manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. API
  6. •
  7. Security System
  8. •
  9. API APD 1700 Manual

API APD 1700 Manual

Frequency Input Alarm Trips, Factory Ranged Input APD 1700, APD 1720
Input: 0-25 Hz to 0-20 kHz
Output: Two 8 Amp SPDT Relays
OFactory Set Frequency Input Range
OAdjustable Setpoint and Deadband Potentiometers
OInput LoopTracker®and Alarm Status LEDs
OFull 1200 V Isolation
OAlarm Test, Optional Reset Button
QMachinery Speed Alarm
QRedundant or Backup Alarm
QConveyor or Machine Malfunction Alarm
Frequency Input Range
Factory configured, please specify input type and range
Frequency: 0-25 Hz to 0-20 kHz
Sine wave, sawtooth, or square wave with min. 5 µsec pulse
Input Impedance
At maximum sensitivity: 10 kWnominal
At minimum sensitivity: 100 kWnominal
Input Sensitivity/Hysteresis
Multi-turn potentiometer for sensitivity adjustment
Maximum sensitivity: ±25 mV typical
Minimum sensitivity: ±2.5 V typical
Input Amplitude Range
100 mV to 150 VRMS
Any waveform with minimum 100 mV amplitude change
Input Power Supply
15 VDC ±10%, regulated, 25 mADC, max. ripple, <10 mVRMS
May be used to power sensor
Input Protection
Normal mode: 200% of input rating
Common mode: 600 VDC or 600 VACpinput to ground
LoopTracker
Variable brightness LED indicates input loop level and status
APD 1700 Relay Output
Dual SPDT Form C contact sets operating in unison
1 setpoint adjustment, 1 deadband adjustment
Standard: HI alarm, non-latching, normal acting
Options: LO alarm, latching, reverse acting
APD 1720 Relay Output
2 independent SPDT Form C contact sets
2 setpoint adjustments, 2 deadband adjustments
Factory configured alarm
Standard: HI/LO alarm, non-latching, normal acting
Options: LO/LO, HI/HI, LO/HI alarms, band alarms,
latching, reverse acting
Relay Contact Ratings
8 A max @ 240 VAC resistive load
External contact protection such as an RC snubber is recom-
mended for inductive loads
Setpoint
12 turn potentiometer adjustable from 0 to 100% of span
Deadband
12 turn potentiometer adjustable from 1 to 100% of span
Output Test/Reset Button
Front button or external contact closure toggles relays to
opposite state when pressed.
Resets relay if latching relay option is ordered.
Ambient Temperature Range and Stability
–10°C to +60°C operating ambient
Better than 0.04% of span per °C
Switching Current (A)
Switching Voltage (V)
0 3 5 10 30 50 100 300 500
8
5
3
1
0.5
0.3
0.1
AC inductive load
(cos f= 0.4) AC resistive
load
DC inductive load
(L/R = 7 ms)
DC resistive
load
Alarm Options—add to end of model number
LAPD 1700 with LO trip. Alarm trips on decreasing signal.
HH APD 1720 with HI/HI trip. Alarms trip at their respective
trip points on increasing signal.
LL APD 1720 with LO/LO trip. Alarms trip at their respective
trip points on decreasing signal.
LH APD 1720 with LO/HI trip. Alarm 1 trips on decreasing
signal. Alarm 2 trips on increasing signal.
BA APD 1720 with band alarm. Alarm trips if signal is
outside LO and HI trip points.
IBA APD 1720 with inverse band alarm. Alarms trip if signal
is between LO and HI trip points.
HT Latching alarm with push button reset
HP Latching alarm with power-off reset. Module power
must be turned off to reset alarms
RA Reverse-acting alarms. Relay coils energized in an alarm
condition. No alarm condition with module power off.
UConformal coating for moisture resistance
Accessory—order as separate line item
API BP4 Spare removable 4 terminal plug, black
Applications
Dimensions
0.89" W x 4.62" H x 4.81" D
(22.5 x 117 x 122 mm)
Height includes connectors
Housing and Connectors
IP 40, requires installation in panel or enclosure
For use in Pollution Degree 2 Environment
Mount vertically to a 35 mm DIN rail
Four 4-terminal removable connectors, 14 AWG max wire size
Power
85-265 VAC, 50/60 Hz or 60-300 VDC, 2 W maximum
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 2 W maximum
Description
The APD 1700 and APD 1720 accept a frequency input and
provides a visual alarm indication and alarm relay contact
outputs.
The input is factory configured to a specific frequency
input range. The input can be of any type as long as it has
a minimum of 100 mV amplitude change and a minimum 5
microsecond pulse width. Input sensitivity is potentiometer
adjustable.
Front-accessible potentiometers are used to adjust alarm
setpoint and deadband.
LoopTracker and Alarm Status LEDs
API exclusive features include a LoopTracker LED that varies
in intensity with changes in the process input signal.
A red/green bicolor alarm status LED (two on the APD 1720)
visually indicate alarm status. These LEDs provide a quick
visual picture of your process at all times.
Output Test / Unlatch
The API exclusive Output Test button can be used to verify the
alarm and system operation and also provides the additional
function of unlatching the alarm when the latching option has
been ordered. This feature can be remotely operated.
The output test button greatly aids in saving time during initial
startup and/or troubleshooting.
© 03-22
api-usa.com
1220 American Way Libertyville, IL 60048
Phone: 800-942-0315 Fax: 800-949-7502
AABSOLUTEBSOLUTE PPROCESSROCESS IINSTRUMENTSNSTRUMENTS
Model Input Standard Alarm Configuration Power
APD 1700 Factory ranged
specify frequency range
0-25 Hz to 0-20 kHz
Single setpoint dual SPDT relays
HI alarm, non-latching, normal acting
85-265 VAC or 60-300 VDC
APD 1700 D 9-30 VDC or 10-32 VAC
APD 1720 2 setpoints, 2 SPDT relays
