5.SERVICESCHEDULE
Table1
TaskPeriodicity
1.Inspectionforvisiblephysicaldamageweekly
2.Satisfactoryoperationtest monthly
3.Checkandcleandustcontaminationevery6months
4.CheckandcleanbaseandheadcontactsandconnectionsAnnually

6.WARRANTY

ThemanufacturerguaranteesproductcompliancewiththeEN54-7:2001.Thewarrantperiodis36
monthsfromthedateofpurchase,providingthatrequirementscoveredinsection5havebeen
observed.










































UniPOSLtd

SHORTCIRCUITISOLATOR6202L







1.INTRODUCTION
Shortcircuitisolator6202Lisdesignedtocutoff(toisolate)ashortcircuitedsegmentinaline
(loop).Inthiswaythevariableunitsñautomaticfiredetectors,manualcallpointsandothers,which
arenotintheshortcircuitedsegmentremainactiveandtheline(loop)protectionlevelishigher.
Whereisolatorsarenotincluded,incaseofashortcircuitthefirecontrolpanelinterruptsthepower
supplyoftheline(loop)andallunitsstopworking.
Asegmentisapartofaloopbetweentwoadjacentisolators.

2.TECHNICALDATA
2.1.Supplyvoltage-(18-26)VDC
2.2.Currentconsumptioninquiescent
state,at26VDC-notmorethan100µA
2.3.Equivalentresistanceofisolatorinaline:
-inquiescentstate-<1Ω
-inalarmstate->6,5kΩ

2.4.Connectiontofirecontrolpanel-two-wire

2.5.Degreeofprotection-IP40

2.6.Operatingtemperaturerange-minus10°—/plus60°—

2.7.Temperaturelimits-minus40°—/plus70°—

2.8.Relativehumidityresistance-(92+3
-2)%at25°—
2.9.Dimensions(baseincl.):
-diameter-∅106mm
-height-48mm
2.10.Weight(baseincl.)-0,150kg


3.STRUCTUREANDFUNCTION
Theshortcircuitisolatorlayoutisseenonfig.16202Lconsistsoftwomainparts:abaseandan
isolatorhead.Thelattercomprisesacircuitboard.Thecontactplatesarefixedtothebase.
Theisolatorheadisfixedonthebasebythemeansofbayonetjoints.Whenlocatingtheisolator
headonthebase,makesurethebenchmarkstandsabout20mmbeforetherespectivebench
markonthebase;thenrotateclockwisetofix.Thebenchmarksshouldfullycoincidewhenfixed.
Option:Aflatpointscrewisprovidedontheadapterheadtopreventunauthorizedremoval.A2
mmtipscrewdriverisrequiredforlockingandunlocking.






TE
ST
Isolatorhead
Base
Leadingbench
marks
LED
LED
Flatpointscrew



Fig.1




Theshortcircuitisolator,connectedbetweentwoadjacentsegments,monitorstheresistanceofthe
segments.Whenresistancevaluereachesafixedlowthreshold,theisolatorswitchesovertoalarm
state.ThesurfaceyellowLEDsilluminateandtheline(loop)powersupply(negativewire)is
interruptedinisolatoríspointofconnection.Whentheresistanceoftheisolatedwiresegmentis
restoredtothenormallimits,theisolatorautomaticallyswitchesovertoitsquiescentstate.The
LEDsextinguishandthepowersupplyisresumed.Isolatordiagramisfullysymmetricalinrelation
totheinputandoutputwiresegment.InLineconfiguration(fig.2.1.)duetoonesidepowersupply
theisolatoriscapabletoisolateshortcircuitdetectedinthesegmentaftertheisolatorinrelationto
thefirecontrolpanel.InLoopconfiguration(fig.2.2.)duetobothsidespowersupplytheisolatoris
activeinbothdirectionsñi.e.theshortcircuitedwiresegmentisisolatedbytwoadjoiningisolators.
WheninLineconfigurationconnectisolatorsatthebeginningofaline;inLoopconfiguration
connectisolatorsatbothloopends;useoneisolatorformaximum32firedetectors.





