4
1.0 mechanical setup
This manual contains specific information regarding the
safe installation, operation and maintenance of Armstrong
Design Envelope pumps. Read this manual carefully before
installing or using the product. If clarification is needed on
any point please contact Armstrong quoting the equipment
serial number.
1.1 precautions
1.1.1 instructions for safe use
No installation of this equipment should take place un-
less this document has been studied and understood.
Handling, transportation and installation of this equipment
should only undertaken by trained personnel with proper
use of lifting equipment. See later diagrams for lifting advice.
Refer to the pump nameplate for pump speed, pressure
and temperature limitations. The limits stated must not be
exceeded without written permission from Armstrong.
1.1.2 ambient temperature
Install the Design Envelope unit with adequate ac-
cess for routine maintenance. A minimum of 50 mm
(2") clearance is required at the fan inlet to facilitate
airflow. Where several Design Envelope units are
installed in close proximity, care must be taken to ensure that
there is no re-circulation of exhausted warm air.
To avoid the inverter unit getting overheated, the
ambient temperature is not to exceed 40°c(104°f)
average daily temperature. Operating in higher
ambient temperatures will require derating of the inverter.
Under normal operating conditions the pump surface
temperature may reach 68°c/ 155°f(Restricted Zone) to
80°c/176°f(Unrestricted Zone). Steps should be taken to
minimize contact or warn operators/users that normal op-
erating conditions will be exceeded. In certain cases, where
the temperature of the pumped liquid exceeds the above
stated temperature levels, pump casing temperatures may
exceed 212°f/100°c and not withstanding pump insulation
techniques appropriate measures must be taken to minimize
risk for operating personnel. The ambient temperature for
standard motors must be no greater than 104°f/40°c.
1.1.3 enclosure rating
The standard enclosure rating for Design Envelope 4322 and
Design Envelope 4372 integrated controls is ul Type12/
ipp55. If the pump is to be installed in a wet or dusty
environment, then a higher enclosure rating may be required
(contact Armstrong).
1.1.4 storage
Pumps not immediately placed into service, or removed from
service and stored, must be properly prepared to prevent
excessive rusting. Pump port protection plates must not be
removed until the pump is ready to connect to the piping.
Rotate the shaft periodically (at least monthly) to keep rotat-
ing element free and bearings fully functional.
For long term storage (longer than three months), the pump
must be placed in a vertical position in a dry environment.
Internal rusting can be prevented by removing the plugs at
the top and bottom of the casing and drain or air blow out all
water to prevent rust buildup or the possibility of freezing. Be
sure to reinstall the plugs when the unit is made operational.
Rustproofing or packing the casing with moisture absorb-
ing material and covering the flanges is acceptable. When
returning to service be sure to remove the drying agent from
the pump.
1.1.5 warranty
Armstrong’s warranty period for Design Envelope pumps
is [18] months from date of shipment, or [12] months from
date of installation, whichever comes first. Please refer to
File 9.10us / 9.10c for full terms and conditions. To receive
an additional [6] months of standard coverage, owner may
register the pump unit at
www.armstrongfluidtechnology.com/warrantyregistration
1.1.6 uncrating
Armstrong Design Envelope 4322 & 4372 Vertical In-Line
pumps are thoroughly inspected before shipment to assure
they meet with your order requirements. After removing the
pump from the crate, make sure the equipment is in good
order and that all components are received as called for on
the packing list. Any shortages or damage should be reported
immediately. Use extreme care in handling the unit, placing
slings and hooks carefully so that stress will not be imposed
on the integrated controls, pump or motor. Never place cable
slings around the pump shaft or integrated controls. The hoist
rings should be used to lift the complete pump assembly.
1.1.7 handling design envelope 4322 & 4372
units
To handle Design Envelope 4322 & 4372 units when received
on site, secure the pallet following uncovering the unit, then
hook straps as detailed below, and carefully lift the pumping
unit to stand the pump vertically upright. Lift only suciently
to remove the pallet, then lower onto a flat surface.
The pump and motor unit will free-stand on the casing ribs.
Extra care is required to ensure the integrated controls do not
get damaged during lifting and installation.