APG FLR Series User manual

Operator’s Manual
AUTOMATION
PRODUCTS
GROUP, INC.
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300•Fax:1/435/753-7490• www.apgsensors.com•E-mail:[email protected]
FLR
Series
Magnetic Float Sensors
9003284
Rev. A5, 10/09

FLR Series Rev. A5, 10/09
2
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
Table of Contents
Warranty ......................................................................................... 3
Description...................................................................................... 4
Installation ................................................................................... 5-6
Wiring.............................................................................................. 7
Circuit Protection ........................................................................... 8
Field Adjustment of Actuation Point......................................... 9-21
Inspection & Maintenance ............................................................ 22
Technical Notes............................................................................. 22
Specifications ................................................................................ 23

Rev. A5, 10/09 FLR Series
3
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
APG warrants its products to be free from defects of material and workmanship
and will, without charge, replace or repair any equipment found defective upon
inspection at its factory, provided the equipment has been returned,
transportation prepaid, within 24 months from date of shipment from factory.
THE FOREGOING WARRANTYIS IN LIEU OFAND EXCLUDESALLOTHER
WARRANTIES NOTEXPRESSLYSET FORTH HEREIN, WHETHER
EXPRESSED OR IMPLIED BYOPERATION OF LAWOR OTHERWISE
INCLUDING BUT NOTLIMITED TOANYIMPLIED WARRANTIES OF
MERCHANTABILITYOR FITNESS FORAPARTICULAR PURPOSE.
No representation or warranty, express or implied, made by any sales
representative, distributor, or other agent or representative of APG which is not
specifically set forth herein shall be binding uponAPG. APG shall not be liable
for any incidental or consequential damages, losses or expenses directly or
indirectly arising from the sale, handling, improper application or use of the
goods or from any other cause relating thereto andAPG’s liability hereunder, in
any case, is expressly limited to the repair or replacement (at APG’s option) of
goods.
Warranty is specifically at the factory. Any on site service will be provided at
the sole expense of the Purchaser at standard field service rates.
All associated equipment must be protected by properly rated electronic/
electrical protection devices. APG shall not be liable for any damage due to
improper engineering or installation by the purchaser or third parties. Proper
installation, operation and maintenance of the product becomes the
responsibility of the user upon receipt of the product.
Returns and allowances must be authorized byAPG in advance. APG will
assign a Return Material Authorization (RMA) number which must appear on
all related papers and the outside of the shipping carton. All returns are subject
to the final review by APG. Returns are subject to restocking charges as
determined by APG’s “Credit Return Policy”.
• Warranty and Warranty Restrictions

FLR Series Rev. A5, 10/09
4
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
•Description
The FLR series instruments contain reed switches in the stem and permanent
magnets in the floats. As the float rises or falls with the level of the liquid, the
magnet inside the float act on the reed switch inside the stem to provide the
SPST switching action.
Permanent Magnet
Float Travel-Stop
Float
Stem
Reed Switch

Rev. A5, 10/09 FLR Series
5
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
•Installation
- Unpacking -
When unpacking the instrument, exercise care not to subject the instrument to
mechanical shock. After unpacking, visually inspect the instrument for
damage.
- Environment -
The FLR series sensors should be installed in an areas indoor or outdoor
which meets the following conditions:
1. Non-hazardous area.
2. The medium temperature does not exceed -400F to 1850F (-140C to 850C).
NOTE: It is recommended that a sun shield be installed over the housing if
exposed to direct sunlight.
3. Relative humidity up to 100%
4. Pollution Degree 2
5. Measurment Category II
6. Altitude 2000 m or less.
7. Locate the sensor away from strong magnetic fields such as those
produced by motors, transformers, solenoid valves, etc.
8. The medium is free from metallic substances and other foreign matter.
9. No corrosive gases such as NH3, SO2, Cl2, etc.
10. No excessive vibration
11. Ample space for maintenance and inspection.

FLR Series Rev. A5, 10/09
6
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
•Installation
- Location -
Do not locate the FLR series sensor near inlets/outlets.
If there is surface wave action, then use a time-delay relay or stilling tube. If a
stilling tube is used, drill vent holes in the tube and use a spacer to assure the
float has free travel inside the tube.
Wave action may cause switch to chatter.Use a stilling tube or time-delay
relay to prevent switch chatter.
- Mounting -
The FLR can be mounted up to 300from vertical.
1. Flange Mounting
Provide the compatible mating flange on the tank and install using a suitable
gasket.
2. Plug Mounting
Provide the compatible female boss on the tank and install the FLR with a
suitable gasket, O-ring, or thread tape.
Stilling Tube
Inflow Inflow
Spacer

