubo, lo stampaggio sul commutatore «riscaldamento / raffreddamento» è concepito per valvole chiuse
diseccitate. Gli altri tipi di regolatori descritti in queste istruzioni sono stati sviluppati soprattutto per
sistemi di climatizzazione a 4 tubi. Se necessario, installare anche limitatori di temperatura.
Per altri settori d’impiego, non previsti dal costruttore, osservare le norme di sicurezza speci-
fiche. Per la compatibilità vedi punto 9 (Garanzia).
1. Applicazione
Il termostato descritto rileva con un sensore a bimetallo interno la temperatura ambiente e regola in base al
valore nominale impostato. I singoli tipi di regolatore si distinguono per l’equipaggiamento, come interruttori
«AVVIO / ARRESTO» e «uscita ventilatore» (.026), interruttori «riscaldamento / raffreddamento» (.065),
interruttori «abbassamento/comfort/automatico» (.075), spia luminosa verde «abbassamento» (.75).
Retroazione termica
Dal momento che durante il ciclo di riscaldamento o di raffreddamento il termostato rileva la temperatura
ambiente con relativo ritardo, con una retroazione termica il termostato viene eccitato tempestivamente per il
disinserimento, raggiungendo così un differenziale molto preciso.
Restringimento di campo
Con le linguette di regolazione sotto il pulsante la campo di regolazione può essere limitato meccanicamente
(vedi punto 6).
Abbassamento della temperatura notturna
Per termostati con funzione di abbassamento della temperatura (indicato dal simbolo dell’orologio nello
schema di collegamento), la temperatura esistente in un locale si abbassa di circa 4K al passaggio di una
tensione di 230 V~ sul morsetto .
2. Funzionamento
9. Gewährleistung / Warranty / Garanzia
4. Dati tecnici
Sensore: bimetallo, tipo 1C
Tensione d’alimentazione e potenza di rottura: vedi capitolo 7, targhetta d’identificazione
Campo di regolazione: 5 … 30°C
Differenziale: circa 0,5 K
Scala: in °C
Velocità max. di variazione
temperatura del sistema controllato: 4 K/h
Tipo di protezione: IP30
Indice di protezione: II (in base all’installazione corrispondente)
Umidità max. dell’aria: 95% d’umidità relativa dell’aria, non condensante
Materiale e colore della scatola: in plastica (ABS), bianco puro (simile a RAL 9010)
Classe di efficienza energetica: I (contributo dell’1% di efficienza energetica per il
riscaldamento stagionale)
6. Installationshinweise / Installation information / Istruzioni per l’installazione
Einstellfahne
für minimalen
Temperaturwert
Pin for the
setting of the
minimum
temperature value
Linguetta regolazione
per valore termico
minimo
Einstellfahne
für maximalen
Temperaturwert
Pin for the
setting of the
maximum
temperature value
Linguetta regola-
zione per valore
termico massimo
5. Terminali e simboli operativi
Simbolo Spiegazione
L Fase tensione di alimentazione
N Conduttore neutro
Uscita riscaldamento
Temperatura ingresso abbassamento (ingresso ECO)
Riscaldamento supplementare
Uscita ventilatore
(simbolo terminale) Uscita raffreddamento
(simbolo servizio) Protezione antigelo ca. 5°C
ION
O OFF
Temperatura modo abbassamento (modo ECO)
Temperatura punto benessere
capitolo 6. Per l’apertura togliere innanzitutto il pulsante, premere quindi il gancetto con un cacciavite
leggermente all’interno ed aprire il coperchio del termostato, rivoltando verso il basso. Le prese di ven-
tilazione non devono essere chiuse, altrimenti possono verificarsi regolazioni scorrette.
Attenzione: il regolatore descritto è idoneo per resistere alle impurità che si producono abitualmente in
abitazioni ed uffici. Lo sporco e la polvere prodotti durante i lavori d’installazione e di rinnovo possono
sporcare i contatti e provocare il mancato funzionamento del regolatore. In tal caso i contatti dovranno
essere ripuliti da un elettricista specializzato. L’operazione può essere effettuata, ad esempio, con getti
d’aria o con un pennello.
7. Maßbild und Anschluss-Schaltbilder
Dimensional drawing and connection diagram
Schizzo quotato e schemi collegamento
8. Montagehinweis
Mounting information
Avvertenza di montaggio

