
SYSTEM OPERATION
15
COOLING
The refrigerant used in the system is R-22. It is a clear,
colorless,non-toxic,non-irritating,andnon-explosiveliquid.
The chemical formula is CHCLF2. The boiling point, at
atmosphericpressureis-41.4°F.
Afewoftheimportantprinciplesthatmaketherefrigeration
cycle possible are: heat always flows from a warmer to a
cooler body, under lower pressure a refrigerant will absorb
heatand vaporize at a lowtemperature, the vaporsmay be
drawnoffandcondensedatahigherpressureandtempera-
ture to be used again.
Theindoorevaporatorcoilfunctionstocoolanddehumidify
theairconditionedspacesthroughtheevaporativeprocess
taking place within the coil tubes.
NOTE: The pressures and temperatures shown in the
refrigerant cycle illustrations on the following pages are for
demonstrationpurposesonly.Actualtemperaturesandpres-
sures are to be obtained from the "Expanded Performance
Chart."
Liquidrefrigerantatcondensingpressureandtemperatures,
(270 psig and 122°F), leaves the outdoor condensing coil
throughthedrierandismeteredintotheindoorcoilthrough
the metering device. As the cool, low pressure, saturated
refrigerantentersthetubesoftheindoorcoil,aportionofthe
liquidimmediatelyvaporizes.Itcontinuestosoakupheatand
vaporizesasitproceedsthroughthecoil,coolingtheindoor
coil down to about 48°F.
Heatiscontinuallybeingtransferredtothecoolfinsandtubes
of the indoor evaporator coil by the warm system air. This
warming process causes the refrigerant to boil. The heat
removedfromtheairiscarriedoffbythevapor.
As the vapor passes through the last tubes of the coil, it
becomes superheated, that is, it absorbs more heat than is
necessarytovaporizeit.Thisisassurancethatonlydrygas
will reach the compressor. Liquid reaching the compressor
canweakenorbreakcompressorvalves.
The compressor increases the pressure of the gas, thus
addingmoreheat,anddischargeshot,highpressuresuper-
heated gas into the outdoor condenser coil.
Inthecondensercoil,thehotrefrigerantgas,being warmer
than the outdoor air, first loses its superheat by heat trans-
ferredfromthegasthroughthetubesandfinsofthecoil.The
refrigerantnowbecomessaturated,partliquid,partvaporand
then continues to give up heat until it condenses to a liquid
alone.Oncethevaporisfullyliquefied,itcontinuestogiveup
heat which subcools the liquid, and it is ready to repeat the
cycle.
HEATING
Theheatingportionoftherefrigerationcycleissimilartothe
coolingcycle.Byenergizingthereversingvalvesolenoidcoil,
the flow of the refrigerant is reversed. The indoor coil now
becomesthecondensercoil,andtheoutdoorcoilbecomes
theevaporatorcoil.
The check valve at the indoor coil will open by the flow of
refrigerant letting the now condensed liquid refrigerant by-
pass the indoor expansion device. The check valve at the
outdoor coil will be forced closed by the refrigerant flow,
therebyutilizingtheoutdoorexpansiondevice.
TherestrictororificeusedwiththeCA*F,CHPFcoils andthe
AR*Fair handler will beforced ontoa seatwhenrunning in
the cooling cycle, only allowing liquid refrigerant to pass
through the orifice opening. In the heating cycle it will be
forcedofftheseatallowingliquidtoflowaroundtherestrictor.
A check valve is not required in this circuit.
COOLINGCYCLE
When the contacts of the room thermostat close making
terminalsRtoY&G,thelowvoltagecircuitofthetransformer
iscompleted.Currentnowflowsthroughthemagnetichold-
ing coils of the compressor contactor (CC) and fan relay
(RFC).
This draws in the normally open contact CC, starting the
compressor and condenser fan motors. At the same time
contacts RFC close starting the indoor fan motor.
When the thermostat is satisfied, it opens its contacts,
breaking the low voltage circuit, causing the compressor
contactor and indoor fan relay to open, shutting down the
system.
If the room thermostat fan selector switch should be set on
the"on"position,thentheindoorblowerwouldruncontinuous
rather than cycling with the compressor.
Heat pumps energize the reversing valve thorough the "O"
circuitintheroomthermostat.Thereforethereversingvalve
remains energized as long as the thermostat subbase is in
the cooling position. The only exception to this is during
defrost.
DEFROSTCYCLE
The defrosting of the outdoor coil is jointly controlled by the
defrosttimingboard, defrost(30/60)control,andcompressor
run time.
HEATINGCYCLE
Thereversingvalveontheheatpumpmodelsisenergizedin
the cooling cycle through the "O" terminal on the room
thermostat.
Thesemodelshavea24voltreversingvalvecoil.Whenthe
thermostatselector switch is set in the cooling position, the
"O" terminal on the thermostat is energized all the time.
Caremustbetakenwhenselectingaroomthermostat.Refer
to the installation instructions shipped with the product for
approvedthermostats.