Rev. A5, 10/09 FLR Series
7
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
•Wiring
7
L1 L2 L3 L4
BlackBlack White White Red Red Green Green
Wiring Color
L1
L1
L2
L3
L4
L5
L6
L7
L2 L3 L4 L5 L6 L7 Com.
Blk x 2
Blk x 2
Blk x 2
Blk x 2
Black
Black
Black
Wh x 2
Wh x 2
Wh x 2
White
White
White
Red x 2
Red x 2
Red
Red
Red
Grn x 2
Green
Green
Green
Yellow
Yellow
Yellow
Brown
Brown
Grey
Grey
GreyBlue
Number
of
Levels
L1 L2 L3 L4 L5 L6 L7
Common
Black White Red Green GreyBlueBrownYellow
- Wiring for 1 to 4 switches
- Wiring for greater than 4 switches

FLR Series Rev. A5, 10/09
8
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
•Circuit Protection
WARNING!
DO NOT EXCEED CONTACT RATINGS! When an inductive load is used
(e.g. a motor, a coil, or an electromagnetic relay), a back electromotive
force of several hundred volts (energy stored in the inductance) arises
when the contacts are opened. This results in considerable decrease in
contact life. The same result arises even when a resistive load is used
with a high voltage or a large current. The figures below show circuits for
protecting the reed switch(s) from the back electromotive force.
L
C
R
E
C = I
R = Approx. 10 x I (I + 50/E)
E
Protecting Circuit Using CR
Protecting Circuit Using Varistor
Protecting Circuit Using Diode
2
/10 (uF)
Code A & B Switches
Max. contact capacity 70 VAAC,
Max. switching current 220 VAC 0.5A, 120 VDC 0.5A
Code C Switches
Max. contact capacity 110 VAAC,
Max. switching current 220 VAC 0.5A, 115 VDC 0.5 A

Rev. A5, 10/09 FLR Series
9
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
•Field Adjustment Of Actuation Point(s)
The FLR sensors are designed to allow field adjustments of the actuation
points by moving the floats and reed switches. This section contains two
procedures for making field adjustments.
NOTE: FLR units without housings are hermetically sealed and cannot be
field adjusted.
Procedure one should be used under the following conditions:
a. You want to move the actuation point relative to the factory settings.
b. Their will be no change to the switching logic (normally open/normally
closed).
Procedure two should be used under the following conditions:
a. The float stops have been loosened and moved without marking their
previous stem location.
b. The switching logic needs to be reversed (normally open/normally
closed).
c. You want to move the actuation point independant of the factory settings
1. Before making any adjustments to the FLR, mark the stem location of the
float stops that will need to be moved.
Procedure One:

FLR Series Rev. A5, 10/09
10
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
3. Loosen the retaining hex screws on the float stops and slide the stops
exactly the same distance along the stem to their new locations. Re-secure the
stops to the stem.
For example (refer to drawing above): Suppose the actuation point needs to be
adjusted 85 mm lower on the stem. The first step is to mark the location of
both float stops that will need to be moved. Next, move the float stops (and
float) exactly 85 mm down the stem from your marks. Re-secure the stops to
the stem and continue to step 4.
85 mm
85 mm
Marks of previous
stop locations
New
Actuation
Point
2. Determine the location of the new actuation point. The actuation point is
located at the center point between the float stops.

Rev. A5, 10/09 FLR Series
11
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
5. Carefully remove the terminal mounting plate along with the wiring and
internal reed switch assembly from the stem of the FLR. Keep the assembly
straight and take care not to bend or put stress on the reed switches.
4. Once the stops and float are set in the desired location, the reed switch
assembly inside the stem needs to be adjusted to match the new actuation
point. To access the reed assembly, you will need to remove the two screws
that secure the terminal mounting plate to the housing.

FLR Series Rev. A5, 10/09
12
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
7. If you look closely at the reed switch assembly rod, you will notice a black
mark at each reed switch location. During factory calibration, these marks are
used to align the center of each reed switch with the desired actuation point.
To align the reed switch with the newly adjusted float position, simply move
the reed switch along the rod the same distance that you previously moved the
float stops on the stem. This distance is measured from the center of the reed
switch to the black mark on the rod.
8. Once the reed switches have been moved into the correct position, use
electrical tape to re-secure the wires to the assembly rod. You are now ready to
carefully reassemble the FLR and test the new actuation point.
6. Carefully lay the reed switch assembly on a clean surface and remove the
tape securing the wires to the assembly rod. Do not cut into the wires!

Rev. A5, 10/09 FLR Series
13
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
Procedure Two:
1. Determine the desired actuation point.
2. Loosen the retaining screws on float stops that need to be repositioned.
3. Slide the float along the stem until the float’s center is aligned with the
desired actuation point.
4. Re-secure the float stops 9 mm above and below the new float position (refer
to drawing below).
NOTE: The 9 mm distance between the float and stops is critical for the switch
to operate reliably.
Desired
Actuation
Point
9 mm
9 mm
•Field Adjustment Of Actuation Point(s)

FLR Series Rev. A5, 10/09
14
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
6. Carefully remove the terminal mounting plate along with the wiring and
internal reed switch assembly from the stem of the FLR. Keep the assembly
straight and take care not to bend or put stress on the reed switches.
5. With the float and stops in place at the new actuation point, the internal reed
switch needs to be repositioned to match the new actuation point. Remove the
two screws that secure the terminal mounting plate to the housing (shown
above).