HI/LO alarms, non-latching, normal acting
85-265 VAC or 60-300 VDC
APD 1720 D 9-30 VDC or 10-32 VAC
Quick Link: api-usa.com/1700
Universal Power
Alarm Status LED
Input LoopTracker LED
Alarm Test Function
Adjustable Deadband
Two 8 Amp SPDT
Alarm Relays
Custom Input Ranges
Removable Plugs
File E145968
85-265 VAC, 60-300 VDC
model only
Adjustable Setpoint
Free Factory
I/O Setup!
HHHHHH
HHHHH
HHHHHH
HHHHH
HHHHHH
HHHHH
HHHHHH
HHHHH
HHHHHH
Made in USA
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
See Wiring
Diagrams on
Next Page
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
Applications Link
api-usa.com/apps
Precautions
WARNING! All wiring must be performed by a qualified electrician
or instrumentation engineer. See diagram for terminal designa-
tions and wiring examples. Consult factory for assistance.
WARNING! Avoid shock hazards! Turn signal input, output, and
power off before connecting or disconnecting wiring, or removing
or installing module.
Précautions
ATTENTION! Tout le câblage doit être effectué par un électricien
ou ingénieur en instrumentation qualifié. Voir le diagramme pour
désignations des bornes et des exemples de câblage. Consulter
l'usine pour assistance.
ATTENTION! Éviter les risques de choc! Fermez le signal d'entrée,
le signal de sortie et l'alimentation électrique avant de connecter
ou de déconnecter le câblage, ou de retirer ou d'installer le module.
Electrical Connections
See wiring diagrams. Observe input polarity.
*Do not make any connections to unused terminals or use them
as wiring junctions for external devices. This may cause perma-
nent damage to the module!
Input
The input range is pre-configured at the factory (at 24°C ±1°C).
The module is compatible with most types of sensors as long as
the waveform produces a minimum 100 mV amplitude change and
a minimum 5 microsecond pulse width.
Refer to the sensor manufacturer's data sheet to determine
proper wiring and supply voltage compatibility. A 15 VDC supply
is available to power the sensor if required.
The signal input is capacitively coupled to prevent any DC in the
input. Some sensors, typically those without an internal load
resistor, require a resistive load in order to function.
The resistor value may be specified by the sensor manufacturer
as the "minimum resistive load" or calculated from the sensor
manufacturer's specified "load current range".
The 15 VDC power supply is capable of providing 25 mA. A load
current range of 3 mA to 25 mA would typically use a 5 kWto
500 Wresistor.
NPN sensors use an external resistor across terminals 9 and 10
if required.
PNP sensors use an external resistor across terminals 9 and 11
if required.
Input Sensitivity Adjustment
A multi-turn potentiometer provides an adjustable threshold level
that the incoming signal must overcome before an output can
be produced. This is used to limit noise and minimize false input
signals that may cause erroneous alarm trips.
When fully clockwise (maximum sensitivity), the input threshold
is typically ±25 mV.
In the fully counterclockwise position (minimum sensitivity), the
input threshold is typically ±2.5 volts.
Alarm Types
Note that the deadband is symmetrical about the setpoint; relay
trip and reset points will both change if either the setpoint or
deadband are changed.
High Alarm (default, H, or HH): The alarm relay changes state
when the input signal exceeds the deadband trip point. The relay
resets when the input signal drops below the deadband reset
point. For a high alarm, the trip point is above the reset point.
Low Alarm (L or LL): The alarm relay changes state when the input
signal goes below the deadband trip point. The relay resets when
the input signal exceeds the deadband reset point. For a low alarm
the trip point is below the reset point.
HT: Latching alarm with push button reset
HP: Latching alarm with power-off reset. Module power must be
turned off to reset alarms
R: Reverse-acting alarms. Relay coils energized in an alarm con-
dition. No alarm condition with module power off.
Relay Output Terminals
See wiring diagrams below right for connections. APD modules do
not provide power to the relay contacts. Inductive loads (motors,
solenoids, contactors, etc.) will greatly shorten relay contact life
unless an appropriate RC snubber is installed.
The APD 1700 operates two sets of relays in unison with a single
setpoint. The dual SPDT contact sets are in a Form C configuration.
The APD 1720 operates two sets of relays independently, each
with its own setpoint. The dual SPDT contact sets are in a Form
C configuration.
Module Power
Check model/serial number label for module operating voltage to
make sure it matches available power.
When using DC power, either polarity is acceptable, but for con-
sistency with similar API products, positive (+) can be wired to
terminal 13 and negative (–) can be wired to terminal 16.
Mounting to a DIN Rail
Install module vertically on a 35 mm DIN rail in a protective enclo-
sure away from heat sources. Do not block air flow. Allow 1" (25
mm) above and below housing vents for air circulation.
1. Tilt front of module downward and position against DIN rail.
2.Clip lower mount to bottom edge of DIN rail.
3. Push front of module upward until upper mount snaps into place.
Removal
1.Push up on the bottom back of the module.
2.Tilt front of module downward to release upper mount from top
edge of DIN rail.
3.The module can now be removed from the DIN rail.