This manual suits for next models

12

Other alre Temperature Controllers manuals

alre RTBSB-001 Series User manual

alre

alre RTBSB-001 Series User manual

alre RTBSB-001.086 User manual

alre

alre RTBSB-001.086 User manual

alre FTRFB-280 Series User manual

alre

alre FTRFB-280 Series User manual

alre FTR 101.2 Series User manual

alre

alre FTR 101.2 Series User manual

alre RTERU-010.715# Series User manual

alre

alre RTERU-010.715# Series User manual

alre ITR 79 User manual

alre

alre ITR 79 User manual

alre RTBSB-001.096 User manual

alre

alre RTBSB-001.096 User manual

alre RTBSB-001 Series User manual

alre

alre RTBSB-001 Series User manual

alre RTBSB-001 Series User manual

alre

alre RTBSB-001 Series User manual

alre FTRFB-080 Series User manual

alre

alre FTRFB-080 Series User manual

alre RTBSB-201.500 User manual

alre

alre RTBSB-201.500 User manual

alre RTBSB-201 Series User manual

alre

alre RTBSB-201 Series User manual

alre FETR 101.715 User manual

alre

alre FETR 101.715 User manual

alre KTRRUu 217.456 User manual

alre

alre KTRRUu 217.456 User manual

alre FETR 101.715 Guide

alre

alre FETR 101.715 Guide

alre FETR 101.700 User manual

alre

alre FETR 101.700 User manual

alre RTBSB-201.2 Series User manual

alre

alre RTBSB-201.2 Series User manual

alre RTBSB-201 Series User manual

alre

alre RTBSB-201 Series User manual

alre BTF2 User manual

alre

alre BTF2 User manual

alre RTBSB-001.500 User manual

alre

alre RTBSB-001.500 User manual

alre RTBSB-001 Series User manual

alre

alre RTBSB-001 Series User manual

Popular Temperature Controllers manuals by other brands

Heat Controller B-VCH12FC-1 owner's manual

Heat Controller

Heat Controller B-VCH12FC-1 owner's manual

Vaillant VRC 470 installation instructions

Vaillant

Vaillant VRC 470 installation instructions

Sentera RXTP Series Mounting and operating instructions

Sentera

Sentera RXTP Series Mounting and operating instructions

WIKA CS4S operating instructions

WIKA

WIKA CS4S operating instructions

Powtier Controls TC308 instruction manual

Powtier Controls

Powtier Controls TC308 instruction manual

Crow SH-TEMP-PRB-XT instruction manual

Crow

Crow SH-TEMP-PRB-XT instruction manual

M&C TRN operating manual

M&C

M&C TRN operating manual

Poniie TC-10A user manual

Poniie

Poniie TC-10A user manual

Store It Cold CoolBot Trouble error codes list

Store It Cold

Store It Cold CoolBot Trouble error codes list

FLIR Screen-EST Kiosk user manual

FLIR

FLIR Screen-EST Kiosk user manual

gefran 650 Series Abbreviated Manual

gefran

gefran 650 Series Abbreviated Manual

Auber Instruments WS-1510DPM Operation & instruction manual

Auber Instruments

Auber Instruments WS-1510DPM Operation & instruction manual

Omron E5*N Series Solutions Guide for FAQs

Omron

Omron E5*N Series Solutions Guide for FAQs

JUMO safetyM TB/TW operating instructions

JUMO

JUMO safetyM TB/TW operating instructions

Ekinex EK-EQ2-TP- Series Applications manual

Ekinex

Ekinex EK-EQ2-TP- Series Applications manual

Clint floyd FVW Series Instructions for installation, use and maintenance manual

Clint

Clint floyd FVW Series Instructions for installation, use and maintenance manual

RKC INSTRUMENT RZ100 instruction manual

RKC INSTRUMENT

RKC INSTRUMENT RZ100 instruction manual

SMC Networks HRS400 Series manual

SMC Networks

SMC Networks HRS400 Series manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.