Overview:
These Altronix Rack Mount CCTV Power Supplies provide 24VAC or 28VAC distributed via sixteen (16) fuse or PTC
protected outputs for powering CCTV Cameras, heaters and other video accessories.
Sixteen (16) Output Rack Mount Configuration Reference Chart:
R2416UL 24 7 amp (175VA) 16 - x 3.5 amp 3 amp
R2416ULCB 24 7 amp (175VA) 16 x - 2.5 amp 3 amp
R2416300UL 24 12.5 amp (300VA) 16 - x 3.5 amp 3 amp
28 10 amp (280VA) 16 - x 3.5 amp 3 amp
R2416300ULCB 24 12.5 amp (300VA) 16 x - 2.5 amp 3 amp
28 10 amp (280VA) 16 x 2.5 amp 3 amp
R2416600UL* 24 25 amp (600VA) 16 - x 3.5 amp 6 amp
28 20 amp (560VA) 16 - x 3.5 amp 6 amp
R2416600ULCB* 24 25 amp (600VA) 16 x - 2.5 amp 6 amp
28 20 amp (560VA) 16 x - 2.5 amp 6 amp
*24VAC models: Outputs 1-8 provide 12.5 amp (300VA) max. Outputs 9-16 provide 12.5 amp (300VA) max.
*28VAC models: Outputs 1-8 provide 10 amp (280VA) max. Outputs 9-16 provide 10 amp (280VA) max.
Specifications:
•UL Listed - U.S. and Canada for CCTV Equipment (UL2044). • Power switch with built-in circuit breaker.
•24VAC or 28VAC (Factory set @ 24VAC). • Sixteen (16) individual power LED indicators.
•2U rack mount chassis for use in standard EIA 19” rack. • Removable terminal blocks with locking screw
•Surge suppression. flange.
•Ease of installation saves time and eliminates • Unit maintains camera synchronization.
costly labor. Rack Dimensions:
3.25”H x 19.125”W x 8.5”D
Installation Instructions:
1. The unit is factory set for 24VAC operation.
For 28VAC operation, adjust unit prior to mounting and applying power as follows:
a. Open bottom of unit by removing six (6) screws (Rack Mechanical Drawing & Dimensions, pg. 4).
b. Change the wire position so that the black wire [28V] is connected to the terminal marked [P] and
the yellow wire [24V] is connected to the terminal marked [S].
c. After securing all wires for proper voltage place bottom panel back on the unit and fasten with the six (6) screws.
2. Mount unit in desired rack location (Space unit at least 3” from any video monitors), Do not obstruct side air vents.
3. Set power switch on back of unit to the OFF position (Fig. 1C, pg. 3).
4. Plug power cord into grounded 115VAC 50/60 Hz receptacle (Fig. 1C, pg. 3), ground should be connected
as indicated in (Fig. 1, pg. 3).
5. Set power switch on back of unit to the ON (RESET) position and measure output voltage before connecting devices
(Fig. 1C, pg. 3). This helps avoid potential damage.
All terminals with common suffix (P) “1P, 2P...” are the same polarity.
6. Set power switch on back of unit to the OFF position (Fig. 1C, pg. 3).
7. Connect devices to removable terminal blocks marked [1P & 1N through 8P & 8N] (Fig. 1A, pg. 3).
When wiring is completed on terminal blocks they can be locked down by tightening screw flanges.
8. Upon completion of wiring, set power switch on back of unit to the ON (RESET) position (Fig. 1C, pg. 3).
Altronix
Model Number
Output Current
(max per output)
Total Output
Current (Power)
Output Voltage
(VAC)
115VAC 50/60Hz
Input Current
Fuse Protected
Outputs
- 2 -
Number of
Outputs
PTC Protected
Outputs (Class 2
power limited).