Setpoint and Deadband Adjustments
Relay operation is factory configured. See the model/serial num-
ber label for relay configurations.
The Setpoint potentiometer allows the operator to adjust the level
at which the alarm is activated. This control is adjustable from 0
to 100% of the input range.
The Deadband potentiometer allows the alarm trip and reset
window to be adjusted symmetrically about the setpoint from 1 to
100% of the span. This allows the operator to fine tune the point
at which the alarm trips and resets. The deadband is typically
used to prevent chattering of the relays or false trips when the
process signal is unstable or changes rapidly.
To calibrate the alarm section, set the deadband control to the
minimum (counterclockwise). The deadband will be 1.0% of input
span in this case.
Set the signal source to the desired trip point.
Adjust the setpoint control to the point at which the relay changes
state from a non-alarm to an alarm condition.
Turn the deadband potentiometer clockwise for a larger amount
of deadband. The deadband is symmetrical about the setpoint;
both transition points will change as deadband is increased.
Relay set and reset points will both change if the setpoint or
deadband are changed. Alternately set the setpoint and deadband
until the desired trip and rest points are set.
Output Test Function
When the front test button is depressed it will drive the relays to
their opposite state. A customer-supplied switch connected to
terminals 4 and 8 can also be used to toggle the relays. When
released, the relays will return to their prior states.
This can be used as a diagnostic aid during initial start-up or
troubleshooting, or as a manual over-ride function. The Test but-
ton also resets the relays on models with the HT option.
Operation
The green LoopTracker®input LED provides a visual indication
that a signal is being sensed by the input circuitry of the module.
It also indicates the input signal strength by changing in intensity
as the process changes from minimum to maximum.
If the LED fails to illuminate, or fails to change in intensity as the
process changes, check the module power or signal input wiring.
Note that it may be difficult to see the LEDs under bright lighting
conditions.
The bicolor alarm LED provides a visual indication of the alarm
status. In all configurations, a green LED indicates a non-alarm
condition and a red LED indicates an alarm condition.
In the normal mode of operation, the relay coil is energized in a
non-alarm condition and de-energized in an alarm condition. This
will create an alarm condition if the module loses power. For a
normal acting, non-latching configuration, the alarm will activate
when the input signal exceeds the setpoint (HI alarm) or falls
below the setpoint (LO alarm), then will automatically reset when
the alarm condition no longer exists.
For a reverse acting alarm, the relay coil is de-energized in a non-
alarm condition and energized in an alarm condition. The alarm
activates when the input signal exceeds the setpoint (HI alarm)
or falls below the setpoint (LO alarm), then automatically resets
when the alarm condition no longer exists.
For models with the latching relay option, it will be necessary to
push the Test button or remove power from the module to reset
the alarm, depending on the type of latching option. The alarm will
only reset if the alarm condition no longer exists.
Installation and Setup APD 1700, APD 1720
Module Power
AC or DC +
AC or DC –
1413 15 16
Cu 60/75°C
conductors
14 AWG
max.
Test Input
APD 1700
Frequency Input to
Single Alarm Trip
Loop
Tracker
Deadband
Setpoint
Alarm
Test
APD 1720
Frequency Input to
Dual Alarm Trip
Input
Loop
Tracker
Deadband 1
Setpoint 1
Alarm 1
Deadband 2
Setpoint 2
Alarm 2
–
2 Wire
109 11 12
Signal
Two wire self-generating
9 Signal (+)
11 Common (–)
15 kWtypical
2 Wire
+15
VDC
109 11 12
Sig.
–
Two wire powered
9 Signal
11 Power (+15 VDC)
Some sensors may require
a bleed resistor.
Three wire NPN
9 Signal: Black or White
10 Power (+15VDC):Brown or Red
11 Common: (–) Blue or Black
Load resistor may be required.
–
NPN
+15
VDC
109 11 12
Signal
Three wire PNP
9 Signal: Black or White
10 Power (+15VDC): Brown or Red
11 Common (–) Blue or Black
Load resistor may be required.
–
PNP
+15
VDC
109 11 12
Signal
Relay Wiring
APD 1700
NO C NC
21 3 4
65 7 8
NO C NC
Customer-
Supplied
Remote
Test Switch
Relay Wiring
APD 1720
RLY 1
RLY 2
NO C NC
21 3 4
65 7 8
NO C NC
Customer-
Supplied
Remote
Test Switch
api-usa.com
1220 American Way Libertyville, IL 60048
Phone: 800-942-0315 Fax: 800-949-7502
AABSOLUTEBSOLUTE PPROCESSROCESS IINSTRUMENTSNSTRUMENTS
API maintains a constant effort to upgrade and improve its products.
Specifications are subject to change without notice. See api-usa.com for
latest product information. Consult factory for your specific requirements.
WARNING: This product can expose you to chemicals includ-
ing nickel, which is known to the State of California to cause
cancer or birth defects or other reproductive harm. For more
information go to www.P65Warnings.ca.gov
* Do not make connections to unused terminals!
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
Input
Relay 1
Power
Relay 2
4 & 8 Relay Test4 & 8 Relay Test Wire terminal torque
0.5Nm to 0.6Nm
(4.4 to 5.3 in-lbs)
To maintain full isola-
tion avoid combining
power supplies in
common with input,
output, or unit power.
* Do not make
connections to
unused terminals!