4.PREPARINGTHEISOLATORFOROPERATION

4.1.Connectiondiagram

Connectiondiagramofisolatorbasetoshieldedfirealarmlineisshownonfig.2.1ñline
configuration,andonfig.2.2ñloopconfiguration.




2
5
1
4
2
1
54
4
5
12
Shield
FS6000Fire
ControlPanel
Firedetector
Address1
IsolatorFiredetector
Address127

Fig.2.1.


1
5
2
4
2
1
54
1
54
2
54
12
5
1
4
2
Shield
Firedetector
Address001
Isolator
Shield
FS6000Fire
ControlPanel
Firedetector
Addressxxx
Firedetector
Address127
Isolator
FS6000Fire
ControlPanel
Fig.2.2.



4.2.Ãounting

Separatethebasefromtheheadbyturningtheisolatorheadinananti-clockwisedirection.
Feedtheconnectioncablethroughthecableentryinthecentreofthebase.Fixthebaseonthe
ceilingusingappropriatefixings.Completethewiringasshownonfig.2.1or2.2.
Replacetheisolatorheadonthebasebyofferingtheisolatorheadtothebaseensuringbench
marksarenomorethan20mmapart.Rotatetheisolatorheadinaclockwisedirectiontocomplete
location.
Locktheisolatorheadtothebasebyscrewingtheflatpointscrew,usinga2mmtipscrewdriver,
ensurenottoovertighten.

4.3.Testing

Accordingtofig.2.1theisolatorissuppliedwithoutputvoltage18VDCñ26VDCandoutput
resistancenotlowerthan20Ω.Terminals4and1aretobeterminatedbyresistor<20Ω.Upon
activationtheyellowLEDisilluminatedandremainsactiveuntilshortcircuitiseliminated.
Exchangethewires,connectedtoterminals1and2.Completethesametestprocedureto
terminals4and2.
Shortcircuitisolatorsaretested,inrealconditions,byterminatingthenegativeandpositivewires
(aftertheisolator)ofthelineorloopconfiguration.

Other UniPOS Security System manuals

UniPOS FD3050 User manual

UniPOS

UniPOS FD3050 User manual

UniPOS 8204 User manual

UniPOS

UniPOS 8204 User manual

UniPOS FD3050Y User manual

UniPOS

UniPOS FD3050Y User manual

Popular Security System manuals by other brands

iSecus G600 user guide

iSecus

iSecus G600 user guide

Honeywell ADEMCO 4110XM user guide

Honeywell

Honeywell ADEMCO 4110XM user guide

DSC New Classic PC585 instruction manual

DSC

DSC New Classic PC585 instruction manual

PATROLLINE HPS 845 manual

PATROLLINE

PATROLLINE HPS 845 manual

Honeywell Ademco VISTA-20P quick start guide

Honeywell

Honeywell Ademco VISTA-20P quick start guide

NETGEAR VueZone Quick install guide

NETGEAR

NETGEAR VueZone Quick install guide

SkyLink SC-100 Guide User instructions

SkyLink

SkyLink SC-100 Guide User instructions

Haake HST-TZ2 Installation and operating manual

Haake

Haake HST-TZ2 Installation and operating manual

WestOz Wireless 9000P owner's manual

WestOz Wireless

WestOz Wireless 9000P owner's manual

Videofied W730 manual

Videofied

Videofied W730 manual

Gira Alarm Connect quick start guide

Gira

Gira Alarm Connect quick start guide

Sony SNT-V304 user guide

Sony

Sony SNT-V304 user guide

Abus SOINT SG1250 installation guide

Abus

Abus SOINT SG1250 installation guide

Watchguard DVR4EONPACK manual

Watchguard

Watchguard DVR4EONPACK manual

Cordes CC-800 instruction manual

Cordes

Cordes CC-800 instruction manual

Kerbl 322084 user guide

Kerbl

Kerbl 322084 user guide

Doberman SE-0154 manual

Doberman

Doberman SE-0154 manual

Bosch LTC 8900 Series user manual

Bosch

Bosch LTC 8900 Series user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.