CY-210D
4.Connection
4-9
⑪DSW2-(3) Selects a schedule No.
OFF: Starts with external schedule No.
ON: Starts with schedule No. on panel
If this dip switch is set to OFF, a schedule No. is selected
and operation starts upon the reception of start signal
[START 1, 2, 4, and/or 8] from outside. If this dip switch is
set to ON, operation starts upon reception of a start-signal
No. selected using the panel. The schedule can be
changed by pressing the SCHEDULE [NUMBER] key.
External start signals are used only to start welding, and
the schedule cannot be selected.
⑫DSW2-(4) Selects start using 4-schedule start mode or 15-schedule start
mode upon receiving an external start signal.
OFF: 15-schedule start mode
ON: 4-schedule start mode
If this dip switch is set to OFF, 15 schedules made by
combining start signals [START 1, 2, 4, and/or 8] are
selected. If this dip switch is set to ON, the
lowest-numbered start signal among 1, 2, 4, and 8 that is
on 20 ms after the first start signal is turned on, is selected.
⑬DSW2-(5) Selects Data Out.
OFF: Does not output data
ON: Outputs data
The data-out function is optional. Set this switch to the OFF
position when the option is not provided.
⑭DSW2-(6) Selects the control speed in constant-current control.
OFF: Half-cycle
ON: 1 cycle
⑮DSW2-(7) Sets the correction value for the constant-current control, or sets it
so that it is variable.
OFF: Fixed constant-current correction value
ON: Variable constant-current correction value
This switch should normally be in the OFF position.
When the weld control is used with a single-phase welding
machine, the welding current rarely rises abnormally to
overshoot or an extremely slow rise occurs. In this case,
set this switch to the ON position, making the
constant-current correction-value variable. When
DSW2-(7) is set to ON, Modes Nos. 8 and 9 are selectable
on the panel. Set the correction value for the initial rise
(G1) in Mode No. 8 (a larger setting provides a larger
amount of correction). Set the correction value for the initial
rise (G2) in Mode No. 9 after the current exceeds the
current setting (a larger setting provides a larger amount of
correction). When there is a big difference between
currents on the plus side and the minus side (the currents
are not balanced), set DSW2-(6) to ON (1 cycle).
Current setting
(10-99) (10-99)
Shipped at G1 = 50, G2 = 50