Rev. A5, 10/09 FLR Series
15
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
7. Measure the distance from the bottom of the stem to the new actuation point.
The actuation point is at the center position between the float stops. In the
example above, the actuation point is at 250 mm.
8. Abrass rod inside the stem holds the reed switches in place. The location of
the switch needs to be adjusted to match the new actuation point. Determine
which switch type you are using and continue to the step indicated below.
NOTE: The float is considered in the “normal” position when it is at
rest against the lower stop.
CODE “A & B” (approx. 20 mm switch length)
CODE “C” (approx. 30 mm switch length)
Normally Open continue to step 8a
(page 15)
Normally Closed skip to step 8b
(page 16)
Normally Open skip to step 8c
(page 17)
Normally Closed skip to step 8d
(page 18)

FLR Series Rev. A5, 10/09
16
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
8a. For “normally open” (NO) switching (codeA& B switches), subtract 6 mm
from the measurement taken in step 7 and record the result. This distance will
be used to adjust the reed switch along the internal brass rod. The 6 mm is
subtracted to compensate for the plug in the bottom of the stem. Refer to
drawings below.
Actuation
Point
Indention designates
top of float
ON
OFF
For normally open (NO) switching action
with a Code "A" or "B" switch, the center
point of reed switch assembly is set in line
with the float center.
9 mm
9 mm
Normally Open Switching for Code “A” & “B” Switches
Plug
Approx. 6 mm
Brass Rod

Rev. A5, 10/09 FLR Series
17
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
8b. For “normally closed” (NC) switching (codeA& B switches), subtract 18
mm from the measurement taken in step 7 and record the result. This distance
will be used to adjust the reed switch along the internal brass rod. The 18 mm
is subtracted to compensate for both the offset of the reed switch from the
actuation point (-12 mm), and the plug in the bottom of the stem (-6 mm).
Refer to drawings below.
Normally Closed Switching for Code “A” & “B” Switches
For normally closed (NC) switching
action with a Code "A" or "B" switch,
the center point of reed switch assembly
is set 12mm below the actuation point.
Indention designates
top of float
ON
OFF
12 mm
Actuation
Point
9 mm
9 mm
Plug
Approx. 6 mm
Brass Rod

FLR Series Rev. A5, 10/09
18
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
8c. For “normally open” (NO) switching (code C switches), subtract 3 mm from
the measurement taken in step 7 and record the result. This distance will be
used to adjust the reed switch along the internal brass rod. The 3 mm is
subtracted to compensate for both the offset of the reed switch from the
actuation point (+3 mm), and the plug in the bottom of the stem (-6 mm). Refer
to drawings below.
Indention designates
top of float
For normally open (NO)
switching action, the center
point of reed switch is set 3 mm
above the desired actuation point.
ON
OFF
3 mm
9 mm
9 mm
Actuation
Point
Normally Open Switching for Code “C” Switches
Plug
Approx. 6 mm
Brass Rod

Rev. A5, 10/09 FLR Series
19
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
8d. For “normally closed” (NC) switching (code C switches), subtract 12 mm
from the measurement taken in step 7 and record the result. This distance will
be used to adjust the reed switch along the internal brass rod. The 12 mm is
subtracted to compensate for both the offset of the reed switch from the
actuation point (-6 mm), and the plug in the bottom of the stem (-6 mm). Refer
to drawings below.
Normally Closed Switching for Code “C” Switches
For normally closed (NC)
switching action, the center
point of reed switch is set
6 mm below the desired
actuation point.
Indention designates
top of float
6 mm
9 mm
9 mm
ON
OFF
Actuation
Point
Plug
Approx. 6 mm
Brass Rod

FLR Series Rev. A5, 10/09
20
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel:1/888/525-7300• Fax:1/435/753-7490• www.apgsensors.com•[email protected]
9. Using the distance you derived in step 8, measure from the bottom of the
reed switch assembly and mark the center rod at that location.
10. Remove the tape securing the reed switch to the assembly rod. Be careful
not to cut any of the wires or to put pressure in the reed switch.
Table of contents
Other APG Accessories manuals
Popular Accessories manuals by other brands

GCS
GCS ZA1501IN-5 Installation & operation manual

Alutech
Alutech LM-L operating manual

lynx System Developers
lynx System Developers RadioLynx quick start guide

Pfeiffer Vacuum
Pfeiffer Vacuum RPT 010 operating instructions

Pioneer
Pioneer SGY-PM910H L Important information for the user

PASCO
PASCO Pasport AirLink2 instruction manual