This manual suits for next models

3

Other API Security System manuals

API 1005 G User manual

API

API 1005 G User manual

API 1000 G User manual

API

API 1000 G User manual

Popular Security System manuals by other brands

Visonic POWERMAX - installation instructions

Visonic

Visonic POWERMAX - installation instructions

IRIS Touch 4 NG Series Quick Installation & Maintenance Guide

IRIS

IRIS Touch 4 NG Series Quick Installation & Maintenance Guide

KSB AS1-M Installation, operating and maintenance manual

KSB

KSB AS1-M Installation, operating and maintenance manual

GE INT-22.5R1-24 Operating	 instruction

GE

GE INT-22.5R1-24 Operating instruction

Sonel MPU-1 operating manual

Sonel

Sonel MPU-1 operating manual

aperta A1ECP manual

aperta

aperta A1ECP manual

Alarm Controls Corporation ZAC-32 user guide

Alarm Controls Corporation

Alarm Controls Corporation ZAC-32 user guide

Samsung SDH-B73023BF quick start guide

Samsung

Samsung SDH-B73023BF quick start guide

Wave W10 user guide

Wave

Wave W10 user guide

Allegion Von Duprin 98 Series Service manual

Allegion

Allegion Von Duprin 98 Series Service manual

Arec TP-100 quick guide

Arec

Arec TP-100 quick guide

SuperFish Pond Alarm instructions

SuperFish

SuperFish Pond Alarm instructions

Optex Morse Genesys 824 Alpha owner's manual

Optex Morse

Optex Morse Genesys 824 Alpha owner's manual

Microjack EYES Pro user manual

Microjack

Microjack EYES Pro user manual

Uniden GSHC1000 Series owner's manual

Uniden

Uniden GSHC1000 Series owner's manual

Velleman CCTVPROM12 Quick installation guide

Velleman

Velleman CCTVPROM12 Quick installation guide

Satel APD-200 Quick installation guide

Satel

Satel APD-200 Quick installation guide

Akai ARW100 user manual

Akai

Akai ARW100 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.